Shortest Acceleration/Deceleration (Automatic Acceleration/Deceleration) - Mitsubishi Electric FR-E800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

9.6
Shortest acceleration/deceleration (automatic
acceleration/deceleration)
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
The inverter can be operated with the same conditions as when the appropriate value is set to each parameter even when
acceleration/deceleration time and V/F pattern are not set. This function is useful for operating the inverter without setting
detailed parameters.
Pr.
Name
292
Automatic acceleration/
F500
deceleration
A110
61
Reference current
F510
62
Reference value at
F511
acceleration
63
Reference value at
F512
deceleration
293
Acceleration/deceleration
F513
separate selection
 Shortest acceleration/deceleration (Pr.292 = "1, 11", Pr.293)
• Set this parameter to accelerate/decelerate the motor at the shortest time. This function is useful when the motor needs
to be accelerated/decelerated at a shorter time, such as for a machine, but the designed value of the machine constant is
not known.
• At acceleration/deceleration, this function adjusts the motor to accelerate/decelerate with the maximum inverter output
torque using the Pr.7 Acceleration time and Pr.8 Deceleration time setting as reference. (Pr.7 and Pr.8 settings are not
changed.)
• Use Pr.293 Acceleration/deceleration separate selection to apply the shortest acceleration/deceleration to one of
acceleration and deceleration only.
When "0" (initial value) is set, the shortest acceleration/deceleration is performed for both acceleration and deceleration.
• Set "11" in Pr.292 when a brake resistor or brake unit is connected. The deceleration time can further be shortened.
• When the shortest acceleration/deceleration is selected under V/F control and Advanced magnetic flux vector control, the
stall prevention operation level during acceleration/deceleration becomes 150% (adjustable using Pr.61 to Pr.63). The
setting of Pr.22 Stall prevention operation level and stall level by analog input are used only during a constant speed
operation.
Under Real sensorless vector control and Vector control, the torque limit level (Pr.22, etc.) is applied during acceleration/
deceleration. The adjustments by Pr.61 to Pr.63 are disabled.
• It is inappropriate to use for the following applications.
- Machines with large inertia (10 times or more), such as a fan. Since stall prevention operation is activated for a long
time, this type of machine may be shut off due to motor overloading, etc.
- When the inverter is always operated at a specified acceleration/deceleration time.
Vector
Vector
Initial
Setting range
value
0
1
0
11
7, 8
0 to 500 A
9999
9999
0% to 400%
9999
9999
0% to 400%
9999
9999
0
0
1
2

9.6 Shortest acceleration/deceleration (automatic acceleration/deceleration)

Description
Normal operation
Shortest acceleration/deceleration (without brakes)
Shortest acceleration/deceleration (with brakes)
Brake sequence 1, 2 (Refer to
page
Set the reference current during shortest acceleration/
deceleration.
Rated output current value reference of the inverter
Set the speed limit value during shortest acceleration.
The limit value is 150% (120% for the LD rating).
Set the speed limit value during shortest deceleration.
The limit value is 150% (120% for the LD rating).
Shortest acceleration/deceleration for both acceleration
and deceleration
Shortest acceleration/deceleration for acceleration only
Shortest acceleration/deceleration for deceleration only
9. (F) Settings for Acceleration/Deceleration
1
2
3
4
5
370.)
6
7
8
9
10
209

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents