Bootos And Standard Monitor Os Installation Using Cf Card Or Usb Memory - Mitsubishi Electric GT1695M-XTBD User Manual

Got1000 gt16 series graphic operation terminal
Hide thumbs Also See for GT1695M-XTBD:
Table of Contents

Advertisement

14.3 BootOS and Standard Monitor OS Installation
Using CF Card or USB Memory
There are the following two types for the BootOS, standard monitor OS installation using the CF card or USB
memory.
(1) Installing when starting the GOT
(
14.3.1)
All the OS and project data stored in the CF card are transferred to the GOT when powering on the
GOT. This installing method is effective in the following cases.
This function is available only for CF card.
• The GOT utility cannot be displayed.
• The standard monitor OS is not installed.
(2) Installing using the data control function (Utility)
(
14.3.2)
By operating the utility, select OS or project data stored in the CF card or USB memory and transfer
them to the GOT.
14
14.3 BootOS and Standard Monitor OS Installation Using CF Card or
- 4
USB Memory
Precautions on installing BootOS, standard monitor OS
(1) Installing both BootOS and standard monitor OS
After completing BootOS installation, install standard monitor OS.
When installing BootOS, the built-in flash memory in the GOT is initialized and
goes to the status at factory shipment. (All OS and project data are erased.)
BootOS is installed in the GOT at factory shipment. It is not necessary to install
BootOS when not upgrading it.
(2) Copying project data using CF card or USB memory
After installing BootOS, standard monitor OS, and other OS, download the project
data.
At this time, match the version of the standard monitor OS in the GOT with the
version of the standard monitor OS with which the project data was created.
(3) When OS and project data are in the CF card or USB memory (when using GT
Designer2)
For S.MODE switch-pressing installation, after the OS installation is complete, the
project data is downloaded.
This function is available only for CF card.
When installing with the utility, install the OS and download the project data from
their respective operation screens.
(4) Installation cannot be interrupted.
Do not perform any of the following during a BootOS or standard monitor OS
installation.
Failure to do so may result in installation failure, causing the GOT malfunction.
• Powering off the GOT
• Pressing the reset button of the GOT
• Turning off the CF card access switch of the GOT
• Removing the CF card

Hide quick links: