3.3.2

For GOTs powered from the 24VDC power supply

Item
Input power
24VDC (+25%, -20%)
supply voltage
Power
60W or less
consumption
At backlight
30W or less
off
Inrush current
12A or less (75ms) (maximum load)
Permissible
instantaneous
10 ms or less
power failure time
500Vp-p noise voltage, 1 s noise width (when measuring with a noise simulator under 25 to 60Hz
Noise immunity
noise frequency)
Dielectric
500VDC for 1 minute across power terminals and earth
withstand voltage
Insulation
10M
resistance
Applicable wire
0.75 to 2 [mm²]
size
Applicable
solderless
Solderess terminal for M3 screw RAV1.25-3, V2-S3.3, V2-N3A, FV2-N3A
terminal
Applicable
tightening torque
0.5 to 0.8 [N•m]
(Terminal block
terminal screw)
GT1695M-XTBD
or more across power terminals and earth by a 500V DC insulation resistance tester
3.3.2 For GOTs powered from the 24VDC power supply
Specifications
GT1685M-STBD
40W or less
26W or less
11A or less (40ms)(maximum load)
3.3 Power Supply Specifications