5.4 Control Panel Inside Temperature and Mounting
Angle
When mounting the GOT to a control panel or similar, set the display section as shown below.
When the temperature inside the control panel is 40 to 55°C or less, the mounting angle should be in the
range 60 to 105 degrees.
Display
section
Control panel,
etc.
• The GOT will be deteriorated earlier if it is used at the mounting angle other than the above. Therefore,
the temperature inside the control panel should be within 40°C.
*:
When mounting a multimedia unit (GT16MMMR), MELSECNET/H communication unit (GT15-J71LP23-25,
GT15-J71BR13), or CC-Link communication unit (GT15-J61BT13), the operating ambient temperature must be
reduced 5°C against the maximum values described in general specifications.
5.5 Installation Procedure
The GOT mounting procedure is as follows.
For the panel cutting dimensions of each GOT, refer to the following.
5.2 Panel Cutting Dimensions