IP 265
4.3

Output and Input Data

IP 265 program processing is controlled by the CPU via the external I/O bus.
For each slot, 8 bytes are reserved for the IP 265 in the process image of the outputs (PIQ) and in
the process image of the inputs (PII) of the CPU. 8 bytes of output data can be stored for the IP 265
in the PIQ. The IP 265 on the other hand provides 8 bytes of input data for the CPU for further
evaluation in the PII.
The PIQ can be assigned the following output data:
Word 0:
Control word:
Word 2, 4, 6: Input parameters of the IP 265 user program
The following IP 265 input data can be evaluated in the PII:
Word 0:
Status word:
Word 2, 4, 6: Output parameter of the IP 265 user program
Contents of the PIQ
Byte 0
Control word
Byte 1
Byte 2
Byte 3
Byte 4
Input
parameters
Byte 5
Byte 6
Byte 7
Figure 4-5. Assignment of the PIQ and PII in the CPU
The PIQ and the PII can be written and read
by the CPU user program (normal operation)
with the aid of COM 265 (on-line test)
with the aid of the "FORCE VAR" PLC function
EWA 4NEB 812 6130-02a
Instructions for IP 265,
e.g. "Switch IP 265 to RUN"
Status of the IP 265 or of program scanning,
e.g. "IP 265 in RUN"
Byte 0
Byte 1
Byte 2
Byte 3
Output
data to
Byte 4
IP 265
Byte 5
Byte 6
Byte 7
General Operation
Contents of the PII
Status word
Output
parameters
Input data
for the
CPU
4-7