Single-Phase Overcurrent Protection - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Technical Data

4.7 Single-phase Overcurrent Protection

4.7
Single-phase Overcurrent Protection
Current Elements
High-set current elements
Definite-Time Current Element
The set times are pure delay times.
1)
Secondary values for Ι
2)
Secondary values for "sensitive" measuring input, independent of nominal device current
Operating Times
Pickup/Dropout Times
Frequency Pickup Time
minimum
maximum
Dropout time approx.
Dropout Ratios
Current Elements
Tolerances
Currents
Times
Influencing Variables for the Pickup Values
Power supply direct voltage in range 0.8 ≤ V
Temperature in range 23.00 °F (-5 °C) ≤ Θ
Frequency in range 25 Hz bis 70 Hz
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
466
50-2
T
50-2
50-1
T
50-1
= 1 A; with Ι
= 5 A multiply currents by 5.
Nom
Nom
50 Hz
14 ms
≤ 35 ms
25 ms
approx 0.95 for Ι/Ι
3 % of setting value or 1 % of nominal current at Ι
5 % of setting value or 3 % of nominal current at Ι
1 % of setting value or 10 ms
/V
PS
PSNom
≤ 131.00 °F (55 °C)
amb
0.05 A to 35.00 A
1)
0.003 A to 1.500 A
2)
or ∞ (element disabled)
0.00 s to 60.00 s
or ∞ (no trip)
0.05 A to 35.00 A
1)
0.003 A to 1.500 A
2)
or ∞ (element disabled)
0.00 s to 60.00 s
or ∞ (no trip)
60 Hz
13 ms
≤ 35 ms
22 ms
≥ 0,5
Nom
≤ 1.15
1 %
0.5 %/10 K
1 %
1 %
1 %
C53000-G1140-C207-8, Edition 08.2016
Increments 0.01 A
Increments
0.001 A
Increments 0.01 s
Increments 0.01 A
Increments
0.001 A
Increments 0.01 s
= 1 A or 5 A
Nom
= 0.1 A
Nom
SIPROTEC 4, 7SJ62/64, Manual