[ablaufdiagramm-2-malige-wiedereinschaltung-erfolgreich-260602-kn, 1, en_US]
Figure 2-102
The following figure shows an example of a timing diagram showing for two unsuccessful reclosing shots,
with no additional reclosing of the circuit breaker.
The number of reclose commands initiated by the automatic reclosure function are counted. A statistical
counter is available for this purpose for the first and all subsequent reclosing commands.
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Timing diagram showing two reclosing shots, first cycle unsuccessful, second cycle successful
Functions
2.16 Automatic Reclosing System 79