Page 1
Preface Open Source Software Table of Contents SIPROTEC 4 Introduction Overcurrent Time Protec- Functions tion 7SJ80 Mounting and Commissioning V4.7 Technical Data Ordering Information and Accessories Manual Terminal Assignments Connection Examples Current Transformer Requirements Default Settings and Protocol-dependent Functions Functions, Settings, Information...
Page 2
Although including rights created by patent grant or registration of a Siemens AG has made best efforts to keep the document as utility model or a design, are reserved. precise and up-to-date as possible, Siemens AG shall not...
• As well as a compilation of the most significant data for advanced users → Appendix. General information with regard to design, configuration, and operation of SIPROTEC 4 devices are set out in the SIPROTEC 4 System Description /1/ SIPROTEC 4 System Description.
Page 4
Preface Additional Support For questions about the system, please contact your Siemens sales partner. Support Our Customer Support Center provides a 24-hour service. Phone: +49 (180) 524-7000 Fax: +49 (180) 524-2471 E-Mail: support.energy@siemens.com Training Courses Inquiries regarding individual training courses should be addressed to our Training Center:...
Page 5
Possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are additionally written in italics. The same applies to the options of the menus. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 6
Formation of one analog output signal from a number of analog input signals Limit stage with setting address and parameter designator (name) Timer (pickup delay T, example adjustable) with setting address and parameter designator (name) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product.
Page 16
Trip/Close Tests for the Configured Operating Devices..........350 3.3.15 Creating Oscillographic Recordings for Tests.............. 350 Final Preparation of the Device..................352 Technical Data............................353 General Device Data......................354 4.1.1 Analog Inputs......................354 4.1.2 Auxiliary voltage......................354 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 17
Ordering Information 7SJ80 ................... 426 Accessories........................431 Terminal Assignments..........................433 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting ......................434 Connection Examples..........................441 Connection Examples for Current and Voltage Transformers..........442 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Introduction The device family SIPROTEC 7SJ80 devices is introduced in this section. An overview of the devices is presented in their application, characteristics, and scope of functions. Overall Operation Application Scope Characteristics SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
It consists of filters that are optimized for measured- value processing with regard to bandwidth and processing speed. The analog-to-digital (AD) transformer group consists of an analog-to-digital converter and memory compo- nents for the transmission of data to the microcomputer. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 21
Voltage dips may occur if the voltage supply system (substation battery) becomes short-circuited. Usually, they are bridged by a capacitor (see also Technical Data). A buffer battery is located under the flap at the lower end of the front cover. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
1.2 Application Scope Application Scope The multi-function numerical overcurrent protection SIPROTEC 4 7SJ80 is used as protection, control and monitoring unit for busbar feeders. For line protection, the device can be used in networks with grounded, lowresistance grounded, isolated or a compensated neutral point structure. It is suited for networks that are radial and supplied from a single source, open or closed looped networks and for lines with sources at both ends.
Page 23
The USB DIGSI interface on the front cover serves for local communication with a PC. By means of the SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this operator interface, such as specifying and modifying configuration parameters and settings, configuring user-specific logic functions, retrieving operational messages and measured values, inquiring device conditions and meas- ured values, issuing control commands.
• Three definite time overcurrent protective elements and one inverse time overcurrent protective element applicable for grounded or high-resistance grounded systems • For inverse-time overcurrent protection, selection from various characteristics of different standards SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 25
• Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are independently adjustable • Insensitive to harmonics and abrupt phase angle changes • Adjustable undervoltage threshold. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 26
Detects and accumulates intermittent ground faults • Tripping after configurable total time. Directional intermittent ground fault protection • Detects intermittent ground faults • Direction determination • Tripping after settable number of intermittent re-ignitions SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 27
• Measurement also possible via transformer without external intermediate matching transformer • Measuring voltages optionally phase–to–phase or phase–to–ground. Phase Rotation • Selectable ABC or ACB by setting (static) or binary input (dynamic). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 28
B (e.g. of SICAM or LSA), or via the user interface (using a personal computer and the DIGSI oper- ating software) • Feedback of switching states via the switch auxiliary contacts • Plausibility monitoring of the circuit breaker position and check of interlocking conditions. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Functions This chapter describes the numerous functions available on the SIPROTEC 4 device 7SJ80. It shows the setting possibilities for each function in maximum configuration. Information with regard to the determination of setting values as well as formulas, if required, are also provided.
USB port on the device front or to port A or port B on the bottom side of the device depending on the device version (ordering code). The operation via DIGSI is explained in the SIPROTEC 4 System Description. The Device Configuration dialog box allows you to adjust your device to the specific system conditions.
Page 31
Setting of the flexible function is done in DIGSI under “Parameters”, “Additional Functions” and “Settings”. The configuration is done, as usual, under “Parameters” and “Masking I/O (Configuration Matrix)”. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Enabled E Flt(ext) Disabled Disabled Earth Fault(extend) EPTR Trans. Neutral Disabled Disabled 46 Negative Sequence Protection TOC ANSI TOC IEC Definite Time Disabled No ambient temp 49 Thermal Overload Protection No ambient temp SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 33
Flexible Function 10 Flexible Function 11 Flexible Function 12 Flexible Function 13 Flexible Function 14 Flexible Function 15 Flexible Function 16 Flexible Function 17 Flexible Function 18 Flexible Function 19 Flexible Function 20 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If you want the time synchronization of the device to be performed via port A, set the parameters required for this purpose at the following addresses: Address 660 IP adr[0](Prim) to 663 IP adr[3] IP-Addresses 0 to 3, NTP primary (Prim) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Client activ Daylight Set Daylight Set Offset TZ/min -1440 .. 1440 min 60 min Offset for time zone in minutes Offset DayT/min -1440 .. 1440 min 60 min Offset for daylight in minutes SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
>Synchronize Internal Real Time Clock >Reset LED >Reset LED >Test mode >Test mode >DataStop >Stop data transmission Device OK Device is Operational and Protecting ProtActive IntSP At Least 1 Protection Funct. is Active SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The device requires certain basic data regarding the protected equipment so that the device can adapt to its desired application. These may be, for instance, nominal power system and transformer data, measured quan- tity polarities and their physical connections, breaker properties (where applicable) etc. There are also certain SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
NO. This setting exclusively affects the function “Current Sum Monitoring” (see Section 2.11.1 Measurement Supervision). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 39
The sensitive ground current at the fourth current input is referred to Ι The setting must be selected according to the system requirements. The following table gives an overview of how the protection functions are assigned to the ground current inputs for the special connection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 40
The table gives an overview of the functions that can be activated for the corresponding connection type (depends also on the ordering number). The functions which are not shown are available for all connection types. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 41
217 Ignd-CT PRIM and 204 CT PRIMARY must be set to the same value. If the device features a sensitive ground current input, parameter 218 Ignd-CT SEC is set to 1 A by default. In this case, the setting cannot be changed. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 42
The threshold value setting applies to all three phases, and must take into consideration all used protection functions. The pickup threshold for the breaker failure protection is set separately (see 2.17.2 Setting Notes). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter Setting Options Default Setting Comments CT Starpoint towards Line towards Line CT Starpoint towards Busbar SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 44
Thresh. BI 176V Thresh. BI 176V Threshold for Binary Input Thresh. BI 88V Thresh. BI 19V Threshold BI 5 Thresh. BI 176V Thresh. BI 176V Threshold for Binary Input Thresh. BI 88V Thresh. BI 19V SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 45
Control Device T 52 BREAKTIME 1 .. 600 ms 80 ms Breaktime (52 Breaker) T 52 OPENING 1 .. 500 ms 65 ms Opening Time (52 Breaker) Holmgr. for Σi Holmgreen-conn. (for fast sum-i-monit.) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Phase rotation ABC 5148 Rotation ACB Phase rotation ACB Oscillographic Fault Records 2.1.4 The Multifunctional Protection with Control 7SJ80 is equipped with a fault record memory. The instantaneous values of the measured values SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
251 CT Connect., the ground current Ι measured with the second current trans- former is indicated under track Ι . The ground current detected by the fourth current transformer is indi- cated under track Ι SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Capture Time via Binary Input 2.1.4.4 Information List Information Type of Comments Informa- tion FltRecSta IntSP Fault Recording Start >Trig.Wave.Cap. >Trigger Waveform Capture Wave. deleted OUT_Ev Waveform data deleted 30053 Fault rec. run. Fault recording is running SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(address 103) when the function extent is configured. For the setting of the function parameters, each of the required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System Description gives further information on how to copy setting groups or reset them to their status at delivery and also how to change from one setting group to another.
20 kV free line 120 mm with the following data: /s = 0.88 Ω/km (1.42 Ω/mile) Zero sequence resistance /s = 1.26 Ω/km (2.03 Ω/mile) Zero sequence reactance /s = 0.24 Ω/km (0.39 Ω/mile) Positive sequence resistance SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 51
In the following, the same line as illustrated in the example for ground impedance ratios (above) and addi- tional data on the voltage transformers will be used: Current Transformers 500 A/5 A Voltage Transformers 20 kV/0.1 kV The secondary reactance per unit length is calculated as follows: [xsekund-beispiel-260602-kn, 1, en_US] SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 52
The current threshold entered in address 1107 I MOTOR START limits the operating range of the overload protection to larger current values. The thermal replica is kept constant for as long as this threshold is exceeded. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
>Trip via Binary Input 18421 Trip via GOOSE ExSP Trip via GOOSE 18423 Direct Trip Direct Trip 18424 PI Trip NC PI Trip NC(ON,if Device ok & No Trip) 18425 >DDI Open >DDI Open status SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Even when installed in heteroge- neous environments, SIPROTEC 4 relays therefore provide for open and interoperable operation. Parallel to the process control integration of the device, this interface can also be used for communication with DIGSI and for inter-relay communication via GOOSE.
The following figures give an example of logic diagrams for the high-set elements 50-2 PICKUP or 50N-2 PICKUP. They also apply analogously to the high-set elements 50-3 PICKUP and 50N-3 PICKUP. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 58
If parameter MANUAL CLOSE is set to 50-2 instant. or 50-3 instant. and manual close detection is used, a pickup causes instantaneous tripping, even if the element is blocked via binary input. The same applies to 79 AR 50-2 inst. or 79 AR 50-3 inst. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
50-1 or 50N-1 has been exceeded again. If the threshold is exceeded again during the dropout delay time, the time is canceled. However, the trip-command delay time 50-1 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 60
The same applies to 79 AR 50-1 inst. The dropout delay only operates if no inrush was detected. An incoming inrush will reset a running dropout delay time. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 61
The dropout delay only functions if no inrush was detected. An incoming inrush will reset a running dropout time delay. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Pickup values of elements 51 (phase currents) and 51N (ground current) and the relevant time multiplicators may be set individually. The following two figures show the logic diagrams for the inverse time overcurrent protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 63
If parameter MANUAL CLOSE is set to 51 instant. and manual close detection applies, the trip is initiated as soon as the pickup conditions arrive, even if the element is blocked via a binary input. The same applies to 79 AR 51N inst. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 64
(95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in idle state. Disk emulation offers advantages when the overcurrent relay elements must be coordinated with conven- tional electromechanical overcurrent relays located towards the source. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
("Fuse Failure Monitor"). The following two figures show the logic diagrams for the inverse time overcurrent protection with under- voltage consideration. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
This dynamic pickup value changeover fuction is common to all overcurrent elements and is described in Section 2.4 Dynamic Cold Load Pickup. The alternative pickup values can be set individually for each element of the time overcurrent protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The inrush restraint has an upper limit: Above this (via adjustable parameter 2205 I Max) current blocking is suppressed since a high-current fault is assumed in this case. The following figure shows the inrush restraint influence on the time overcurrent elements including cross- blocking. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The pickup annunciations of the individual phases (or ground) and the individual element are combined with each other in such a way that the phase information and the element that has picked up are issued. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If the fault is a simple ground fault in B, the element will not pick up. A double ground fault is assumed only after pickup on A or C, causing the element to pick up and trip after the delay time has elapsed. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Pickup signals output by the load-side protective relay are used as input message >BLOCK 50-2 via a binary input at the feeder-side protective relay. [rueckwverr-150502-kn, 1, en_US] Figure 2-16 Reverse interlocking protection scheme SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The pickup current of the high-set element 50-2 PICKUP or50-3 PICKUP can be set at address 1202 or 1217. The corresponding delay time 50-2 DELAY or 50-3 DELAY can be configured under address 1203 or SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 73
The selected time is an additional delay time and does not include the operating time (measuring time, dropout time). The delay can also be set to ∞. In this case, the element will not trip after pickup. However, SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 74
The corresponding time multiplier for an IEC characteristic is set at address 1208 51 TIME DIAL and in address 1209 51 TIME DIAL for an ANSI characteristic. It must be coordinated with the time coordination chart of the system. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 75
356 ). The internal "Manual close" signal remains active as long as the binary input signal >Manual Close is active, but at least for 300 ms (see the following logic diagram). To enable the device to react properly on SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 76
50N-2 or 50N-3 will be blocked. At address 1314 50N-2 active or 1316 50N-3 active active it can be specified whether the 50N-2 or the 50N-3 element should be influenced by the SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
50-2 active Always Always 50-2 active with 79 active 1215A 50 T DROP-OUT 0.00 .. 60.00 sec 0.00 sec 50 Drop-Out Time Delay 1216A 50-3 active Always Always 50-3 active with 79 active SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 78
Very Inverse Very Inverse ANSI Curve Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. 1313A MANUAL CLOSE 50N-3 instant. 50N-2 instant. Manual Close Mode 50N-2 instant. 50N-1 instant. 51N instant. Inactive SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
50/51 PH BLK 50/51 O/C is BLOCKED 1753 50/51 PH ACT 50/51 O/C is ACTIVE 1756 50N/51N OFF 50N/51N is OFF 1757 50N/51N BLK 50N/51N is BLOCKED 1758 50N/51N ACT 50N/51N is ACTIVE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 80
51 Disk emulation Pickup 1867 51N Disk Pickup 51N Disk emulation picked up 7551 50-1 InRushPU 50-1 InRush picked up 7552 50N-1 InRushPU 50N-1 InRush picked up 7553 51 InRushPU 51 InRush picked up SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 81
Phase A InRush picked up 7566 Ib InRush PU Phase B InRush picked up 7567 Ic InRush PU Phase C InRush picked up 10034 50-3 BLOCKED 50-3 BLOCKED 10035 50N-3 BLOCKED 50N-3 BLOCKED SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(or object to be protected). This is not necessarily identical with the direction of the normal load flow, as shown in Figure 2-19. [ueberstromzeitschutz-bei-paralleltransformatoren-020626-kn, 1, en_US] Figure 2-19 Overcurrent protection for parallel transformers SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
These elements can be blocked by the automatic reclosing function (79 AR). The following figure gives an example of the logic diagram for the high-set elements 67-2 of the phase currents. The high-set element 67-3 is structured identically. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
When the relevant delay times 67-1 DELAY, 67N-1 DELAY have expired, a tripping command is issued SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 86
Each of these elements can be directional or non-directional (non-directional from V4.7 on). These elements can be blocked by the automatic reclosure function (AR). The following figure shows by way of an example the logic diagram for the directional overcurrent element 67-1. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 87
The same applies to 79 AR 67-1 instantaneous. The dropout delay does only function if no inrush was detected. An approaching inrush resets an already running dropout time delay. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The following figure shows by way of an example the logic diagram for the 67-TOC relay element of the direc- tional inverse time overcurrent protection of the phase currents. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(Dir Phase and Dir Ground) can be blocked, see logic diagrams. Undervoltage protection, sensitive ground fault detection and synchronization are also blocked in this case. For additional information on the operation of the fuse failure monitor, see Section 2.11.1 Measurement Supervision. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Then the directional ground element will not initiate a trip signal. The directional ground element cannot be applied when only two current transformers are used. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 92
V ref,rot ±86° and reaches the undefined area. If the vector leaves the undefined area in direction of the forward area SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 93
Figure 2-29 shows the treatment of the reference voltage for the directional ground element using the nega- tive sequence values based on a single-phase ground fault in phase A. As reference voltage, the negative SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
67-1 will block one of the non-directional overcurrent elements (50-1, 50-TOC) of devices at the opposite end of the same feeder. In addition, a "Reverse" message is generated and transmitted via the auxil- iary voltage loop to the relay located at the opposite end of the line. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Thus, at address 1601 FCT 67N/67N-TOC, directional ground time overcurrent protection may be switched ON or OFF independent of the directional phase time overcurrent protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 96
0° (remote fault) and 30° (close-up fault) depending on the collapse of the faulty voltage. This can be taken into account with a mean value of 15°: Ref. volt. angle of rotation = 90 - φ -15° Phase directional element (phase- to-phase fault) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 97
Quantity Selection for Direction Determination for the Directional Ground Element Parameter 1617 67N POLARIZAT.can be set to specify whether direction determination is accomplished from the zero sequence quantities or ground quantities (with VN and IN) or from the negative sequence SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 98
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of 7SJ80 may be used for the 67N-1 relay element (67N-1 PICKUP) (for more information see margin heading "Inrush Restraint"). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 99
1.1 times the setting value is present. If Disk Emulation was selected at address 1610 67N-TOC DropOut, reset will occur in accordance with the reset curve as for the existing nondirectional time overcurrent protection described in Section 2.2 Overcurrent Protection 50, 51, 50N, 51N. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 100
The manual closing information must be allocated via CFC (interlocking task-level) using the CMD_Information block, if the internal control function is used. [handein-260602-kn, 1, en_US] Figure 2-33 Example for the generation of a manual close signal using the internal control function SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 103
67N-2 measurement of True RMS 1621A 67N-1 MEASUREM. Fundamental Fundamental 67N-1 measurement of True RMS 1622A 67N-TOC MEASUR. Fundamental Fundamental 67N-TOC measurement of True RMS 1623 67N-2 Direction Forward Forward 67N-2 Direction Reverse Non-Directional SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Phase A reverse 2633 Phase B reverse Phase B reverse 2634 Phase C reverse Phase C reverse 2635 Ground forward Ground forward 2636 Ground reverse Ground reverse 2637 67-1 BLOCKED 67-1 is BLOCKED SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 105
2696 67/67N TRIP 67/67N TRIP 2697 67-3 picked up 67-3 picked up 2698 67N-3 picked up 67N-3 picked up 2699 67-3 Time Out 67-3 Time Out 2700 67N-3 Time Out 67N-3 Time Out SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If the dynamic setting values were activated via the binary input >ACTIVATE CLP or the signal "79M Auto Reclosing ready" and this cause drops out, the "normal" settings are restored immediately, even if a pickup is the result. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 107
"normal" settings are effective. The following figures show the timing sequenceand the logic diagram of the dynamic cold load pickup feature. [zeitablaeufe-der-dynamischen-parameterumschaltung-260602-kn, 1, en_US] Figure 2-34 Timing charts of the dynamic cold load pickup function SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Contact can only be selected if the device receives information regarding the switching state of the circuit breaker via at least one binary input. The option 79 ready modifies dynamically the pickup thresholds of the directional and non-directional time overcurrent protection when the automatic reclosing function is ready. To SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
2106 67Nc-TOC T-DIAL (for IEC characteristics) or 2107 67Nc-TOC T-DIAL (for ANSI charac- teristics) for the directional inverse time overcurrent protection element. Settings 2.4.3 The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon- dary nominal current of the current transformer. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PICKUP element by at least factor 2 · √2. [ueb-einph-kennlinie-020926-rei, 1, en_US] Figure 2-36 Two-stage characteristic of the single-phase time-overcurrent protection The following figure shows the logic diagram of the single-phase overcurrent protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The right-hand example depicts an ungrounded transformer winding or an ungrounded motor/generator where the grounding of the system is assumed somewhere else. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 114
Resistance R is sized such that, even with the very lowest ground fault current to be detected, it generates a secondary voltage, which is equal to half the saturation voltage of current transformers (see also notes on "Dimensioning" in Subsection 2.5.4 Setting Notes). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The knee-point voltage can be approxi- mately calculated from the rated data of a CT as follows: [ueb-einph-saetigungsspannung-021026-rei, 1, en_US] Knee-point voltage SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 117
CT1 transmits current Ι . CT2 shall be saturated. Because of saturation the transformer represents a low-resis- tance shunt which is illustrated by a dashed short-circuit line. R >> (2R ) is a further prerequisite.. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 118
Since, furthermore, the resistance shall be high-resistance (condition: R >> 2R , as mentioned above), the inherent resistance of the measuring input can be neglected. The resistance is then calculated from the pickup current Ι and half the knee-point voltage: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 119
For the 1 A current transformer 800/1 with 40 kA primary Ι 50 A secondary. k,max,int This yields a short-time load over 0.5 s for the series resistor of: [fohochimpp-5a-20120514, 1, en_US] SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 120
(address 2703 50 1Ph-2 PICKUP = ∞ ). The trip command of the element can be delayed in address 2707 50 1Ph-1 DELAY. It is normally set to 0. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
None (direct evaluation of the voltage connected to Direct voltage value Vph-g, VSyn voltage input 1) Undervoltage Vphph (smallest phase-to-phase voltage) Phase-to-phase voltage Van, Vbn, Vcn Vph-n (smallest phase-to-ground voltage) Phase-to-ground voltage V1 (positive sequence voltage) Positive sequence voltage· √3 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The time delay is not dependent on the magnitude of the overvoltage. The dropout ratio for the two overvoltage elements (= V ) can be set. dropout value pickup value The following figure shows the logic diagram of the overvoltage protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
27-1 DELAY. As long as the voltage remains below the dropout setting, reclosing is blocked. Only after the fault has been cleared, i.e. when the voltage increases above the dropout level, the element drops out and allows reclosing of the circuit breaker. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 125
MIN) is exceeded. Pickup of the protection function is also reset by the action of the AND-combination of voltage and current. As a consequence, energization is admitted anew when the minimum command time elapsed. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 126
(unlike Figure 2-46), the desired pickup of the element will be delayed by 60 ms. The following figure shows the logic diagram of the undervoltage protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Setting Notes General Voltage protection is only effective and accessible if address 150 27/59 is set to Enabled during configura- tion of protection functions. If this function is not required, then Disabled is set. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 128
The time delays of the overvoltage elements are entered at addresses 5004 59-1 DELAY and 5007 59-2 DELAY, and should be selected in such manner that they make allowance for brief voltage peaks that are generated during switching operations and also enable clearance of stationary overvoltages in due time. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 129
(configured pickup threshold) ≤ 225 V with calculation of the measured values from the connected voltages (e.g. calculated phase-to-phase voltages from the connected phase-to-ground voltages). The minimum hysteresis is 0.6 V. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The inverse time element is dependent on the ordered device version. It operates with IEC or ANSI character- istic tripping curves. The curves and associated formulas are given in the Technical Data. When programming SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 133
Logic The following figure shows the logic diagram for the negative sequence protection function. The protection may be blocked via a binary input. This resets pickup and time elements and clears measured values. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 134
The configured dropout times do not influence the tripping times of the inverse time elements as these depend dynamically on the measured current value. For purposes of dropout coordination, disc emulation is used with electro-mechanical relays. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
"CTR" is taken into consideration. Consider a transformer with the following data: Base Transformer Rating = 16 MVA NomT Primary Nominal Voltage = 110 kV = 110/20) Secondary Nominal Voltage = 20 kV SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
When a frequency element drops out, the tripping command is immediately terminated, but not before the minimum command duration has elapsed. Each of the four frequency elements can be blocked individually via binary inputs. The following figure shows the logic diagram for the frequency protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PICKUP is set individually as overfrequency or underfrequency protection or set to OFF, if the element is not required. Minimum Voltage Address 5402 Vmin is used to set the minimum voltage. Frequency protection is blocked as soon as the minimum voltage is undershot. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The inrush blocking of the QU protection can then be activated via parameter Inrush blk. The overcurrent protection detects the inrush. The QU protection evaluates the inrush indications of the overcurrent protection (see Figure 2-15). The following figure shows the logic diagram of the QU protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 143
The tripping of the protection stages of voltage and frequency protection is always included. The following figure shows the logic diagram of the QU protection for reconnection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The release current is entered at address 5502 I-Release. The default setting is at 10 % of the rated current. The threshold is one of the pickup criteria for tripping. At address 5503 Inrush blk you can activate the blocking when inrush has been detected. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
For a motor that is switched off, the 7SJ80 increases the time constant τ by a programmable factor (kτ factor). The motor is considered to be off SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 148
The first option is the default setting (see /5/ Additional description for the protection of explosion-protected motors of protection type increased safety “e”). The following figure shows the logic diagram for the overload protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Logic diagram of the overload protection 2.10.2 Setting Notes General Overload protection is only in effect if address 142 49 is set to No ambient temp during configuration. If this function is not required, select Disabled. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 150
NomCT prim NOTE The setting for 49 K-FACTOR (address 4202) has always to be made as a secondary value. Example: Belted cable 10 kV, 150 mm Permissible continuous current = 322 A Ι SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 151
(kept constant) as soon as the current exceeds the threshold value 1107 I MOTOR START. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Σ I THRESHOLD (address 8106) and Σ I FACTOR (address 8107) are setting parameters. The component Σ I FACTOR · Σ | Ι | takes into account the permissible current proportional ratio errors of the input transducers SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 155
The settings CT PRIMARY (address 204) and Ignd-CT PRIM (address 217) must be the same. • The settings CT SECONDARY (address 205) and Ignd-CT SEC (address 218) must be the same. The following logic diagram illustrates the operational mode of the current sum monitoring. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Error Offset ) and integrated into the warning group indication (160). As increased offset values impair the measurements, we recommend sending the device to the OEM plant for corrective action should this indication persist. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(see Figure 2-70). Both parameters can be set. The dropout ratio is about 97%. This fault is signalled after settable delay time with Fail V balance . SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The measuring voltage failure detection function - referred to as “Fuse Failure Monitor” (FFM) - only operates if parameter 213 VT Connect. 3ph is set to Van, Vbn, Vcn or Vab, Vbc, VGnd. With all other voltage transformer connection modes, FFM is not operative. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 159
The generation of the internal signal “Alarm FFM” for the operation in isolated systems is shown in Figure 2-60. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 160
If this part of the FFM logic picks up, the internal signal “Alarm FFM” is gener- ated. The processing of this signal is shown in Figure 2-59. NOTE In isolated systems, only the following logic is used. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 161
Fault-free Case: [u2-u1-fehlerfreier-fall-020828-ho, 1, en_US] If a fault occurs in the voltage transformer secondary system, the following rules apply to the Single-phase Failure: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
A blocking of the protection functions is however not effected. This is done by the measuring voltage failure detection. The “Broken Wire” monitoring is also active during a fault. The function may be enabled or disabled. The following logic diagram shows how “Broken Wire” monitoring functions. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Address 8105 BAL. FACTOR I is the associated symmetry factor; that is, the slope of the symmetry characteristic curve. In address 8111 T BAL. I LIMIT you set the delay time for fault message no. 163 Fail I balance . SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
VT BROKEN WIRE VT broken wire supervision 5202 Σ V> 1.0 .. 100.0 V 8.0 V Threshold voltage sum 5203 Vph-ph max< 1.0 .. 100.0 V 16.0 V Maximum phase to phase voltage SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Supervision with Two Binary Inputs When using two binary inputs, these are connected according to Figure 2-62, parallel to the associated trip contact on one side, and parallel to the circuit breaker auxiliary contacts on the other. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 167
2-63). The repeated measurements determine the delay of the alarm message and avoid that an alarm is output during short transition periods. After the malfunction in the trip circuit is cleared, the fault annuncia- tion is reset automatically after the same time period. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 168
Alarm Delay. A message is only released after expiry of this time. After clearance of the fault in the trip circuit, the fault message is automatically reset. [7sj6x_ausloesekreis_1_binaerein-050906-he, 1, en_US] Figure 2-65 Logic diagram of trip circuit supervision with one binary input SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Information for dimensioning resistor R is given in the Chapter "Installation and Commissioning" under Config- uration Notes in the Section "Trip Circuit Supervision". 2.11.2.3 Settings Addr. Parameter Setting Options Default Setting Comments 8201 FCT 74TC 74TC TRIP Circuit Supervision SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(processor failure) Working memory ROM Internal (hardware) Relay aborts restart, LED blinkt drops device shutdown Program memory RAM Internal (hardware) During boot sequence LED "ERROR" drops Detection during oper- LED "ERROR" ation: Restart attempt SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 171
Appendix F.4 Group Alarms. In this case, it must be noted that message 160 Alarm Sum Event is only issued when the measured value monitoring functions (8101 MEASURE. SUPERV) are activated. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
For this purpose, the individual phase-to-ground voltages are measured or calculated, irre- spective of the connection type of the voltage transformers. If the voltage magnitude for any given phase falls SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 173
The following figure illustrates an example using a complex vector diagram in which the displacement voltage is the reference magnitude of the real axis. The active part 3Ι0 of current 3Ι0 is calculated with reference real SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 174
+45° (see the following Figure). Furthermore the directional limit lines may be rotated by 90° to determine ground faults and their direction in isolated systems. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 175
The pickup of the displacement voltage element V starts the ground fault recording. As the pickup of the V element drops out, fault recording is terminated (see logic diagrams Figure 2-71 Figure 2-72). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 176
Parameter PU CRITERIA specifies, whether a fault is generated by means of the AND-function or the ORcom- bination of displacement voltage and pickup of the ground current. The former may be advantageous if the pickup setting of displacement voltage element V was chosen to be very low. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 177
Functions 2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s) [7sj80-erdfehler-ue-cos-sin-20061206, 1, en_US] Figure 2-71 Logic diagram of the V > element for cos-φ -/sin-φ measurement SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If the device is only provided with phase-to- phase voltages, it is not possible to calculate a displacement voltage from them. In this case, the direction cannot be determined. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 179
50Ns-2 Phi), the center of the zone with reference to the displacement voltage V is set. Via the angle Δϕ (parameter 3155 50Ns-1 DeltaPhi or 3152 50Ns-2 DeltaPhi), the zone is extended to both sides of the center. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 180
To support the commissioning, a message is issued if the current and voltage threshold of an element is exceeded but the ground fault phasor is not inside of the trip range. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 181
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s) [7sj80-aktiv-empf-erdfehler-20061218, 1, en_US] Figure 2-75 Activation of the sensitive ground fault detection for V0/I0-ϕ measurement [7sj80-erdfehler-ue-u0-i0-messung-20061206, 1, en_US] Figure 2-76 Logic diagram during V0-/Ι0 -φ measurement, part 1 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The functions can only be used as an alternative. They work independently from the setting of address 130 S.Gnd.F.Dir.Ch. The following figure shows the used input variables and the activation criteria of the functions. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
You can find information on the setting values in Section 2.12.5 Setting Notes. Logic The following figure shows the logic diagram of the function EPTR. [7sj80-lo-eptr, 2, en_US] Figure 2-79 Logic of the Ground-Fault Detection EPTR SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Petersen coil that flows via the measuring point. Therefore, on the faulty cables a clear "forward" decision is made whereas in other feeders either "reverse" direction is sent back or no measurement is carried out in case ground current is too low. Definitely the faulty line can be determined clearly. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
At address 3101 Sens. Gnd Fault, the function ON or OFF can be set to either ON with GF log or Alarm Only. If settings ON and ON with GF log are applied, tripping is also possible, otherwise a fault log SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 186
The default setting of current values is ∞. They are, therefore, not enabled — and no pickup or tripping of these protective functions will occur. Up to 20 value pairs (current and time) may be entered at address 3131 M.of PU TD. The device then approximates the characteristic, using linear interpolation. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 187
40 V. Setting VPH MAX must be greater than the maximum expected operational phase-to-ground voltage, but less than the minimum expected operational phase-to-phase voltage. For V = 100 V, approxi- mately 75 V is a typical setting. These settings have no significance in a grounded system. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 188
With regard to a ground fault in a ungrounded or resonant-grounded system, nearly the entire displacement voltage appears at the device terminals, therefore the pickup setting is not critical, and typically lies between SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 189
RELEASE DIRECT. (3Ι0 DIR.), MEAS. METHOD = SIN φ the reactive (capacitive) component of the ground current with respect to the displacement voltage is most relevant for the current value RELEASE DIRECT. (3Ι0 DIR.) (Figure 2-84). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 190
3161 α2 red.dir.area (see Figure 2-84). Siemens recommends using the default setting of 2° (this corresponds to the behavior of versions without this setting option). In a grounded system in feeders with very high capacitive current, it can be reasonable to set a slightly larger angle α1 to prevent erroneous pickup due to transformer and algorithm tolerances.
Page 192
3513 T max, maximum delay when the current threshold TNP I Tmax picks up. T min and T max determine the range of the tripping time. With address 3514 T Function you set the time delay for the complete function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Phase Vph Min 3107 VPH MAX 10 .. 100 V 75 V L-Gnd Voltage of Unfaulted Phase Vph Max 3109 64-1 VGND 1.8 .. 200.0 V; ∞ 40.0 V 64-1 Ground Displacement Voltage SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Intermitt.EF is issued. This prevents a burst of messages. If the message is allocated to an LED or a relay, this limitation does not apply. This is accomplished by doubling the message (message numbers 6924, 6926). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 199
(and reported to the system interface) so often until the number of pickups IIE Fault det has reached the value set for parameter Nos.det.. When this happens, the message Intermitt.EF is issued and IIE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 200
67-TOC element picked up 67-TOC pickedup 2692 67/67-TOC Phase A picked up 67 A picked up 2693 67/67-TOC Phase B picked up 67 B picked up 2694 67/67-TOC Phase C picked up 67 C picked up SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The setting range depends on the selection of the current to be evaluated at address 133 INTERM.EF. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Counter of det. times elapsed 6929 IEF Tres run. Interm. E/F: reset time running 6930 IEF Trip Interm. E/F: trip 6931 Iie/In= Max RMS current value of fault = 6932 Nos.IIE= No. of detections by stage Iie>= SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The function is blocked in case of a measuring voltage failure under the condition that the fuse-failure monitor is configured for the functioning in a grounded system (see Section 2.11.1 Measurement Supervision, Fuse- Failure Monitor). Furthermore, the function can be blocked externally using the binary input signal >dIEF block . SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 205
The raising pickup of the function (indication 6972 dIEF pick up ) is the criterion for opening the ground fault log. Logic Diagram The following figure shows the logic diagram of the directional intermittent ground fault protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 206
For with with Vgnd/3V0>, pickup is initiated once the threshold Vgnd> / 3V0> has been exceeded. For with oper. dir., pickup is initiated when a pulse is detected in the direction specified at SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
At address 3406 Pickup you can set the criterion for the pickup of the function. For with with Vgnd/3V0> pickup takes place as soon as the threshold Vgnd> / 3V0> has been exceeded, regardless of whether a real SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Program Execution 2.15.1 The 7SJ80 is equipped with an integrated three-pole, single-shot and multi-shot automatic reclosure (AR). Figure 2-100 shows an example of a timing diagram for a successful second reclosure. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 210
The number of reclose commands initiated by the automatic reclosure function are counted. A statistical counter is available for this purpose for the first and all subsequent reclosing commands. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 211
CFC (fast PLC task processing). Automatic reclosure can thus be initi- ated via any messages (e.g. protective pickup) if address 7164 BINARY INPUTis set to Starts 79. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 212
"Interaction with the Automatic Reclosing Function" which can be found with the setting notes of the overcurrent protection functions and the functional description of the intermittent ground fault protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(FNo. 2784) is generated. The static blocking signal is also used internally to block the protection elements that are only supposed to work when reclosing is enabled (see also side title "Reclosing Before Selectivity" further above). The automatic reclosing function is statically blocked if: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 214
The automatic reclosure system resumes normal state when the lock-out time has elapsed and new blocking conditions do not apply (indicated by 79 TdeadMax Exp ) . SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
TRIP-CLOSE-TRIP cycle. The readiness of the circuit breaker is monitored by the device using a binary input >CB Ready . In the case where this signal from the breaker is not available, the circuit breaker monitoring feature should be disabled, otherwise reclosing attempts will remain blocked. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Control of the protection is again assumed by the parameters for the starting cycle. The following figure illustrates the control of the protection elements 50-2 and 50N-2. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 217
(addresses 7200, 7201, 7212, 7213, 7224 and 7225). The blocking applies only after reclosure in accordance with the set address. Hence, it is possible to specify again other conditions for a third reclosure. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If zone sequencing is not applied, the 50-1 element is to be used only with its relatively long time period (0.9 s). [ablaufkoordinierung-fehler-am-abgang-5-ss-260602-kn, 1, en_US] Figure 2-93 Zone sequencing with a fault occurring at Tap Line 5 and at the busbar SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Automatic reclosure thus is blocked. Time Max. DEAD EXT. serves for monitoring the dead time extension. The extension can be initiated by the circuit breaker monitoring time CB TIME OUT and by an external synchronism check. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 220
AR has finished the reclosure attempts. The flipflop is reset via the OR- combination of the annunciations 2784 79 is NOT ready , 2785 79 DynBlock and 2862 79 Successful . Manual closing is initiated if a CLOSE command comes from the control function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 221
Initiation and Blocking of Automatic Reclosure by Protective Elements (configuration) At addresses 7150 through 7164, and 7166 through 7174, reclosing can be started or blocked for various types of protection functions. Together they constitute the wiring between protection elements and auto- SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 222
Cyclic control of the various protection functions by the 3rd reclosing 7252, 7253, 7260, 7261 attempt For the 4th cycle: Address 7133 DEADTIME 4: PH Dead time for the 4th reclosing attempt phase SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 223
The auto-reclosure function provides the signal 79 ready for controlling the cold load pickup. The signal 79 ready is always active if the auto-reclosing system SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Cmd.via control (Einstellmöglichkeiten none Close command via control device anwendungsabhängig) 7138 Internal SYNC (Einstellmöglichkeiten none Internal 25 synchronisation anwendungsabhängig) 7139 External SYNC External 25 synchronisation 7140 ZONE SEQ.COORD. ZSC - Zone sequence coordination SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 225
Starts 79 Stops 79 7163 No influence No influence Starts 79 Stops 79 7164 BINARY INPUT No influence No influence Binary Input Starts 79 Stops 79 7165 3Pol.PICKUP BLK 3 Pole Pickup blocks 79 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 226
TOC Set value T=T Set value T=T before 1. Cycle: 67 TOC instant. T=0 blocked T=∞ 7211 bef.1.Cy:67NTOC Set value T=T Set value T=T before 1. Cycle: 67N TOC instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 227
T=∞ 7226 bef.3.Cy:50-2 Set value T=T Set value T=T before 3. Cycle: 50-2 instant. T=0 blocked T=∞ 7227 bef.3.Cy:50N-2 Set value T=T Set value T=T before 3. Cycle: 50N-2 instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 228
T=∞ 7242 bef.4.Cy:67-1 Set value T=T Set value T=T before 4. Cycle: 67-1 instant. T=0 blocked T=∞ 7243 bef.4.Cy:67N-1 Set value T=T Set value T=T before 4. Cycle: 67N-1 instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 229
7258 bef.2.Cy:67-3 Set value T=T Set value T=T before 2. Cycle: 67-3 instant. T=0 blocked T=∞ 7259 bef.2.Cy:67N-3 Set value T=T Set value T=T before 2. Cycle: IE>>> directional instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The following table shows the assignment of the evaluated loops to the possible pickup scenarios of the protection elements. Pickup by Fault Type Measured Loop Signaled Loop A-N, B-N, C-N signaled loop SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(address 8001 START = Pickup), e.g. when another protection element clears the fault. Irrespective of this fact, calculation of the fault location can be triggered externally via a binary input. (FNo. 1106 >Start Flt. Loc ) provided the device has picked up. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If current flows above the set threshold or thresholds (enabled w/ 3I0>) are detected, the breaker failure protection trips even if the auxiliary criterion indicates “Breaker Open”. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 236
3·I2Ι or a second phase current is used as plausibility current. [7sj80-plausibilitaet-i-sv-20061218, 1, en_US] Figure 2-97 Monitoring of the current flow SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 237
This external signal must be present during the entire period of the delay times, otherwise the timer is reset and no tripping signal is issued. The following figure shows the logic diagram for the breaker failure protection function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
3I0> additionally evaluates the ground current or the negative sequence system when only one phase current occurs. If this function is not required, then Disabled is set. The function can be set to ON or OFF under address 7001 FCT 50BF. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 239
In case of an external start, the set time delay is reduced automatically by 10 ms in order to compensate the residual time of the external start. Figure 2-101 illustrates the time sequences in an example. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
27, 59 Negative-sequence component Voltage asymmetry dV/dt Voltage change Voltage change protection Power Real power Reverse power protection 32R, 32, 37 Power protection Reactive power Power protection cos φ Power factor Power factor SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 243
All other characteristics use always the rms value of the fundamental component. Param- eter PICKUP WITH moreover specifies whether the function picks up on exceeding the threshold (>-element) or on falling below the threshold (<-element). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 244
The following figure shows the logic diagram of a three-phase function. If the function operates on one phase or without phase reference, phase selectivity and phase-specific indications are not relevant. [logik-flexstz-100504-st, 1, en_US] Figure 2-102 Logic diagram of the flexible protection functions SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 245
(no. 235.2114 >$00 BLK.TRIP ). The flexible func- tion also needs to be delayed by at least 20 ms to make sure that the inrush restraint picks up before the flexible function. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Parameter BLK f out of r allows you to specify whether the protection function is blocked if the meas- ured power frequency is outside the operating range of the function (25 Hz to 70 Hz). SIEMENS recommends using the default setting (YES). A release beyond the normal operating range is only required for special appli- cations.
Page 247
The ratio of the negative-sequence current to the positive-sequence current is evaluated. Ratio I2/I1 Please note that the function only operates ifΙ2 or Ι1 has exceeded the threshold value 0.1 · Ι Parameter MEAS. QUANTITY = Voltage Parameter VOLTAGE SYSTEM SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 248
If parameter 251 is set to A,G2,C,G; G->B, the setting ΙN2 refers to the current at the second current (ΙN2). The setting ΙNS or ΙNS refers to the sensitive or highly sensitive ground current at the fourth current input. Parameter MEAS. QUANTITY = Voltage Parameter VOLTAGE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 249
The dropout of pickup can be delayed via parameter T DROPOUT DELAY. This setting is also set to zero by default (standard setting) A setting deviating from zero may be required if the device is utilized together with electro-magnetic devices with considerably longer dropout ratios than the digital protection device (see SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Setting Options Default Setting Comments FLEXIBLE FUNC. Flexible Function Alarm Only OPERRAT. MODE 3-phase 3-phase Mode of Operation 1-phase no reference BLK f out of r Block while Freq. is out of range SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 251
Pickup Threshold 0.25 .. 200.00 A 10.00 A P.U. THRESHOLD 0.001 .. 1.500 A 0.100 A Pickup Threshold 0.005 .. 7.500 A 0.500 A P.U. THRESHOLD 2.0 .. 260.0 V 110.0 V Pickup Threshold SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Function $00 Pickup Phase C 235.2125 $00 Time Out Function $00 TRIP Delay Time Out 235.2126 $00 TRIP Function $00 TRIP 235.2128 $00 inval.set Function $00 has invalid settings 236.2127 BLK. Flex.Fct. IntSP BLOCK Flexible Function SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The example illustrates how a reverse power protection is implemented by means of the flexible protection functions. Frequency protection and voltage protection are described in Sections 2.8 Frequency Protection 81 2.6 Voltage Protection 27, SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 254
The transformer with a transformation ratio of 10:1 transforms the voltage level to 11 kV. The transformer, the generator and the two feeders are linked via a busbar at the low-voltage side. Circuit breakers CB2 to CB5 separate consumer and operational equipment from the busbar. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 255
The following figure shows the wiring of the device for reverse power protection. The power flow in positive or forward direction occurs from the high-voltage busbar (not shown) via the transformer to the lowvoltage busbar. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Functional Logic The following logic diagram depicts the functional logic of the reverse power protection. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 257
When using the reverse power protection to disconnect the substation quickly from the power supply compa- ny's system if faults occur, it is useful to select a larger pickup value (e.g. 50% of nominal power) and shorter time delays. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Power System Data 1 for the connection of the voltage and current transformers (Addresses 213 and 251). [flexfkn-weitere-funktionen-030204-he, 1, en_US] Figure 2-107 The flexible function appears in the function selection. First activate the function at “Settings --> General” and select the operating mode “3-phase” SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 259
Figure 2-109 Setting options of the flexible function Allocating the Reverse-Power Protection in DIGSI Configuration Matrix The DIGSI configuration matrix initially shows the following indications (after selecting “Indications and commands only” and “No filter”. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 260
Clicking the texts allows for editing short text and long text as required by the application. [flexfkn-rangierung-nach-dem-editieren-030204-he, 1, en_US] Figure 2-111 Indications after editing The indications are allocated in the same way as the indications of other protective functions. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If a transformer is connected between the two voltage transformers as shown in the following example, its vector group can be adapted in the 7SJ80 relay so that there is no external adjustment required. [synchro-fkt-einspeis-061115, 1, en_US] Figure 2-112 Infeed SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 262
Please note that some of the protection functions are restricted or do not work at all with this kind of connec- tion. Notes on the effects of the current transformer connection can be found in Section 2.1.3.2 Setting Notes, Table 2-1. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
CLOSE command to the circuit breaker (see also margin heading “Interaction with Control”). However, the message 25 Synchron is applied as long as the synchronous condi- tions are met. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Before granting a release for connecting the energized component V and the de-energized component V the following conditions are checked: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
) to the synchrocheck function which is then started. Having completed the check, the synchrocheck function issues the release message ( 25 CloseRelease ) to which the control responds by terminating the switching operation either positively or negatively. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 266
If the configured conditions of the SYNC function group are fulfilled, the release is granted and the control issues the CLOSE command. [anbind-awe-an-synchro-fkt-061115, 1, en_US] Figure 2-115 Connection of the automatic reclosing function to the synchrocheck function SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Selecting the SYNC function group in DIGSI opens a dialog box with tabs in which the individual parameters for synchronization can be set. General Settings The general thresholds for the synchronizing function are set at addresses 6101 to 6112. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 268
The transformer vector group is defined from the high side to the low side. In the example, the reference voltage transformers (V ) are the ones of the transformer high side, i.e. the setting angle is 5 x 30° (according to vector group), that is 150°: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 269
For the device to perform the internal conversion to primary values, the primary rated transformer voltage of the measured quantity V must be entered via parameter 6125 VT Vn2, primary, primary if a transformer is located between the system parts to be synchronized. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 270
If only phase-to-ground voltages are available, the reference voltage V is connected to the first voltage trans- former and the additional voltage V to the third voltage transformer. [sync-1phasig-anschl-le-061116, 1, en_US] Figure 2-119 Phase-to-ground voltage connection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
25 Vdiff too large (V2>V1) 170.2091 25 V2<V1 25 Vdiff too large (V2<V1) 170.2092 25 f2>f1 25 fdiff too large (f2>f1) 170.2093 25 f2<f1 25 fdiff too large (f2<f1) 170.2094 25 α2>α1 25 alphadiff too large (a2>a1) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 273
25 Multiple selection of func-groups 170.2097 25 Set-Error 25 Setting error 170.2101 25-1 OFF Sync-group 1 is switched OFF 170.2102 >BLK 25 CLOSE >BLOCK 25 CLOSE command 170.2103 25 CLOSE BLK 25 CLOSE command is BLOCKED SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The normal phase sequence is set at 209 (see Section 2.1.3 Power System Data 1). If, on the system side, phase rotation is reversed temporarily, then this is communicated to the protection device using the binary input >Reverse Rot. (5145). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
>Reset LED ). A precondition, of course, is that the circuit-breaker close coil – as usual – remains blocked as long as the trip signal is present, and that the trip coil current is interrupted by the auxil- iary contact of the circuit breaker. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Setting Notes Trip Signal Duration The minimum trip command duration TMin TRIP CMD was described already in Section 2.1.3 Power System Data 1. This setting applies to all protective functions that initiate tripping. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
LCD at any time by selection via the keypad or transferred to a personal computer via the serial service or PC interface. Readout of messages during operation is described in detail in the SIPROTEC 4 System Descrip- tion.
Page 278
(address 3101 = Alarm Only) or the setting ON with GF log has been selected. With setting ON with GF log, there is also a trip, apart from the opening of the ground fault log. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
General Interrogation The general interrogation which can be retrieved via DIGSI enables the current status of the SIPROTEC 4 device to be read out. All messages requiring general interrogation are displayed with their present value.
The procedures ΣΙx, 2P and Ι t make use of the same criteria for that purpose. The logic of the start and end criterion is illustrated Figure 2-124. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 281
52 WearSet.fail , 52WL.blk n PErr or 52WL.blk I PErr (see Section 2.1.6.2 Setting Notes, “Power System Data 2”). The latter two indications can only take effect if the 2P-proce- dure was configured. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 282
The interrupted current in each pole is determined for each trip signal. The interrupted fault current is indi- cated in the fault messages and is added up with previously stored fault current values in the statistic-coun- ters. Measured values are indicated in primary terms. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 283
Point P1 is determined by the number of permitted operating cycles at rated operating current Ιr, point P2 by the maximum number of operating cycles at rated fault tripping current Ιsc. The associ- ated four values can be configured. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 284
The maximum number of operating cycles with Ιsc (263 OP.CYCLES Isc) is used instead as the calculation result for the current number of operating cycles, see Figure 2-126. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 285
CB operating time on tripping has elapsed. They are set off against the remaining lifetime allowing the present statistic SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Setting Notes Reading/Setting/Resetting Counters The SIPROTEC 4 System Description provides a description of how to read out the statistical counters via the device front panel or DIGSI. Setting or resetting of these statistical counters takes place under the menu item MESSAGES —>...
Page 287
Parameter 172 52 B.WEAR MONIT can be set to activate the 2P procedure. An operating cycles diagram (see sample diagram in the functional description of the 2P procedure), provided by the manufacturer, shows the SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
A series of measured values and the values derived from them are constantly available for call up on site, or for data transfer. Applications • Information on the actual status of the system • Conversion of secondary values to primary values and percentages SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
P, Q, S (P and Q No secondary measured values phase-segre- gated) Power Factor cos φ cos φ cos φ · 100 in % (phase-segre- gated) Frequency f in Hz f in Hz Protection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The measured values as well as their unit format are set out in detail in manual PIXIT 7SJ. The measured values are transmitted in “Float” format. The transmitted measuring range is not limited and corresponds to the operational measurement. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
If the settings for averaging are changed, then the measured values stored in the buffer are deleted, and new results for the average calculation are only available after the set time period has passed. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
To select this feature, address 8311 MinMax cycRESET should be set to YES. The point in time when reset is to take place (the minute of the day in which reset will take place) is set at address 8312 MiMa RESET TIME. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PdMax= Active Power Demand Maximum QdMin= Reactive Power Minimum QdMax= Reactive Power Maximum SdMin= Apparent Power Minimum SdMax= Apparent Power Maximum Ia Min= Ia Min Ia Max= Ia Max Ib Min= Ib Min SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
This can be allocated to LEDs and/or binary outputs, transferred via the interfaces and linked in DIGSI CFC. The limit values can be configured via DIGSI CFC and allocated via the DIGSI device matrix. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The setting of threshold values for the statistical counters takes place in DIGSI under Messages → Statistics in the sub-menu Threshold Values for Statistics. Double-click to display the corresponding contents in another window. By overwriting the previous value the settings can be changed (please refer to the SIPROTEC 4 System Description).
Applications • Test Mode • Commissioning Prerequisites In order to be able to use the commissioning aids described in the following, the device must be connected to a control center via port B. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(e.g. message ON / message OFF). After having entered password no. 6 (for hardware test menus), the corre- sponding message is issued and can be read out in the event log of the SIPROTEC 4 device and in the substa- tion control center.
2.24 Breaker Control 2.24 Breaker Control A control command function is integrated in the SIPROTEC 4 7SJ80 to coordinate the operation of circuit breakers and other equipment in the power system. Control commands can originate from four command sources: •...
Command Sequence Safety mechanisms in the command sequence ensure that a command can only be released after a thorough check of preset criteria has been successfully concluded. Standard Interlocking checks are provided for each SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Runtime Monitor (feedback message monitoring time) Interlocking 2.24.4 System interlocking is executed by the user-defined logic (CFC). 2.24.4.1 Functional Description Interlocking checks in a SICAM / SIPROTEC 4 system are normally divided in the following groups: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 302
The minus sign means a negative confirmation, the command was rejected. Possible command feedbacks and their causes are dealt with in the SIPROTEC 4 System Description. The following figure shows operational indications relating to command execution and operation response information for successful switching of the circuit breaker.
Page 303
VD (when Switching Authority = REMOTE) will be accepted by the device. Remote switching commands will be rejected. • Switching authority REMOTE: A remote switch command (command with source REMOTE) is only allowed if remote control is enabled at the device (by configuration). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 304
Functions 2.24 Breaker Control [schutz-standardverriegelungen-090902-kn, 1, en_US] Figure 2-129 Standard interlockings The following figure shows the configuration of the interlocking conditions using DIGSI. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 305
The interlocking condition "Switching Authority" serves for determining the switching authority. It enables the user to select the authorized command source. For devices with operator panel, the following switching authority ranges are defined in the following priority sequence: • LOCAL • DIGSI • REMOTE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 306
With a 7SJ80, the switching mode can be changed between "locked" and "unlocked" on the operator panel after having entered the password or by means of CFC also via binary inputs and a function key. The following switching modes (remote) are defined: SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 307
• SC=LOCAL – The user can switch between the modes “interlocked“ or “non-interlocked“ (bypassed) in the oper- ator panel after entering the password or using CFC via binary input and function key. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Prerequisites A listing of possible operating messages and their meaning as well as the command types needed for tripping and closing of the switchgear or for raising and lowering of transformer taps are described in the SIPROTEC 4 System Description.
Display The SIPROTEC 4 System Description applies to devices with a 4-line ASCII display. Apart from that there are devices with a graphical display and a size of 30 lines. The 7SJ80 uses the outputs of the graphical display, but with 6 lines.
Page 310
Functions 2.25 Notes on Device Operation [grundbild-parameter-20070404, 1, en_US] Figure 2-132 Representation of the active parameter group (line 6) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Hardware adjustments to the power system data might be necessary. The primary tests require the protected object (line, transformer, etc.) to carry load. Mounting and Connections Checking Connections Commissioning Final Preparation of the Device SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Prerequisites For installation and connections the following conditions must be met: The rated device data have been checked as recommended in the SIPROTEC 4 System Description. It has been verified that these data comply with the power system data. General Diagrams...
Page 313
(therefore 52a is open and 52b is closed), the circuit breaker trip coil (52TC) is no longer energized and binary input (BI1) is still energized if the command relay contact is open. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 314
, the calculation has to be repeated with the next smaller threshold . This threshold is determined via the parameters 220 Threshold BI 1 to 226 Threshold BI 7. The BI min settings Thresh. BI 176V, Thresh. BI 88V, Thresh. BI 19V are possible. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Any service activities exceeding the installation or exchange of communication modules must only be carried out by Siemens personnel For preparing the workplace, a pad suitable for electrostatic sensitive devices (ESD) is required.
Page 316
If you have not removed the terminal blocks from the rear panel, much more force is required for removing and reinstalling the electronics block, which might lead to the damaging of the device. Therefore, we abso- lutely recommend to remove the terminal blocks before removing the electronics block. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 317
Electronics block without housing Replacing the Fuse The fuse holder is located at the edge of the basic I/O board close to the power supply connection. [7sx80-fuse-basic-io-080408, 1, en_US] Figure 3-4 Placing the fuse SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Make sure that the defective fuse has not left any obvious damage on the device. If the fuse trips again after reconnection of the device, refrain from any further repairs and send the device to Siemens for repair. The device can now be reassembled again (see Section Reassembly).
144 from Tyco Electronics. When connecting single cables, the following cross-sections are allowed: Cable cross-sections: AWG 20-14 (0.5 mm to 2.0 mm Connector sleeve with plastic collar L = 12 mm (0.47 in) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Installation or Replacement of the Ethernet Interface Module The following requirement must be fulfilled: There is no SIPROTEC 4 communication module mounted yet. Otherwise, this has to be removed before actually installing the Ethernet interface module (see below). The Ethernet interface module is inserted in the respective slot, most suitably from the open bottom, i.e.
Page 321
The following description assumes the normal case that a SIPROTEC 4 communication module which has not yet been existing is retrofitted. If a SIPROTEC 4 communication module has to be removed or replaced, the steps are to be performed in reverse order.
Mounting and Commissioning 3.1 Mounting and Connections [com-modul-20071107, 1, --_--] Figure 3-9 Installation of a SIPROTEC 4 communication module The device can now be reassembled again (see Section Reassembly). 3.1.2.5 Reassembly The reassembly of the device is performed in the following steps: Carefully insert the complete electronics block into the housing.
Insert the current and voltage terminal blocks again and lock them in place! Installation 3.1.3 3.1.3.1 General The 7SJ80 relay has a housing size 1/6. The housing has 2 covers and 4 fixing holes each at the top and bottom (see Figure 3-11 Figure 3-12). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
• Insert the device into the panel cut-out and fasten it with four screws. For dimensional drawings, refer to Section 4.25 Dimensions. • Mount the 2 covers again. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The details on the connection technique for the communication modules at the bottom of the device (port A and port B) in accordance with the SIPROTEC 4 System Description and the details on the connection technique for the current and voltage terminals on the rear of the device in the Sections “Connections of the Current Terminals”...
The details on the connection technique for the communication modules at the bottom of the device (port A and port B) in accordance with the SIPROTEC 4 System Description and the details on the connection technique for the current and voltage terminals on the rear of the device in the Sections “Connections of the Current Terminals”...
Page 327
Mounting and Commissioning 3.1 Mounting and Connections [montagehalterung-20070116, 1, en_US] Figure 3-15 Mounting rails for panel surface mounting SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Microsoft Windows USB driver is used which is installed together with DIGSI (as of version V4.82). The interface is installed as a virtual serial COM port. We recommend the use of standard USB cables with a maximum length of 5 m/16 ft. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 329
With data cables, the connections are designated according to DIN 66020 and ISO 2110: • TxD = Data output • RxD = Data input • RTS = Request to send • CTS = Clear to send • GND = Signal/Chassis Ground SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The standard setting of the character idle state for the optical fiber interface is “Light off”. If the character idle state is to be changed, use the operating program DIGSI as described in the SIPROTEC 4 System Description. Checking the System Connections 3.2.2...
Page 331
Check the trip and close circuits to the power system circuit breakers. • Verify that the control wiring to and from other devices is correct. • Check the signaling connections. • Switch the mcb back on. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Primary tests are only allowed to be carried out by qualified personnel, who are familiar with the ² commissioning of protection systems, the operation of the plant and the safety rules and regulations (switching, grounding, etc.). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Functions). If the test mode is switched on, the messages sent by a SIPROTEC 4 device to the main system has an addi- tional test bit. This bit allows the messages to be recognized as not resulting from actual faults. Furthermore, it can be determined by activating the transmission block that no annunciations are transmitted via the system interface during test mode.
To do so, click on the button Send on the corresponding line. The corresponding message is issued and can be read out either from the event log of the SIPROTEC 4 device or from the substation control system. As long as the window is open, further tests can be performed.
Page 335
Select the SIPROTEC device in DIGSI 4 Manager project and choose the menu entry Edit > Object Properties to open the dialog Properties – SIPROTEC 4 Device (see the following figure). Select an Interfac for 11. Port B (on back of device bottom) and for 12. Port A (on front of device bottom) in the properties box Communications modules.
Page 336
3-22). The type of this setting depends of the protocol used and is described in the protocol documentation. Please only perform the described changes in the settings window and confirm your entries with "OK". SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 337
Mounting and Commissioning 3.3 Commissioning [modulspez-071122, 1, en_US] Figure 3-22 Module-specific settings Transfer the data to the protection device (see the following figure). [daten-uebertragen-071122, 1, en_US] Figure 3-23 Transmitting data SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
3.3.4 Prefacing Remarks The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually and precisely controlled in DIGSI. This feature is used to verify control wiring from the device to plant equipment (operational checks) during commissioning. This test option should however definitely not be used while the device is in “real”...
Page 339
Each output relay must be tested via the corresponding Scheduled-cell in the dialog box. • Finish the testing (see margin title below “Exiting the Test Mode”), so that during further testings no unwanted switchings are initiated. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Before starting the circuit breaker tests it is recommended to isolate the circuit breaker of the tested feeder at both ends, i.e. line isolators and busbar isolators should be open so that the breaker can be operated without risk. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 341
A general detailed test guide cannot be specified because the layout of the adjacent circuit breakers largely depends on the system topology. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Fail Ph. Seq. (FNo 171) is generated. The measured value phase allocation must be checked and corrected, if required, after the line has been isolated and current transformers have been short-circuited. The measurement must then be repeated. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Tripping is performed within time 50-1 DELAY (longer time period) (with definite time overcurrent protection) or according to characteristic (with inverse time overcurrent protection). These tests also check the proper functioning of the wiring for reverse interlocking. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
After isolation of the line and short- circuiting of the current transformers the connections must be checked and corrected. The measurements must then be repeated. Finally, switch off the protected power line. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
For the synchrocheck, the program 25 Function 1 is set to SYNCHROCHECK (address 161) • Via a binary input (170.0043 >25 Sync requ. ) a measurement request is entered. The synchrocheck must release closing (message 170.0049 25 CloseRelease ). SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 346
Addresses 6107 to 6110 must be restored as they were changed for the test. If the allocation of the LEDs or signal relays was changed for the test, this must also be restored. [messspan-synch-kontr-20070716, 1, en_US] Figure 3-26 Measuring voltages for synchrocheck SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(see also connection circuit diagram in Appendix C Connection Examples), then the correct polarity of the ground current path usually occurs automatically. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 348
This can be checked via operational measured values. Important! If parameters were changed for this test, they must be returned to their original state after completion of the test ! SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 349
, example with current transformers configured in a Holmgreen-connec- tion (VTs with broken delta connection -- e-n winding) [polaritaetspruefung-ie-mituen-berechnet-211002-kn, 1, en_US] Figure 3-28 Polarity testing for Ι , example with current transformers configured in a Holmgreen-connec- tion (VTs Wye-connected) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
For devices with graphic display this is easy to do with the control display. The switching procedure is described in the SIPROTEC 4 System Description. The switching authority must be set according to the command source used. The switching mode can be selected from interlocked and nonin- terlocked switching.
Page 351
Oscillographic recording is started immediately. During recording, a report is given in the left part of the status bar. Bar segments additionally indicate the progress of the procedure. The SIGRA or the Comtrade Viewer program is required to view and analyse the oscillographic data. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The annunciation buffers are deleted under MAIN MENU → Annunciations → Set/Reset, so that future infor- mation will only apply to actual events and states (see also SIPROTEC 4 System Description). The counters in the switching statistics should be reset to the values that were existing prior to the testing (see also SIPROTEC 4 System Description).
DC 60 V to 250 V Permissible voltage ranges DC 19 V to 60 V DC 48 V to 300 V Overvoltage category, IEC 60255-27 AC ripple voltage peak to peak, IEC 60255-11 15 % of auxiliary voltage SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Signal/command Relay, Alarm Relay Quantity and data depending on the order variant (allocatable) Order variant NO contact NO/NC selectable 7SJ801/803/807/808 2 (+ 1 life contact not allocatable) 7SJ802/804 2 (+ 1 life contact not allocatable) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Impulse voltage test (type test) of all process 6 kV (peak value); circuits (except for communication ports) against 1.2 µs/50 µs; 0.5 J; the internal electronics 3 positive and 3 negative impulses at intervals of 1 s SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 359
Shut-down ramp: 60 s IEC 60255-26 Power off: 5 min. Start-up ramp: 60 s EMC Tests for Noise Emission (Type Test) Standard: EN 61000-6-4 /01.07 + A1 EN 55011 /11.2009 + A1 class A SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
56 days of the year up to 93 % relative humidity; condensation must be avoided! Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur.
Design Field Wires of Control Circuits shall be separated from other circuits with respect to the end use requirements! Type 1 if mounted into a door or front cover of an enclosure. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
= 1 A 3 % of setting value or 15 mA for Ι for Ι = 5 A 3 % of setting value or 75 mA Time delays T 1 % or 10 ms SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 364
- up to 10 % 3rd harmonic - up to 10 % 5th harmonic at instantaneous value of 50-3/50N-3 elements Increased tolerances Transient overreaction for τ > 100 ms (with full displacement) <5 % SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
For zero sequence current, read 3Ι0p instead of Ι and T instead of T 3Ι0p for ground fault, read Ι instead of Ι and T instead of T ΙEp Pickup threshold approx. 1.10 · Ι SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 366
Frequency in the range of 25 Hz to 70 Hz Frequency in the range of 0.95 ≤ f/f ≤ 1.05 (f = 50 Hz or 60 Hz) Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 367
Increased tolerances Transient overreaction for τ > 100 ms (with full displacement) <5 % [ausloese-rueckfall-kennli-amz-iec-norm-stark-170502-wlk, 1, en_US] Figure 4-1 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to IEC SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 368
Technical Data 4.3 Inverse-time Overcurrent Protection [ausl-rueckfall-kennl-amz-iec-extrem-langzeit-170502-wlk, 1, en_US] Figure 4-2 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to IEC SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 369
Ι and T instead of T ΙEp Pickup threshold ca. 1.10 · Ι Dropout Time Characteristics with Disk Emulation acc. to ANSI/IEEE Acc. to ANSI/IEEE (see also Figure 4-3 Figure 4-6) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 370
5 % of reference (calculated) value + 2 % current tolerance, or 30 Dropout Time for Ι/Ιp ≤ 0.90 Influencing Variables for Pickup and Dropout Auxiliary DC voltage in range 0.8 ≤ V ≤ 1,15 AuxNom SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 371
- up to 10 % 3rd harmonic - up to 10 % 5th harmonic at instantaneous value of 50-3/50N-3 elements Increased tolerances Transient overreaction for τ > 100 ms (with full displacement) <5 % SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 372
Technical Data 4.3 Inverse-time Overcurrent Protection [ausl-rueckfallkennl-amz-ansi-inv-short-170502-wlk, 1, en_US] Figure 4-3 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 373
Technical Data 4.3 Inverse-time Overcurrent Protection [ausl-rueckfallkennl-amz-ansi-lang-maessig-170502-wlk, 1, en_US] Figure 4-4 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 374
Technical Data 4.3 Inverse-time Overcurrent Protection [ausloese-rueckfallkennl-ansi-amz-stark-extrem-170502-wlk, 1, en_US] Figure 4-5 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 375
Technical Data 4.3 Inverse-time Overcurrent Protection [ausloese-rueckfall-amz-ansi-gleichmaessig-170502-wlk, 1, en_US] Figure 4-6 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Pickup times (without inrush restraint, with restraint + 1 period) 50-1, 50-2, 50-3, 50N-1, 50N-2, 50N-3 - for 2 x setting value approx. 45 ms - for 10 x setting value approx. 40 ms SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 377
50-1, 50-2, 50-3, 50N-1, 50N-2, 50N-3 approx. 40 ms Tolerances Angle faults for phase and ground faults ±1° electrical Influencing Variables Frequency Influence – With no memory voltage approx 1° in range 25 Hz to 50 Hz SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
0.30 A to 25.00 A Increments 0.01 A for Ι = 1 A configurable for Ι = 5 A 1.50 A to 125.00 A Increments 0.01 A Crossblock Crossblock Ι , Ι , Ι ON/OFF SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Increments 1 s Stop reset inactive) Dynamic Settings of Pickup Currents and Time Adjustable within the same ranges and with the same Delays or Time Multipliers increments as the directional and non-directional time overcurrent protection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(r · 59-1) or (r · 59-2) max. 260 V for phase-to-ground voltage Minimum hysteresis 0.6 V Time delays 59-1 DELAY, 59-2 DELAY 0.00 s to 100.00 s or ∞ (disa- Increment 0.01 s bled) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 382
≤ 1.05 (f = 50 Hz or 60 Hz) Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic Transient overreaction for τ > 100 ms (with full displacement) <5 % SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Ι Trip Time Curves acc. to IEC See also Figure 4-7 The trip times for Ι /Ι ≥ 20 are identical to those for Ι /Ι = 20 Pickup Threshold approx. 1.10· Ι SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 385
5 % of reference (calculated) value + 2 % current tolerance, or 30 ms Dropout Time Curves with Disk Emulation acc. to ANSI Representation of the possible dropout time curves, see Figure 4-8 Figure 4-9 each on the left side of the figure SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 386
Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic Transient overreaction for τ > 100 ms (with full displacement) <5 % SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 387
Technical Data 4.10 Negative Sequence Protection (inverse-time characteristics) [ausloese-iec-schieflast-inv-stark-extr-170502-wlk, 1, en_US] Figure 4-7 Trip time characteristics of the inverse time negative sequence element 46-TOC, acc. to IEC SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 388
Technical Data 4.10 Negative Sequence Protection (inverse-time characteristics) [ausloese-rueckfall-ansi-schieflast-inv-mod-170502-wlk, 1, en_US] Figure 4-8 Dropout time and trip time characteristics of the inverse time unbalanced load stage, acc. to ANSI SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 389
Technical Data 4.10 Negative Sequence Protection (inverse-time characteristics) [ausl-rueckfall-schieflast-ansi-stark-extrem-170502-wlk, 1, en_US] Figure 4-9 Dropout time and trip time characteristics of the inverse time unbalanced load stage, acc. to ANSI SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PSNom Temperature in range 23 °F (-5 °C) ≤ Θ ≤ 131 °F (55 °C) 0,5 %/10 K Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Ι = 1 A 2% of set value or 20 mA nents) 2% of set value or 100 mA for Ι = 5 A Voltage 1% of set value or 0.1 V SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 392
≤ 131.00 °F (55 °C) 0.5 %/10 K Frequency in the range from 25 Hz to 70 Hz Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Influencing Variables Referring to k · Ι Auxiliary DC voltage in range 0.8 ≤ V ≤ 1,15 AuxNom Temperature in range –5 °C (23 °F) ≤ Θ ≤ 55 °C (131 °F) 0.5 %/10 K SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 394
≤ 1.05 (f = 50 Hz or 60 Hz) Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances [ausloesekennlinie-ueberlast-1111203-he, 1, en_US] Figure 4-10 Trip time curves for the thermal overload protection (49) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
= 1 A 3 % of setting value or 15 mA for Ι = 5 A 3 % of setting value or 75 mA Operating time tolerance 1 % of setting value or 10 ms SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 396
0.05 A to 35.00 A Increments 0.01 A for normal 1 A transformer 0.25 A to 175.00 A Increments 0.05 A for normal 5-A transformer Dropout ratio approx. 0.80 Measurement method cos φ and sin φ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 397
EPTR Setting Ranges / Increments Pickup current 0.001 A to 2.400 A Incre- for Ι = 1 A ments0.001 A for Ι = 5 A 0.005 A to 7.000 A SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 398
0.10 s to 30.00 s Increments 0.01 s Maximum Time Delay 0.50 s to 300.00 s Increments 0.01 s Delay Time T of the whole function -0.50 s to 30.00 s Increments 0.01 s SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 399
200 A; 300 A t = 0.80 Maximum Tolerance = 0.88 Maximum Tolerance = 0.72 300 A; 1000 A t = 0.80 Maximum Tolerance = 0.58 x (Ir) -0.073 Maximum Tolerance = 1.26 x (Ir) -0.098 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 400
Approx. 0.95 for Ι /Ι > 0.005 EPTR/TNP Tolerance Pickup/dropout thresholds Ιp = 1 A 3 % of setting value or 1 mA Ι = 5 A 3 % of setting value or 5 mA Ι SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PSNim Temperature in range 23.00 °F (-5 °C) ≤ Θ ≤ 131.00 °F (55 °C) <0.5 %/ K Frequency in range 25 Hz to 70 Hz <5 % relating to the set time SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Influencing Variables Power supply direct voltage in range 0.8 ≤ V ≤ 1.15 <1 % PSNom Temperature in range 23.00 °F (-5 °C) ≤ Θ ≤ 131.00 °F (55 °C) <0,5 %/ K SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
30° ≤ φ ≤ 90° and V ≥ 0.1 and Ι /Ι ≥ 1.0 Homogeneous lines or correctly configured line sections are assumed when the fault distance is given in km, miles or %. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Command delay time 0.00 s to 3,600.00 s Increments 0.01 s Dropout delay 0.00 s to 60.00 s Increments 0.01 s Fixed Dropout Difference Dropout difference df/dt 0.1 Hz/s Dropout difference dV/dt 3 V/s SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 407
4% of setting value or 100 mA for Ι = 5 A Current (Ι /Ι 4% of setting value Voltage 3% of setting value or 0,2 V Voltage (symmetrical components) 4% of setting value or 0,2 V SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 408
≤ 1.05 (f = 50 Hz or 60 Hz) Frequency outside range 0.95 ≤ f/f ≤ 1.05 Increased tolerances Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Reference voltage V1 in kV primary, in V secondary or in % V - Range 10 % to 120 % of V - Tolerance ≤ 1 % of measured value, or 0,5 % V SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 410
≤ 1 % of measured value, or 0,5 % V Frequency difference f2-f1 in mHz - Range ± 5 Hz - Tolerance 20 mHz Angle difference λ2-λ1 in ° - Range 0 to 180° 0,5° - Tolerance at nominal frequency SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Timer (max.1193h) LOOP Feedback Loop — LOWER_SETPOINT Lower Limit — — — Multiplication MV_GET_STATUS Decode status of a value MV_SET_STATUS Set status of a value NAND NAND - Gate Negator NOR - Gate SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 412
Maximum number of all CFC charts If the limit is exceeded, the device rejects the parameter considering all task levels set with an error message, restores the last valid param- eter set and restarts using that parameter set. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 413
Processing Times in TICKS for the Individual Elements Individual element Number of TICKS Block, basic requirement Each input from the 3rd additional input on for generic modules Combination with input signal border Combination with output signal border SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 415
Time and clock pulse TIMER TIMER_LONG TIMER_SHORT ALARM BLINK Other IO_UNIT Routable in Matrix In addition to the defined preassignments, indications and measured values can be freely routed to buffers, preconfigurations can be removed. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Range –1 to +1 2 % for | cos φ | ≥ 0.707 Tolerance Frequencies f in Hz Range ± 5 Hz Tolerance 20 mHz Temperature overload protection in % Θ /Θ Trip SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 417
Min/Max Values for Power S, P; Q, cos φ; frequency Min/Max Values for Overload Protection Θ/Θ tRIP Min/Max Values for Mean Values ; Ι ; Ι Ι Admd Bdmd Cdmd (positive sequence component); Ι 1dmd SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 418
Intervals at 60 Hz 1 instantaneous value each per 0.83 ms Energy Counter Meter Values for Energy in kWh (MWh or GWh) or in kVARh (MVARh or GVARh) Wp, Wq (real and reactive energy) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 419
External synchronization using port B (IEC 60870-5-103) Pulse via binary input External synchronization with pulse via binary input Fieldbus (DNP (serial or DNP3 TCP), External synchronization using field bus Modbus, IEC 60870-5-103 redundant) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 420
As from version V4.6 of the devices, applications with protective functions have to be checked with regard to their required runtime. In individual cases, the manufacturer has to be consulted with regard to the requirements to ensure that the application functions safely. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
PLC logic, graphic input tool Local Control Control via menu control assignment of function keys Remote Control Using Communication Interfaces Using a substation automation and control system (e.g. SICAM) Using DIGSI (e.g. via Modem) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
D200-1) is required for cubicle mounting. When using the Ethernet interface, it may be necessary to rework the lower mounting rail. Provide for sufficient space at the device bottom side or below the device to accommodate the cables of the communication modules. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Modbus, electrical RS485 + L 0 D Modbus, optical 820 nm, ST connector + L 0 E DNP3.0, electrical RS485 + L 0 G DNP3.0, optical 820 nm, ST connector + L 0 H SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 427
Port A (bottom side of device, front) Pos. 12 not equipped with Ethernet interface (DIGSI interface, I/O unit connection, not IEC61850), RJ45 connector Measurement / Fault Recording Pos. 13 With fault recording With fault recording, average values, min/max values SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 428
Undervoltage / overvoltage 81 U/O Underfrequency / overfrequency, f< ,f> Phase sequence 32/55/81R/ Flexible protection functions 27R/59R (parameters from current and voltage): Voltage protection, power protection, power factor protection, frequency change protection voltage change protection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 429
Underfrequency / overfrequency, f< ,f> — Undervoltage-controlled reactive power protection (Q>/U<) Phase sequence 32/55/81R/ Flexible protection functions 27R/59R (parameters from current and voltage): Voltage protection, power protection, power factor protection, frequency change protection voltage change protection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 430
79, 21FL With AR, with fault locator only deliverable with position 6 = 1, 2 or 7 Conformal Coating Supplementary for 7SJ801, 7SJ803 +Z Y 15 for 7SJ802, 7SJ804, 7SJ807, 7SJ808 +Z Y 16 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Surface mounting console (converts flush mounting variants into surface mounting variant) Surface mounting console C53207-A356-D850-1 Battery Lithium battery 3 V/1 Ah, type CR 1/2 AA Order No. VARTA 6127 101 301 Panasonic BR-1/2AA Terminals Terminals Voltage terminal block C or block E C53207-A406-D181-1 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 432
Current terminal short circuit links, 3 pieces C53207-A406-D193-1 Voltage terminal short circuit links, 6 pieces C53207-A406-D194-1 Varistor Voltage-limiting resistor for high-impedance differential protection Name Order number 125 Veff, 600 A, 1S/S256 W73028-V3125-A1 240 Veff, 600 A, 1S/S1088 W73028-V3300-A2 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ801* [kl-uebers-7sx80-1, 1, en_US] Figure B-1 Block diagram 7SJ801* SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 435
Terminal Assignments B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ802* [kl-uebers-7sx80-2, 1, en_US] Figure B-2 Block diagram 7SJ802* SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 436
Terminal Assignments B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ803* [kl-uebers-7sx80-3, 1, en_US] Figure B-3 Block diagram 7SJ803* SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 437
Terminal Assignments B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ804* [kl-uebers-7sx80-4, 1, en_US] Figure B-4 Block diagram 7SJ804* SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 438
B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ807* [kl-uebers-7sx80-7, 1, en_US] Figure B-5 Block diagram 7SJ807* The shield of the connecting cable is connected directly to the shield cover SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 439
B.1 7SJ80 — Housing for panel flush mounting and cubicle installation and for panel surface mounting 7SJ808* [kl-uebers-7sx80-8, 1, en_US] Figure B-6 Block diagram 7SJ808* The shield of the connecting cable is connected directly to the shield cover. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Connection Examples Connection Examples for Current and Voltage Transformers Connection Examples for SICAM I/O Units SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Current transformer connections to two current transformers – only for isolated or resonant- grounded networks [anschl-3-stromwdl-summenstromw-060606, 1, en_US] Figure C-3 Current transformer connections to three current transformers, ground current from addi- tional summation current transformer – preferably for effectively or low-resistance grounded networks SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 443
Important: Grounding of the cable shield must be effected at the cable side The switchover of the current polarity (address 201) also reverses the polarity of the current input INs! SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 444
C.1 Connection Examples for Current and Voltage Transformers [anschl-3-stromwdl-3-spannungsw-060606, 1, en_US] Figure C-6 Transformer connections to three current transformers and three voltage transformers (phase- to-ground voltages), normal circuit layout – appropriate for all networks SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 445
C.1 Connection Examples for Current and Voltage Transformers [anschl-3-stromwdl-2-spannung-e-n-wickl-060606, 1, en_US] Figure C-7 Transformer connections to three current transformers, two voltage transformers (phase- tophase voltages) and broken delta winding (da-dn) – appropriate for all networks SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 446
Note: If the system has only 2 voltage transformers (open-delta connection), the device, too, should be connected in open-delta connection and the unused voltage input should be short-circuited. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 447
I at F8 and F7 must be exchanged. [stromwdl-2phasenstrwdl-1erdstrwdl-080211, 1, en_US] Figure C-11 Current transformer connections to two phase-current transformers and a ground-current transformer; the ground current is taken via the highly sensitive and sensitive ground input. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 448
For busbar-side grounding of the current transformers, the current polarity of the device is changed via address 0201. This also reverses the polarity of the current input IN/INs. When using a cable-type current transformer, the connection of k and I at F8 and F7 must be exchanged. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 449
Example for the connection type "VAN, VBN, VCN" with voltage connection on the feeder side [anschl-u12-u23-ue-20070129, 1, en_US] Figure C-15 Voltage transformer connections to two voltage transformers (phase-to-phase voltages) and broken delta winding (da-dn) – appropriate for all networks SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 450
[anschl-uph-usyn-20070129, 1, en_US] Figure C-17 Example for connection type "Vph-n, Vsyn" The connection can be established at any one of the three phases. The phase must be the same for Vph-n and Vsyn. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 451
Connection Examples C.1 Connection Examples for Current and Voltage Transformers [anschl-u12-u23-ux-20070129, 1, en_US] Figure C-18 Example for connection type "VAB, VBC, Vx" [anschl-u12-u23-20070129, 1, en_US] Figure C-19 Example for connection type "VAB, VBC" SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 452
C.1 Connection Examples for Current and Voltage Transformers [anschl-u12-u23-v-schalt-20070129, 1, en_US] Figure C-20 Example for connection type "VAB, VBC" with phase voltage connection as open-delta connec- tion [anschl-u12-u23-usyn-20070129, 1, en_US] Figure C-21 Example for connection type "VAB, VBC, VSYN" SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 453
Connection Examples C.1 Connection Examples for Current and Voltage Transformers [anschl-u12-u23-usyn-v-schalt-20070129, 1, en_US] Figure C-22 Example for connection type "VAB, VBC, VSYN" with phase voltage connection as open-delta connection SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Connection Examples for SICAM I/O Units [sicam-io-unit-01-20120731-kn, 1, en_US] Figure C-23 Connection of 2 SICAM I/O units to port A via Y cable (up to 2 SICAM I/O units connectable) Y cable 7KE6000–8GD00–0BA2 RJ45 cable SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
The standards IEC 60044-6, BS 3938 and ANSI/IEEE C 57.13 are referred to for converting the requirement into the knee-point voltage and other transformer classes. Accuracy limiting factors Class conversion Cable core balance current transformer SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(< 50 mA secondary) is not defined in rated general. For very sensitive directional measurements, Siemens recommends the classes 0.5S or 0.1S that define the class accuracy via an extended current range (up to 1% I ) (see chapter 5.6.201.5, IEC 61869-2).
When the device leaves the factory, a large number of LED indications, binary inputs and outputs as well as function keys are already preset. They are summarized in the following table. LEDs Binary Input Binary Output Function Keys Default Display Protocol-dependent Functions SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Fail Ph. Seq. I Failure: Phase Sequence Current Fail Ph. Seq. V Failure: Phase Sequence Voltage VT brk. wire Failure VT circuit: broken wire LED7 Not configured No Function configured LED8 Brk OPENED Breaker OPENED SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 461
Fail Ph. Seq. I Failure: Phase Sequence Current Fail Ph. Seq. V Failure: Phase Sequence Voltage VT brk. wire Failure VT circuit: broken wire LED7 Not configured No Function configured LED8 Brk OPENED Breaker OPENED SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Further binary input presettings for 7SJ807* or 7SJ808* Binary Input Default function Function No. Description not pre-assigned not pre-assigned not pre-assigned not pre-assigned not pre-assigned not pre-assigned BI10 not pre-assigned BI11 not pre-assigned SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Default function Display of the operational indications Display of the primary operational measured values Display of the last fault log buffer not pre-assigned not pre-assigned not pre-assigned not pre-assigned not pre-assigned not pre-assigned SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
640 Start image DD auswählen. for the 6-line Display of 7SJ80 [grundbild6zei-mit-u-ohne-erw-mw-20070116, 1, en_US] Figure E-1 Default display of the 7SJ80 for models with V without extended measured values SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 466
With the V0/IO ϕ measurement, the measured ground current IN2 is displayed under N and the ground current IN or INs under Ns. [grundbild6zei-mit-u-und-erw-mw-20070116, 1, en_US] Figure E-2 Default display of the 7SJ80 for models with V with extended measured values SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 467
After a fault has occurred, the most important fault data are automatically displayed after general device pickup in the order shown in the picture below. [anzeige-spontanmeldungen-im-display-des-geraetes-260602-kn, 1, en_US] Figure E-5 Representation of spontaneous messages on the device display SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Functions, Settings, Information Functional Scope Settings Information List Group Alarms Measured Values SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Binray Input MEAS. METHOD Fundamental Fundamental Selection of Measure- ment Method True RMS Positive seq. Negative seq. Zero sequence Ratio I2/I1 PICKUP WITH Exceeding Exceeding Pickup with Dropping below CURRENT Current In sensitive SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 473
Line CT Starpoint towards Busbar Vnom PRIMARY P.System Data 0.10 .. 800.00 kV 20.00 kV Rated Primary Voltage Vnom SECONDARY P.System Data 34 .. 225 V 100 V Rated Secondary Voltage (L-L) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 474
Thresh. BI 176V Threshold for Binary Input Thresh. BI 88V Thresh. BI 19V Threshold BI 6 P.System Data Thresh. BI 176V Thresh. BI 176V Threshold for Binary Input Thresh. BI 88V Thresh. BI 19V SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 475
Control Device sabhängig) T 52 BREAKTIME P.System Data 1 .. 600 ms 80 ms Breaktime (52 Breaker) T 52 OPENING P.System Data 1 .. 500 ms 65 ms Opening Time (52 Breaker) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 476
Osc. Fault Rec. 0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input FltDisp.LED/LCD Device, General Target on PU Target on PU Fault Display on LED / LCD Target on TRIP SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 477
Offset for daylight in minutes W2S month Device, General 1 .. 12 month of time set winter to summer W2S week Device, General 1 .. 5 week of time set winter to summer SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 478
85 ° Line angle 1110 Line length P.System Data 0.1 .. 1000.0 km 100.0 km Line length in kilometer 1111 Line length P.System Data 0.1 .. 650.0 Miles 62.1 Miles Line length in miles SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 479
50/51 Overcur. Fundamental Fundamental 50-2 measurement of True RMS 1221A 50-1 measurem. 50/51 Overcur. Fundamental Fundamental 50-1 measurement of True RMS 1222A 51 measurem. 50/51 Overcur. Fundamental Fundamental 51 measurement of True RMS SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 480
0.00 .. 60.00 sec; ∞ 0.05 sec 50N-3 Time Delay 1319A 50N-3 measurem. 50/51 Overcur. Fundamental Fundamental 50N-3 measurement of True RMS Instantaneous 1320A 50N-2 measurem. 50/51 Overcur. Fundamental Fundamental 50N-2 measurement of True RMS SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 481
67 Direct. O/C Fundamental Fundamental 67-1 measurement of True RMS 1522A 67-TOC MEASUR. 67 Direct. O/C Fundamental Fundamental 67-TOC measurement of True RMS 1523 67-2 Direction 67 Direct. O/C Forward Forward 67-2 Direction Reverse Non-Directional SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 482
Normal Inverse IEC Curve Very Inverse Extremely Inv. Long Inverse 1612 67N-TOC ANSI 67 Direct. O/C Very Inverse Very Inverse ANSI Curve Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 483
Start Condition Breaker Contact 79 ready 1703 CB Open Time ColdLoadPickup 0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time 1704 Active Time ColdLoadPickup 0 .. 21600 sec 3600 sec Active Time SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 484
2104 67Nc-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; ∞ 0.30 sec 67Nc-1 Time Delay 2105 67Nc-TOC PICKUP ColdLoadPickup 1A 0.05 .. 4.00 A 1.00 A 67Nc-TOC Pickup 0.25 .. 20.00 A 5.00 A SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 487
E Flt(ext) 0.003 .. 1.400 A 0.100 A Current at Knee Point 0.015 .. 7.000 A 0.500 A 3510 TNP I Tknee E Flt(ext) 0.05 .. 17.00 A 0.20 A Current at Knee Point SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 488
Current Overload Alarm Setpoint 0.50 .. 20.00 A 5.00 A 4207A Kτ-FACTOR 49 Th.Overload 1.0 .. 10.0 Kt-FACTOR when motor stops 4208A T EMERGENCY 49 Th.Overload 10 .. 15000 sec 100 sec Emergency time SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 492
SYNC V1<V2< SYNC function ON-Command at V1< and V2< 6110A Direct CO SYNC function Direct ON-Command 6111A TSUP VOLTAGE SYNC function 0.00 .. 60.00 sec 0.10 sec Supervision time of V1>;V2> or V1<;V2< SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 493
T-Start MONITOR 79M Auto Recl. 0.01 .. 320.00 sec; 0.50 sec AR start-signal monitoring ∞ time 7115 CB TIME OUT 79M Auto Recl. 0.10 .. 320.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 494
No influence No influence 50N-2 Starts 79 Stops 79 7154 79M Auto Recl. No influence No influence Starts 79 Stops 79 7155 79M Auto Recl. No influence No influence Starts 79 Stops 79 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 495
Set value T=T Set value T=T before 1. Cycle: 50-1 instant. T=0 blocked T=∞ 7201 bef.1.Cy:50N-1 79M Auto Recl. Set value T=T Set value T=T before 1. Cycle: 50N-1 instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 496
Set value T=T Set value T=T before 2. Cycle: 51 instant. T=0 blocked T=∞ 7217 bef.2.Cy:51N 79M Auto Recl. Set value T=T Set value T=T before 2. Cycle: 51N instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 497
Set value T=T Set value T=T before 3. Cycle: 67-2 instant. T=0 blocked T=∞ 7233 bef.3.Cy:67N-2 79M Auto Recl. Set value T=T Set value T=T before 3. Cycle: 67N-2 instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 498
Set value T=T Set value T=T before 1. Cycle: 50-3 instant. T=0 blocked T=∞ 7249 bef.1.Cy:50N-3 79M Auto Recl. Set value T=T Set value T=T before 1. Cycle: 50N-3 instant. T=0 blocked T=∞ SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 499
START Fault Locator Pickup Pickup Start fault locator with TRIP 8101 MEASURE. SUPERV Meas- Measurement Supervision urem.Superv 8102 BALANCE V-LIMIT Meas- 10 .. 100 V 50 V Voltage Threshold for urem.Superv Balance Monitoring SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 500
1 .. 365 Days 7 Days MinMax Reset Cycle Period 8314 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle 8315 MeterResolution Energy Standard Standard Meter resolution Factor 10 Factor 100 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
(“.._Ev”“). Further information on indications can be found in detail in the SIPROTEC 4 System Description, Order No. E50417-H1176-C151. In columns “Event Log”, “Trip Log” and “Ground Fault Log” the following applies: UPPER CASE NOTATION “ON/OFF”:...
Page 502
Disconnect Switch Control (Disc.Swit.) Device Disconnect Switch Control CB 24 (Disc.Swit.) Device Ground Switch Control (GndSwit.) Device Ground Switch Control CB 24 (GndSwit.) Device >CB ready Spring is Process charged (>CB ready) Data SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 503
>Transformer Danger Process CB 24 (>Tx Danger) Data Reset Minimum and Min/Max IntS Maximum counter meter (ResMinMax) Reset meter (Meter res) Energy IntS Error Systeminterface Protocol IntS (SysIntErr.) DCP identify (DCP ident) Protocol IntS SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 504
General At Least 1 Protection Device, IntS Funct. is Active (ProtAc- General tive) Reset Device (Reset Device, OUT On * Device) General Initial Start of Device Device, OUT On * (Initial Start) General SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 505
General Alarm Summary Event Device, OUT On (Alarm Sum Event) General Failure: General Current Meas- OUT On Supervision (Fail I urem.Super Superv.) Failure: Current Summa- Meas- OUT On tion (Failure Σ I) urem.Super SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 507
(fdiff) okay (25 fdiff ok) tion 1 170.20 25 Angle difference SYNC func- OUT On (alphadiff) okay (25 αdiff tion 1 170.20 25 Frequency f1 > fmax SYNC func- OUT On permissible (25 f1>>) tion 1 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 508
(a2>a1) (25 α2>α1) tion 1 170.20 25 alphadiff too large SYNC func- OUT On (a2<a1) (25 α2<α1) tion 1 170.20 25 Multiple selection of SYNC func- OUT On func-groups (25 FG-Error) tion 1 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 509
Error: Neutral CT different Device, OUT On from MLFB (Error General neutralCT) Measurement Supervision Meas- OUT On is switched OFF (MeasSup urem.Super OFF) Waveform data deleted Osc. Fault On * (Wave. deleted) Rec. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 511
($00 inval.set) 236.21 BLOCK Flexible Function Device, IntS (BLK. Flex.Fct.) General Failure VT circuit: broken Meas- OUT On wire (VT brk. wire) urem.Super Failure VT circuit (Fail VT Meas- OUT On circuit) urem.Super SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 512
>GOOSE-Stop (>GOOSE- Device, Stop) General >Manual close signal P.System (>Manual Close) Data 2 >I MIN/MAX Buffer Reset Min/Max On * (>I MinMax Reset) meter >I1 MIN/MAX Buffer Reset Min/Max On * (>I1 MiMaReset) meter SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 513
Trip via control command P.System IntS (Cmd Trip) Data 2 Relay PICKUP (Relay P.System m LED PICKUP) Data 2 Relay Drop Out (Relay Device, Drop Out) General General CLOSE of relay Device, (Relay CLOSE) General SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 515
OUT On (50Ns/67Ns ACT) Fault 1215 64 displacement voltage Sens. Gnd OUT * pick up (64 Pickup) Fault 1217 64 displacement voltage Sens. Gnd OUT * m LED element TRIP (64 TRIP) Fault SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 516
Ph C (Sens. Fault Gnd Ph C) 1276 Sensitive Gnd fault in Sens. Gnd OUT On forward direction Fault (SensGnd Forward) 1277 Sensitive Gnd fault in Sens. Gnd OUT On reverse direction Fault (SensGnd Reverse) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 517
49 Th.Over- Protection (>BLOCK 49 load O/L) 1507 >Emergency start of 49 Th.Over- motors (>EmergencyS- load tart) 1511 49 Overload Protection is 49 Th.Over- OUT On OFF (49 O / L OFF) load SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 519
OUT * picked up) Overcur. 1768 50N-3 picked up (50N-3 50/51 OUT * picked up) Overcur. 1769 50-3 TRIP (50-3 TRIP) 50/51 OUT * Overcur. 1770 50N-3 TRIP (50N-3 TRIP) 50/51 OUT * Overcur. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 520
Overcur. 1837 51N picked up (51N 50/51 OUT * picked up) Overcur. 1838 51N Time Out (51N 50/51 OUT * TimeOut) Overcur. 1839 51N TRIP (51N TRIP) 50/51 OUT * m LED Overcur. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 521
Pickup 1995 Cold-Load-Pickup is ColdLoad- OUT On BLOCKED (CLP BLOCKED) Pickup 1996 Cold-Load-Pickup is ColdLoad- OUT On RUNNING (CLP running) Pickup 1997 Dynamic settings are ColdLoad- OUT On ACTIVE (Dyn set. ACTIVE) Pickup SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 522
Phase B reverse (Phase B 67 Direct. OUT On * reverse) 2634 Phase C reverse (Phase C 67 Direct. OUT On * reverse) 2635 Ground forward (Ground 67 Direct. OUT On * forward) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 523
(67N ACTIVE) 2659 67N-1 is BLOCKED (67N-1 67 Direct. OUT On BLOCKED) 2660 67-1 picked up (67-1 67 Direct. OUT * picked up) 2664 67-1 Time Out (67-1 Time 67 Direct. OUT * Out) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 524
67 Direct. OUT * is ACTIVE (67N-TOC Disk 2691 67/67N picked up 67 Direct. OUT * m LED (67/67N pickedup) 2692 67/67-TOC Phase A 67 Direct. OUT * picked up (67 A picked SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 525
ANSI#-2) 2722 >Switch zone sequence 79M Auto coordination ON (>ZSC Recl. 2723 >Switch zone sequence 79M Auto coordination OFF (>ZSC Recl. OFF) 2730 >Circuit breaker READY 79M Auto for reclosing (>CB Ready) Recl. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 526
(79 no starter) Recl. 2824 79: no cycle configured 79M Auto OUT On (79 no cycle) Recl. 2827 79: blocking due to trip 79M Auto OUT On * (79 BLK by trip) Recl. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 527
ON (ZSC Recl. 2885 Zone sequence coordina- 79M Auto OUT On * tion switched OFF (ZSC Recl. OFF) 2889 79 1st cycle zone exten- 79M Auto OUT * sion release (79 1.CycZo- Recl. neRel) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 528
ACB) Data 1 5151 46 switched OFF (46 OFF) 46 Negative OUT On 5152 46 is BLOCKED (46 46 Negative OUT On BLOCKED) 5153 46 is ACTIVE (46 ACTIVE) 46 Negative OUT On SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 529
81-1 picked up (81-1 81 O/U OUT * picked up) Freq. 5233 81-2 picked up (81-2 81 O/U OUT * picked up) Freq. 5234 81-3 picked up (81-3 81 O/U OUT * picked up) Freq. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 532
6571 59-2 Overvoltage V>> 27/59 O/U OUT * picked up (59-2 picked Volt. 6573 59-2 Overvoltage V>> 27/59 O/U OUT * TRIP (59-2 TRIP) Volt. 6851 >BLOCK 74TC (>BLOCK 74TC Trip- 74TC) Circ. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 533
Interm.E/F det.stage Iie> Intermit. EF OUT * f.Flt. ev.Prot (IIE Flt.det 6927 Interm. E/F detected Intermit. EF OUT * (Intermitt.EF) 6928 Counter of det. times Intermit. EF OUT * elapsed (IEF Tsum exp.) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 534
7552 50N-1 InRush picked up 50/51 OUT * (50N-1 InRushPU) Overcur. 7553 51 InRush picked up (51 50/51 OUT * InRushPU) Overcur. 7554 51N InRush picked up 50/51 OUT * (51N InRushPU) Overcur. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 535
Ext I/O) General 10081 Error Ethernet (Error Device, OUT On Ethernet) General 10082 Error Current Terminal Device, OUT On (Error Terminal) General 10083 Error Basic I/O (Error Basic Device, OUT On I/O) General SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 536
16016 Sum Squared Current Statistics Integral Phase C (ΣI^2t 16018 Threshold Sum Squa. SetPoint(Sta OUT On Curr. Int. exceeded (Thresh. ΣI^2t>) 16019 >52 Breaker Wear Start P.System Criteria (>52 Wear start) Data 2 SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 537
18908 Transformer Neutral(TNP) E Flt(ext) OUT On is OFF (TNP OFF) 18909 Transformer Neutral(TNP) E Flt(ext) OUT On is ACTIVE (TNP ACT) 18910 EPTR picked up (EPTR E Flt(ext) OUT * picked up) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 538
Fault recording is running Osc. Fault OUT * (Fault rec. run.) Rec. 31000 Q0 operationcounter= Control (Q0 OpCnt=) Device 31001 Q1 operationcounter= Control (Q1 OpCnt=) Device 31008 Q8 operationcounter= Control (Q8 OpCnt=) Device SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Measurement V2 (negative sequence) (V2 =) Measurement Vsync (synchronism) (Vsync =) Measurement P (active power) (P =) Measurement Q (reactive power) (Q =) Measurement Frequency (Freq=) Measurement S (apparent power) (S =) Measurement SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 542
Min/Max meter - (PdMin=) Active Power Demand Maximum Min/Max meter - (PdMax=) Reactive Power Minimum Min/Max meter - (QdMin=) Reactive Power Maximum Min/Max meter - (QdMax=) Apparent Power Minimum Min/Max meter - (SdMin=) SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 543
Reactive Power Maximum Min/Max meter - (Qmax=) Apparent Power Minimum Min/Max meter - (Smin=) Apparent Power Maximum Min/Max meter - (Smax=) Frequency Minimum (fmin=) Min/Max meter - Frequency Maximum (fmax=) Min/Max meter - SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 544
Measurement 30705 Qb (reactive power, phase B) (Qb Measurement 30706 Qc (reactive power, phase C) (Qc Measurement 30707 Power Factor, phase A (PFa =) Measurement 30708 Power Factor, phase B (PFb =) Measurement SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 545
Functions, Settings, Information F.5 Measured Values Description Function IEC 60870-5-103 Configurable in Matrix 30709 Power Factor, phase C (PFc =) Measurement 30800 Voltage VX (VX =) Measurement 30801 Voltage phase-neutral (Vph-n =) Measurement SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Combination devices are bay devices with protection functions and a control display. Combination matrix From DIGSI V4.6 onward, up to 32 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination (IRC combination). Which device exchanges which information is defined with the help of the combination matrix.
Page 550
Device container In the Component View, all SIPROTEC 4 devices are assigned to an object of type Device container. This object is a special object of DIGSI Manager. However, since there is no component view in DIGSI Manager, this object only becomes visible in conjunction with STEP 7.
Page 551
External double point indication via an ETHERNET connection, device-specific → Double point indication ExDP_I External double point indication via an ETHERNET connection, intermediate position 00, device-specific → Double point indication ExMV External metered value via an ETHERNET connection, device-specific SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 552
This data is split up into several files. One file contains details about the fundamental project structure. This also includes, for example, information detailing which fields exist in this project. This file is called a HV project description file. SIPROTEC 4, 7SJ80, Manual E50417-G1140-C343-A8, Edition 12.2017...
Page 553
An Ethernet network is used for data transfer. IEC address Within an IEC bus a unique IEC address has to be assigned to each SIPROTEC 4 device. A total of 254 IEC addresses are available for each IEC bus. IEC communication branch Within an IEC communication branch the users communicate on the basis of the IEC60-870-5-103 protocol via an IEC bus.
Page 554
(energy purchase/supply, energy transportation). MLFB MLFB is the abbreviation for "MaschinenLesbare FabrikateBezeichnung" (machine-readable product designa- tion). This is the equivalent of an order number. The type and version of a SIPROTEC 4 device is coded in the order number. Modem connection This object type contains information on both partners of a modem connection, the local modem and the remote modem.
Page 555
Each object has properties. These might be general properties that are common to several objects. An object can also have specific properties. Off-line In offline mode a connection to a SIPROTEC 4 device is not required. You work with data which are stored in files. On-line When working in online mode, there is a physical connection to a SIPROTEC 4 device.
Page 556
2, PROFIBUS. It defines the functional, electrical, and mechanical properties for a bit-serial field bus. PROFIBUS address Within a PROFIBUS network a unique PROFIBUS address has to be assigned to each SIPROTEC 4 device. A total of 254 PROFIBUS addresses are available for each PROFIBUS network.
Page 557
SIPROTEC 4 Variant This object type represents a variant of an object of type SIPROTEC 4 device. The device data of this variant may well differ from the device data of the original object. However, all variants derived from the original object have the same VD address as the original object.
Page 558
Users From DIGSI V4.6 onward , up to 32 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination. The individual participating devices are called users. A VD (Virtual Device) includes all communication objects and their properties and states that are used by a communication user through services.
Need help?
Do you have a question about the SIPROTEC 4 and is the answer not in the manual?
Questions and answers