Functions
2.27 Breaker Control
corresponding actual status. Cancellation via the ESC key is possible at any time before the control command
is issued.
During normal processing, the control display indicates the new actual status after the control command was
executed and the message command end appears at the lower display edge. In case of control commands
with feedback, the message FB reached is displayed for a short time before this.
If the attempted command fails, because an interlocking condition is not met, an error message appears in the
display. The message indicates why the control command was not accepted (see also SIPROTEC 4 System
Description). This message must be acknowledged with ENTER before any further control commands can be
issued.
Operation using DIGSI
Switchgear devices can be controlled via the operator control interface with a PC using the DIGSI operating
program. The procedure to do so is described in the SIPROTEC 4 System Description (Control of Switchgear).
Operation Using the System Interface
Control of switching devices can be performed via the serial system interface and a connection to the switch-
gear control and protection system. It is therefore required to ensure that the required peripherals physically
exist in the device and in the power system. Furthermore, certain settings for the serial interface in the device
need to be carried out (see SIPROTEC 4 System Description).
2.27.1.2

Information List

No.
Information
-
52Breaker
-
52Breaker
-
Disc.Swit.
-
Disc.Swit.
-
GndSwit.
-
GndSwit.
-
52 Open
-
52 Close
-
Disc.Open
-
Disc.Close
-
GndSw Open
-
GndSw Cl.
-
UnlockDT
-
Q2 Op/Cl
-
Q2 Op/Cl
-
Q9 Op/Cl
-
Q9 Op/Cl
-
Fan ON/OFF
-
Fan ON/OFF
31000
Q0 OpCnt=
31001
Q1 OpCnt=
31002
Q2 OpCnt=
31008
Q8 OpCnt=
31009
Q9 OpCnt=
354
Type of
Comments
Informa-
tion
CF_D12
52 Breaker
DP
52 Breaker
CF_D2
Disconnect Switch
DP
Disconnect Switch
CF_D2
Ground Switch
DP
Ground Switch
IntSP
Interlocking: 52 Open
IntSP
Interlocking: 52 Close
IntSP
Interlocking: Disconnect switch Open
IntSP
Interlocking: Disconnect switch Close
IntSP
Interlocking: Ground switch Open
IntSP
Interlocking: Ground switch Close
IntSP
Unlock data transmission via BI
CF_D2
Q2 Open/Close
DP
Q2 Open/Close
CF_D2
Q9 Open/Close
DP
Q9 Open/Close
CF_D2
Fan ON/OFF
DP
Fan ON/OFF
VI
Q0 operationcounter=
VI
Q1 operationcounter=
VI
Q2 operationcounter=
VI
Q8 operationcounter=
VI
Q9 operationcounter=
SIPROTEC 4, 7SJ62/64, Manual