Information List - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.22 Temperature Detection via RTD Boxes
Addr.
Parameter
9105
RTD10 STAGE 2
9106
RTD10 STAGE 2
9111A
RTD11 TYPE
9112A
RTD11 LOCATION
9113
RTD11 STAGE 1
9114
RTD11 STAGE 1
9115
RTD11 STAGE 2
9116
RTD11 STAGE 2
9121A
RTD12 TYPE
9122A
RTD12 LOCATION
9123
RTD12 STAGE 1
9124
RTD12 STAGE 1
9125
RTD12 STAGE 2
9126
RTD12 STAGE 2

Information List

2.22.4
No.
Information
264
Fail: RTD-Box 1
267
Fail: RTD-Box 2
14101
Fail: RTD
14111
Fail: RTD 1
14112
RTD 1 St.1 p.up
312
Setting Options
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Type of
Comments
Informa-
tion
OUT
Failure: RTD-Box 1
OUT
Failure: RTD-Box 2
OUT
Fail: RTD (broken wire/shorted)
OUT
Fail: RTD 1 (broken wire/shorted)
OUT
RTD 1 Temperature stage 1 picked up
Default Setting
Comments
120 °C
RTD10: Temperature Stage 2
Pickup
248 °F
RTD10: Temperature Stage 2
Pickup
Not connected
RTD11: Type
Other
RTD11: Location
100 °C
RTD11: Temperature Stage 1
Pickup
212 °F
RTD11: Temperature Stage 1
Pickup
120 °C
RTD11: Temperature Stage 2
Pickup
248 °F
RTD11: Temperature Stage 2
Pickup
Not connected
RTD12: Type
Other
RTD12: Location
100 °C
RTD12: Temperature Stage 1
Pickup
212 °F
RTD12: Temperature Stage 1
Pickup
120 °C
RTD12: Temperature Stage 2
Pickup
248 °F
RTD12: Temperature Stage 2
Pickup
C53000-G1140-C207-8, Edition 08.2016
SIPROTEC 4, 7SJ62/64, Manual

Hide quick links:

Advertisement

Table of Contents
loading