2.3 Directional Overcurrent Protection 67, 67N
Interaction with Automatic Reclosing Function (ground)
If reclosing follows, high-speed and simultaneous closing in the event of a fault with 67N-2 is usually desired.
If the fault still exists after reclosing, the 67N-1 or 67N-TOC element is initiated with graded tripping times,
that is, the 67N-2 or 67N-3 element is blocked. For this purpose, parameter 1614 67N-2 active or 1632
67N-3 active is used to determine whether the 67N-2 or 67N-3 element is influenced by the release signal
of the internal or an external automatic reclosing device or not. The setting with 79 active means that the
67N- 2 or 67N-3 element is only released if the automatic reclosing function is not blocked. If this is not
desired, the setting always is selected so that the 67N-2 or 67N-3 element is always active as configured.
The integrated automatic reclosing function of 7SJ62/64 also provides the option to individually determine for
each overcurrent element whether tripping or blocking is to be carried out instantaneously, unaffected by the
AR with time delay (see Section
2.3.11

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
1501
FCT 67/67-TOC
1502
67-2 PICKUP
1503
67-2 DELAY
1504
67-1 PICKUP
1505
67-1 DELAY
1507
67-TOC PICKUP
1508
67 TIME DIAL
1509
67 TIME DIAL
1510
67-TOC Drop-out
1511
67- IEC CURVE
1512
67- ANSI CURVE
1513A
MANUAL CLOSE
1514A
67-2 active
106
2.16 Automatic Reclosing System
C
Setting Options
OFF
ON
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
67-3 instant.
67-2 instant.
67-1 instant.
67-TOC instant.
Inactive
with 79 active
always
79).
Default Setting
Comments
OFF
67, 67-TOC Phase Time
Overcurrent
2.00 A
67-2 Pickup
10.00 A
0.10 sec
67-2 Time Delay
1.00 A
67-1 Pickup
5.00 A
0.50 sec
67-1Time Delay
1.00 A
67-TOC Pickup
5.00 A
0.50 sec
67-TOC Time Dial
5.00
67-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
67-2 instant.
Manual Close Mode
always
67-2 active
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016