Settings; Information List - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

intermittent ground fault is present or not. For with oper. dir., recording starts when a direction pulse in
the direction parameterized at 3402 has been detected.
2.15.3

Settings

Addr.
Parameter
3401
Dir. Interm. EF
3402
Direction
3403
No. of pulses
3404
Monitoring time
3405
Vgnd> / 3V0>
3406
Pickup
2.15.4

Information List

No.
Information
6951
>dIEF block
6961
dIEF OFF
6962
dIEF blocked
6963
dIEF active
6972
dIEF pick up
6973
dIEF TRIP
6974
No.forward=
6975
No.reverse=
6976
No.undef.=
6979
dIEF ALARM
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Setting Options
OFF
ON
ON with GF log
Alarm Only
Forward
Reverse
2 .. 50
0.04 .. 10.00 sec
2.0 .. 100.0 V
with Vgnd/3V0>
with oper. dir.
Type of
Comments
Informa-
tion
SP
>Block directional interm. E/F prot.
OUT
Dir. Interm. E/F prot. is switched off
OUT
Dir. Interm. E/F prot. is blocked
OUT
Dir. Interm. E/F prot. is active
OUT
dIEF: pick up
OUT
dIEF: Trip
VI
dIEF: No. of detected forward pulses =
VI
dIEF: No. of detected reverse pulses =
VI
dIEF: No. of detected undefined pulses =
OUT
dIEF: Alarm
2.15 Dir. Intermittent earth fault protection
Default Setting
Comments
OFF
Dir. Intermittent earth fault
protection
Forward
Direction to be protected
5
Pulse no. for detecting the interm.
E/F
2.00 sec
Monitoring time after pickup
detected
20.0 V
Vgnd> measured / 3V0> calcu-
lated
with Vgnd/3V0>
Pickup of the function
Functions
235