Mounting and Commissioning
3.1 Mounting and Connections
Pickup Voltages of BI6 to BI7
Table 3-18
Binary Input
BI6
BI7
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 220 V and AC 115 V or 115 V to 230
V
3)
Use only with pickup voltages DC 220 V or 250 V
Jumpers X71, X72 and X73 on the input/output board C-I/O-11 are used to set the bus address and must not
be changed. The following table lists the jumper presettings.
Mounting location:
with housing size
with housing size
with housing size
Bus Address
Table 3-19
Jumper
X71
X72
X73
392
Jumper settings for Pickup Voltages of the binary inputs BI6 and BI7 on the input/output
board C-I/O-11
Jumper
X21
X22
1
/
3
1
/
2
1
/
1
Jumper Settings of Bus Addresses of Input/Output Board C–I/O-11 for 7SJ64
Presetting
1-2 (H)
1-2 (H)
2-3 (L)
DC 19 V Pickup
1)
DC 88 V Pickup
L
M
L
M
Serial no. 2 in
Figure
Serial no. 2 in
Figure
Serial no. 2 in
Figure
2)
DC 176 V Pickup
H
H
3-5, slot 19
3-6, slot 33
3-7, slot 33 on right side
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
3)