Tank Leakage Protection - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.5 Single-Phase Overcurrent Protection
High-impedance Protection with 7SJ62/64
With 7SJ62/64 the sensitive measurement input INs or alternatively the insensitive measurement input Ι
used for high-impedance protection. As this is a current input, the protection detects current through the
resistor instead of the voltage across the resistor R.
Das
Figure 2-44
and measures its current.
Varistor B limits the voltage when internal faults occur. High voltage peaks emerging with transformer satura-
tion are cut by the varistor. At the same time, voltage is smoothed without reduction of the mean value.
[sj6x-ueb-einph-hochimpedanz3-141103, 1, en_US]
Figure 2-44
For protection against overvoltages it is also important that the device is directly connected to the grounded
side of the current transformers so that the high voltage at the resistor can be kept away from the device.
For generators, motors and shunt reactors, the high-impedance differential protection can be used analo-
gously. All current transformers at the overvoltage side, the undervoltage side and the current transformer at
the neutral point have to be connected in parallel when using auto-transformers.
In principle, this procedure can be applied to every protected object. When applied as busbar protection, for
example, the device is connected to the parallel connection of all feeder current transformers via the resistor.

Tank Leakage Protection

2.5.3
Application Example
The tank leakage protection has the task to detect ground leakage — even high-ohmic — between a phase
and the frame of a power transformer. The tank must be isolated from ground. A conductor links the tank to
ground, and the current through this conductor is fed to a current input of the relay. When tank leakage
occurs, a fault current (tank leakage current) will flow through the grounding conductor to ground. This tank
leakage current is detected by the single-phase overcurrent protection as an overcurrent; an instantaneous or
delayed trip command is issued in order to disconnect all sides of the transformer.
A high-sensitivity single-phase current input is used for tank leakage protection.
120
illustrates the connection scheme. The protection device is connected in series to resistor R
Connection diagram of the ground fault differential protection according to the high-impe-
dance principle
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
is
N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents