Siemens SIPROTEC 7SJ80 Manual

Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection; motor protection; voltage and frequency protection;
Hide thumbs Also See for SIPROTEC 7SJ80:

Advertisement

SIPROTEC
Overcurrent Protection
7SJ80
Motor Protection
7SK80
Voltage and Frequency
Protection
7RW80
Communication Modules
Modbus
Bus mapping
Edition: September 2010
C53000-L2240-A320-3
Preface
Table of contents
Modbus Register Map Organization
Index
1

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7SJ80

  • Page 1 Preface Table of contents Modbus Register Map Organization SIPROTEC Index Overcurrent Protection 7SJ80 Motor Protection 7SK80 Voltage and Frequency Protection 7RW80 Communication Modules Modbus Bus mapping Edition: September 2010 C53000-L2240-A320-3...
  • Page 2 Registered Trademarks We are grateful for any improvements that you care to suggest. SIPROTEC and DIGSI are registered trademarks of SIEMENS AG. Modbus and Modbus Plus are trademarks of Modicon, Inc. We reserve the right to make technical improvements Other designations in this manual may be trademarks whose use by third without notice.
  • Page 3: Preface

    SIPROTEC communication modules, C53000-L1840-C001-03 Modbus - Communication profile You can order the manuals via the internet under http://www.siprotec.com or contact your local Siemens representative. The Modbus specification with a detailed explanation of the Modbus protocol is Modbus contained in: specification Modbus over Serial Line Specification &...
  • Page 4 “SIPROTEC communication modules, Modbus - Communication profile”). The following have to be used for device parameterization: • DIGSI version 4.82 or higher, • Modbus Standard mapping 3-1 For questions regarding the SIPROTEC system, please contact your Siemens Additional representative. support...
  • Page 5 Preface Warning! During operation of electrical equipment, certain parts of these devices are under high voltage. Severe personal injury or property damage can result if the device is not handled properly. Only qualified personnel should work on this equipment or in the vicinity of this equipment.
  • Page 6 Preface SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 7: Revision Index

    Revision index Listing of the changes between the editions of this manual: Modified chapters / Edition Reasons of modification pages First edition, doc. no.: C53000-L2240-A320-1 15.09.2008 4, 22 Correction, doc. no.: C53000-L2240-A320-2 10.10.2008 Preface Correction, doc. no.: C53000-L2240-A320-3 Chapter 1.2 new 29.09.2010 7RW80 added SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80...
  • Page 8 Revision index SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 9: Table Of Contents

    Table of contents Preface..............................3 Revision index ............................. 7 Modbus Register Map Organization ....................11 Explanations ......................... 12 Functional Scope........................14 Coil Status Registers (0X register) ..................17 1.3.1 Registers 00001 to 00018: Double commands ..............17 1.3.2 Registers 00019 to 00043: Single commands and taggings ..........18 1.3.3 Registers 00044 to 00048: Internal commands..............
  • Page 10 Table of contents Glossary.............................. 39 Index..............................41 SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 11: Modbus Register Map Organization

    Modbus Register Map Organization This chapter describes the register map organization of the Modbus slave for the SIPROTEC devices 7SJ80, 7SK80 and 7RW80. Explanations Functional Scope Coil Status Registers (0X register) Input Status Registers (1X register) Input Registers (3X register) Holding Registers (4X register) SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 12: Explanations

    Modbus Register Map Organization Explanations One standard mapping (standard mapping 3-1) is available for setting the parameters of the SIPROTEC devices 7SJ80, 7SK80 and 7RW80. Standard mapping 3-1 contains: • Coil Status registers: − 9 double commands incl. 9 double-point indications as checkback indication −...
  • Page 13 Modbus Register Map Organization Chapters 1.3 to 1.6 define the allocation (in the following also called “mapping“) of the Register map data objects of the SIPROTEC devices 7SJ80, 7SK80 and 7RW80 to the positions in the Modbus registers. Note: The examples shown in this chapter 1.1 do not necessarily correspond to the real allocation of the objects in the bus mapping.
  • Page 14: Functional Scope

    Modbus Register Map Organization Functional Scope Depending of the functional scope, some of the following described functions, annun- ciations, commands, measured and metered values are not available. 7SJ80 Table 1-1 7SJ80 Functional scope Function Ref. to Chapter Setting Group Change Option 1.3.3 Oscillographic Fault Records 50/51 (Charac.
  • Page 15 Modbus Register Map Organization 7SK80 Table 1-2 7SK80 Functional scope Function Ref. to Chapter Setting Group Change Option 1.3.3 Oscillographic Fault Records 50/51 (Charac. Phase) Overcurrent Protection 1.4.3 50N/51N (Charac. Ground) Overcurrent Protection 1.4.3 67N, 67N-TOC Directional Overcurrent Protection 1.4.4 Cold Load Pickup 1.4.4 2nd Harmonic Inrush Restraint...
  • Page 16 Modbus Register Map Organization 7RW80 Table 1-3 7RW80 Functional scope Function Ref. to Chapter Setting Group Change Option Oscillographic Fault Records 24 Overexcitation Protection Jump of Voltage Vector 27, 59 Under/Overvoltage Protection 1.4.7 VT Broken wire supervision 81 Over/Underfrequency Protection 1.4.6 Load Restoration 25 Function group 1 Synchronism and Voltage Check...
  • Page 17: Coil Status Registers (0X Register)

    Modbus Register Map Organization Coil Status Registers (0X register) The Coil Status register block allows the Modbus master to scan • command outputs through the output relays of the devices (external commands), • manipulation of taggings (internal commands) that can be changed using Modbus. Furthermore, these registers can be used to execute switching operations and internal commands.
  • Page 18: Registers 00019 To 00043: Single Commands And Taggings

    Modbus Register Map Organization Internal Register Designation of the SIPROTEC objects Comment object 00015 <user-defined> ON not pre-allocated 00016 <user-defined> OFF 00017 <user-defined> ON not pre-allocated 00018 <user-defined> OFF 1.3.2 Registers 00019 to 00043: Single commands and taggings • User-defined single commands and taggings with the corresponding checkback indications can be routed on these positions as a "Source/destination system interface"...
  • Page 19: Registers 00044 To 00048: Internal Commands

    Modbus Register Map Organization Internal Register Designation of the SIPROTEC objects Comment object 00039 <user-defined> not pre-allocated 00040 <user-defined> not pre-allocated 00041 <user-defined> not pre-allocated 00042 <user-defined> not pre-allocated 00043 <user-defined> not pre-allocated 1.3.3 Registers 00044 to 00048: Internal commands Internal Register Designation of the SIPROTEC objects Comment...
  • Page 20 Modbus Register Map Organization Changing the setting group: • In order to change the setting group, the value "1" = ON must be transmitted to the corresponding register of the setting group to be activated. • Switching ON one setting group automatically switches OFF the currently active setting group.
  • Page 21: Registers 00257 To 00264: Exception Flags

    Modbus Register Map Organization 1.3.4 Registers 00257 to 00264: Exception flags • Registers are write-protected. • The contents of these registers are also readable using the function “Read Exception Status” (function code 7). • Installation-specific SIPROTEC objects can be routed to these register positions as a “Destination system interface”...
  • Page 22: Input Status Registers (1X Register)

    Modbus Register Map Organization Input Status Registers (1X register) The Input Status register block allows the Modbus master to scan the current status of the input channels and the annunciations generated in the SIPROTEC device (protection annunciations, status annunciations etc.). Note: •...
  • Page 23: Registers 10025 To 10033: Auto-Reclose Function

    Modbus Register Map Organization Internal Register Designation of the SIPROTEC objects Comment object 10019 <user-defined> not pre-allocated 10020 <user-defined> not pre-allocated 10021 <user-defined> not pre-allocated 10022 <user-defined> not pre-allocated 10023 <user-defined> not pre-allocated 10024 <user-defined> not pre-allocated 1.4.2 Registers 10025 to 10033: Auto-Reclose Function Internal Register Designation of the SIPROTEC objects Comment...
  • Page 24: Registers 10046 To 10053: Directional Overcurrent Protection

    Modbus Register Map Organization Internal Register Designation of the SIPROTEC objects Comment object 10044 PhC InrushBlk 1 = Phase C trip blocked by inrush detection 1842 10045 INRUSH X-BLK 1 = Cross blk: PhX blocked PhY 1843 1.4.4 Registers 10046 to 10053: Directional Overcurrent Protection Internal Register Designation of the SIPROTEC objects Comment...
  • Page 25: Registers 10064 To 10069: Under/Overvoltage Protection

    Modbus Register Map Organization 1.4.7 Registers 10064 to 10069: Under/Overvoltage Protection Internal Register Designation of the SIPROTEC objects Comment object 10064 27 ACTIVE 1 = 27 Undervoltage protection is ACTIVE 6532 10065 27-1 picked up 1 = 27-1 Undervoltage picked up 6533 10066 27-1 TRIP...
  • Page 26: 1.4.10 Registers 10084 To 10086: Startup Supervision Of Motors

    Modbus Register Map Organization 1.4.10 Registers 10084 to 10086: Startup Supervision of Motors Internal Register Designation of the SIPROTEC objects Comment object 10084 START-SUP ACT 1 = Startup supervision is ACTIVE 6813 10085 START-SUP TRIP 1 = Startup supervision TRIP 6821 10086 START-SUP pu...
  • Page 27: Input Registers (3X Register)

    Modbus Register Map Organization Input Registers (3X register) The Input register block allows the Modbus master to read measured values. Note: Depending on the protection functions provided (MLFB selection or configuration) and the connected analog inputs, not all of the indicated measured values (and corresponding Modbus registers) may be available.
  • Page 28 Modbus Register Map Organization Scaling Internal Designation of the Register Comment (32767 corresponds object SIPROTEC objects to ...) 30001 Ia = 3276.7 A 30002 Ib = 3276.7 A 30003 Ic = 3276.7 A 30004 In = 3276.7 A 30005 Va = 327.67 kV 30006 Vb =...
  • Page 29: Holding Registers (4X Register)

    Modbus Register Map Organization Holding Registers (4X register) The Holding register block allows the Modbus master to read system and diagnostic information, statistic values as well as to execute time synchronization of the SIPROTEC device. Holding registers are also used for reading the Event recorder entries (“Sequence of Events”).
  • Page 30: Registers 40065 To 40069: Time Synchronization

    Modbus Register Map Organization 1.6.2 Registers 40065 to 40069: Time synchronization • Refer to chap. “Time synchronization” in the manual “SIPROTEC Communication module, Modbus - Communication profile” (ref. to page 3). Designation of the Register Comment SIPROTEC objects 40065 Milliseconds 40066 Hours / Minutes Time/Date transfer registers...
  • Page 31: Register 40129: Diagnostics

    Modbus Register Map Organization 1.6.3 Register 40129: Diagnostics • Registers are write-protected. • The contents of this register are also readable using function "Diagnostics" (function code 8), subfunction "Return Diagnostic Register" (function code 2). • Ref. to chap. “Bus-specific parameters” in the manual “SIPROTEC Communication module, Modbus - Communication profile”...
  • Page 32: Registers 40201 To 40208: Metered Measurands

    Modbus Register Map Organization 1.6.4 Registers 40201 to 40208: Metered measurands • Registers are write-protected. The scaling of the metered measurands, which are derived from measured values, Scaling refers to: 60000 impulses per hour for V = V and I = I = Full Scale Voltage (parameter address 1101) = Full Scale Current (parameter address 1102) In the parameter set is configured:...
  • Page 33: Registers 40301 To 40324: Statistic Values

    Modbus Register Map Organization 1.6.5 Registers 40301 to 40324: Statistic values • Registers are write-protected. • Statistic values can be routed on these positions as a "Destination system interface" using the DIGSI Configuration matrix. Scaling Internal Designation of the Register Comment (100000 corresponds object...
  • Page 34: Registers 40351 To 40520: Min/Max Values Of Measured Values

    Modbus Register Map Organization 1.6.6 Registers 40351 to 40520: Min/max values of measured values • Registers are write-protected. • Ref. to chap. 1.5 for additional notes regarding scaling of metered measurands. • You find regarding the data type “Absolute time” in the manual “SIPROTEC communication modules, Modbus - Communication profile”...
  • Page 35 Modbus Register Map Organization Scaling Internal Designation of the Register Comment (32768 corresponds object SIPROTEC objects to ...) 40396 Vb-nMax = Vb-nMax 327.67 kV 40397 Date and time of Vb-n Max Vb-nMax - Time/Date 40400 40401 Vc-nMin = Vc-nMin 327.67 kV 40402 Date and time of Vc-n Min Vc-nMin - Time/Date...
  • Page 36 Modbus Register Map Organization Scaling Internal Designation of the Register Comment (32768 corresponds object SIPROTEC objects to ...) 40451 fmin = Frequency Minimum 327.67 Hz 40452 Date and time of fmin fmin - Time/Date 40455 40456 fmax = Frequency Maximum 327.67 Hz 40457 Date and time of fmax...
  • Page 37: Registers 40601 To 40626: Event Recorder ("Sequence Of Events")

    Modbus Register Map Organization 1.6.7 Registers 40601 to 40626: Event recorder ("Sequence of Events") • Registers are write-protected (with the exception of “SOE_Control”). • Information regarding the handshake register, the data type “Message block” and the evaluation of Event recorder entries you find in the manual “SIPROTEC communication modules, Modbus - Communication profile”...
  • Page 38 Modbus Register Map Organization SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 39 Glossary Universal asynchronous interface module with (electrical) isolated RS485 interface for the SIPROTEC devices made by Siemens Universal asynchronous communication module with optical interface for the SIPROTEC devices made by Siemens Continuous Function Chart Cyclical Redundancy Check Double Command Parameterization system for SIPROTEC devices...
  • Page 40 Glossary SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...
  • Page 41 Index ........23 Automatic recloser status Sequence of events →Event record ..........18 Single commands ............33 Statistic values .........20 Changing the setting group ........20 Control mode REMOTE ......4 Target audience of the manual ........23 Time overcurrent protection ..........30 Time synchronization ........5 ..........17 Typographic conventions Double commands ........17...
  • Page 42 Index SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80 C53000-L2240-A320-3...

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents