Ground Fault Check; Polarity Check For Current Input Ι - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Ground Fault Check

3.3.11
Ungrounded Systems
The ground fault check is only necessary if the device is connected to an isolated or resonant-grounded system
and the ground fault detection is applied. The device must thus have been preset during configuration of the
device functions to Sens. Gnd Fault (address 131) not equal to Disabled. Furthermore, the direction
characteristic (S.Gnd.F.Dir.Ch, address 130) must be set to cos φ / sin φ.
If none of this is the case, this section is not relevant.
The primary check serves to find out the correct polarity of the transformer connections for the determination
of the ground fault direction.
!
DANGER
Energized equipment of the power system ! Capacitive coupled voltages at disconnected equipment of the
power system !
Non-observance of the following measure will result in death, severe personal injury or substantial
property damage.
Primary measurements must only be carried out on disconnected and grounded equipment of the
²
power system !
Using the primary ground fault method a most reliable test result is guaranteed. Therefore please proceed as
follows:
Isolate the line and ground it on both ends. During the whole testing procedure the line must be open at
the remote end.
Make a test connection between a single phase and ground. On overhead lines it can be connected
anywhere, however, it must be located behind the current transformers (looking from the busbar of the
feeder to be checked). Cables are grounded on the remote end (sealing end).
Remove the protective grounding of the line.
Connect a circuit breaker to the line end that is to be tested.
Check the direction indication (LED if allocated)
The faulty phase (FNo 1272 for A or 1273 for B or 1274 for C) and the direction of the line, i.e.
Forward (FNo 1276) must be indicated in the ground fault protocol.
The active and reactive components of the ground current are also indicated (
reactive current
message
SensGnd Reverse (FNo. 1277), either the current or voltage transformer terminals are
swapped in the neutral path. If message
be too low.
Deenergize and ground the line.
The test is then finished.
Polarity Check for Current Input Ι
3.3.12
General
If the standard connection of the device is used with current input Ι
of current transformers (see also connection circuit diagram in Appendix
correct polarity of the ground current path usually occurs automatically.
If, however, current Ι
Appendix
C Connection
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
INs Real , FNo. 701) is the most relevant for isolated systems. If the display shows the
SensGnd undef. (FNo 1278) appears, the ground current may
E
is derived from a separate summation CT (see e.g. a connection circuit diagram in the
N
Examples), an additional direction check with this current is necessary.
Mounting and Commissioning
3.3 Commissioning
INs Reac , FNo. 702). The
connected in the neutral point of the set
N
C Connection
Examples), then the
SensGnd
429

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents