Functions
2.8 Motor Protection
Addr.
Parameter
4311
ROTOR OVERLOAD
4401
Load Jam Prot.
4402
Load Jam I>
4403
TRIP DELAY
4404
I Alarm
4405
ALARM DELAY
4406
T Start Blk.
2.8.4.2

Information List

No.
Information
4822
>BLOCK 66
4823
>66 emer.start
4824
66 OFF
4825
66 BLOCKED
4826
66 ACTIVE
4827
66 TRIP
4828
>66 RM th.repl.
4829
66 RM th.repl.
4834
Rot.overl.TRIP
4835
Rot.overl.alarm
6801
>BLOCK 48
6805
>48 Rot. locked
6811
48 OFF
6812
48 BLOCKED
6813
48 ACTIVE
6821
48 TRIP
6822
48 Rotor locked
6823
48 pickup
10020
>BLOCK Load Jam
10021
Load Jam BLOCK.
10022
Load Jam OFF
10023
Load Jam ACTIVE
10024
Load Jam alarm
10025
Load Jam pickup
10026
Load Jam TRIP
162
C
Setting Options
ON
OFF
Alarm Only
OFF
ON
Alarm Only
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
0.00 .. 600.00 sec
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
0.00 .. 600.00 sec
0.00 .. 600.00 sec
Type of
Comments
Informa-
tion
SP
>BLOCK 66 Motor Startup Counter
SP
>66 Mot.St.Cnt: Emergency start
OUT
66 Motor Startup Counter OFF
OUT
66 Motor Startup Counter BLOCKED
OUT
66 Motor Startup Counter ACTIVE
OUT
66 Motor Startup Counter TRIP
SP
>66 Mot.St.Cnt: Reset therm.memory rotor
OUT
66 Mot.St.Cnt: therm. memory rotor reset
OUT
Rotor thermal overload TRIP
OUT
Rotor thermal overload alarm
SP
>BLOCK 48 Motor Startup Time Supervision
SP
>48/14 Mot.St.Time Sup. Rotor locked
OUT
48 Motor Startup Time Supervision OFF
OUT
48 Motor Startup Time Superv. BLOCKED
OUT
48 Motor Startup Time Supervision ACTIVE
OUT
48 Motor Startup Time Supervision TRIP
OUT
48/14 Mot.St.Time Sup. Rotor locked
OUT
48 Motor Startup Time Superv. picked up
SP
>BLOCK Load Jam Protection
OUT
Load Jam Protection is BLOCKED
OUT
Load Jam Protection is OFF
OUT
Load Jam Protection is ACTIVE
OUT
Load Jam Protection alarm
OUT
Load Jam Protection picked up
OUT
Load Jam Protection TRIP
Default Setting
Comments
ON
Rotor Overload Protection
OFF
Load Jam Protection
2.00 A
Load Jam Tripping
Threshold
10.00 A
1.00 sec
Load Jam Trip Delay
1.80 A
Load Jam Alarm Threshold
9.00 A
1.00 sec
Load Jam Alarm Delay
10.00 sec
Load Jam Blocking after
motor start
SIPROTEC 4, 7SJ62/64, Manual