Siemens SIPROTEC 4 User Manual page 26

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Introduction
1.3 Characteristics
In-rush restraint with second harmonic current quantities
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Directional Time Overcurrent Protection 67, 67N
Four elements each for phase and ground operate in parallel to the non-directional overcurrent protec-
tion elements. Their pickup values and time delays can be set independently of these
Direction determination with cross-polarized voltages and voltage memory and dynamically unlimited
direction sensitivity
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summa-
tion current faults.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recog-
nized
Detection of cold load condition via circuit breaker position or current threshold
Activation via automatic reclosure (AR) is possible
Activation also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive or insensitive ground current transformer
Suitable as differential protection that includes the neutral point current on transformer side, generator
side or motor side or for a grounded reactor set
As tank leakage protection against abnormal leakage currents between transformer tanks and ground.
Voltage Protection 27, 59
Two element undervoltage detection via the positive-sequence system of the voltages, phase-to-phase or
phase-to-ground voltages
Choice of current supervision for 27-1 and 27-2
Two-element overvoltage detection via the positive sequence system voltages, negative sequence system
voltages, phase-to-phase or phase-to-ground voltages
For a single-phase connection, the connected single-phase phase-to-ground or phase-to-phase voltage is
evaluated
Settable dropout ratio for all elements of the undervoltage and overvoltage protection.
Negative Sequence Protection 46
Evaluation of the negative sequence component of the currents
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common
standards are available for 46-TOC.
Motor Starting Protection 48
Inverse time tripping characteristic based on an evaluation of the motor starting current
Definite time delay for blocked rotor.
26
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents