Service Conditions; Certifications; Constructive Designs - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Technical Data
4.1 General Device Data
Permissible temporary operating temperature
(tested for 96 h)
Recommended for permanent operation (according
to IEC 60255-6)
Limiting Temperatures for Storage
Limiting temperatures for transport
STORE AND TRANSPORT THE DEVICE WITH FACTORY PACKAGING!
1
) UL–certified according to Standard 508 (Industrial Control Equipment):
Limiting temperatures for normal operation (i.e.
output relays not energized)
Limiting temperatures with maximum load (max.
cont. permissible energization of inputs and
outputs)
Humidity
Permissible humidity
Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor
subject to large fluctuations in temperature that may cause condensation to occur.

Service Conditions

4.1.8
The protective device is designed for use in an industrial environment and an electrical utility environment.
Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC).
In addition, the following is recommended:
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protec-
tive device should, as a rule, be equipped with suitable surge suppression components.
For substations with operating voltages of 100 kV and above, all external cables should be shielded with
a conductive shield grounded at both ends. For substations with lower operating voltages, no special
measures are normally required.
Do not withdraw or insert individual modules or boards while the protective device is energized. In with-
drawn condition, some components are electrostatically endangered; during handling the ESD stand-
ards (for Electrostatic Sensitive Devices) must be observed. They are not endangered when inserted into
the case.
4.1.9

Certifications

7SJ62**-*B***-****
7SJ62**-*E***-****
7SJ64**-*B***-****
7SJ64**-*C***-****
7SJ64**-*E***-****
7SJ64**-*F***-****
4.1.10

Constructive Designs

Case
448
UL listing
Models with threaded
terminals
–20 °C to +70 °C or –4 °F to +158 °F
(legibility of the display may be restricted from +55 °C
or +131 °F
–5 °C to +55 °C or +23 °F to +131 °F
–25 °C to +55 °C or –13 °F to +131 °F
–25 °C to +70 °C or –13 °F to +158 °F
–20 °C to +70 °C or –4 °F to +158 °F
–5 °C to +55 °C or +23 °F to +131 °F für 7SJ62
–5 °C to +40 °C or +23 °F to +104 °F für 7SJ64
Mean value per year ≤ 75 % relative humidity;
on 56 days of the year up to 93 % relative humidity;
condensation must be avoided!
UL recognition
7SJ62**-*D***-****
7SJ64**-*A***-****
7SJ64**-*D***-****
7SJ64**-*G***-****
7XP20
C53000-G1140-C207-8, Edition 08.2016
Types with plug-in
terminals
SIPROTEC 4, 7SJ62/64, Manual