Information List - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A
46 T DROP-OUT

Information List

2.7.5
No.
Information
5143
>BLOCK 46
5151
46 OFF
5152
46 BLOCKED
5153
46 ACTIVE
5159
46-2 picked up
5165
46-1 picked up
5166
46-TOC pickedup
5170
46 TRIP
5171
46 Dsk pickedup
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
C
Setting Options
1A
0.05 .. 2.00 A
5A
0.25 .. 10.00 A
0.50 .. 15.00 ; ∞
0.05 .. 3.20 sec; ∞
Instantaneous
Disk Emulation
0.00 .. 60.00 sec
Type of
Comments
Informa-
tion
SP
>BLOCK 46
OUT
46 switched OFF
OUT
46 is BLOCKED
OUT
46 is ACTIVE
OUT
46-2 picked up
OUT
46-1 picked up
OUT
46-TOC picked up
OUT
46 TRIP
OUT
46 Disk emulation picked up
2.7 Negative Sequence Protection 46
Default Setting
Comments
0.90 A
46-TOC Pickup
4.50 A
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
Functions
143

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents