Single-Phase Overcurrent Protection; Description - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

2.5

Single-Phase Overcurrent Protection

The single-phase overcurrent protection evaluates the current that is measured by the sensitive Ι
normal Ι
input. Which input is used depends on the device version according to the order number.
N
Applications
Plain ground fault protection at a power transformer
Sensitive tank leakage protection.

Description

2.5.1
The single-phase definite time overcurrent ground protection is illustrated by the tripping characteristic as
shown in
Figure
sensitivity a particularly narrow band filter is used. The current pickup thresholds and tripping times can be
set. The detected current is compared to the pickup value 50 1Ph-1 PICKUP or 50 1Ph-2 PICKUP and
reported if this is violated. After expiry of the respective delay time 50 1Ph-1 DELAY or 50 1Ph-2 DELAY,
the trip command is issued. The two elements together form a two-stage protection. The dropout value is
approximately 95% of the pickup value for currents greater than I > 0.3 · INom.
The current filter is bypassed if currents are extremely high in order to achieve a short tripping time. This
occurs automatically as soon as the instantaneous value of the current exceeds the set value of the 50 1Ph-2
PICKUP element by at least factor 2 · √2.
[ueb-einph-kennlinie-020926-rei, 1, en_US]
Figure 2-40
The following figure shows the logic diagram of the single-phase overcurrent protection function.
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
2-40. The current to be measured is filtered by numerical algorithms. Because of the high
Two-stage characteristic of the single-phase time-overcurrent protection
2.5 Single-Phase Overcurrent Protection
- or the
NS
Functions
117