Siemens SIPROTEC 4 User Manual page 222

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Addr.
Parameter
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3119
51Ns PICKUP
3119
51Ns PICKUP
3120
51NsTIME DIAL
3120
51c TIME DIAL
3121A
50Ns T DROP-OUT
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
3126
RESET DELAY
3127
51Ns I T min
3127
51Ns I T min
3128
51Ns I T knee
3128
51Ns I T knee
3129
51Ns T knee
3130
PU CRITERIA
3131
M.of PU TD
3132
51Ns TD
3140
51Ns Tmin
3140
51Ns T min
3141
51Ns Tmax
3141
51Ns T max
3142
51Ns TIME DIAL
3143
51Ns Startpoint
3144
51Ns IEC CURVE
222
C
Setting Options
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
0.00 .. 320.00 sec; ∞
0.001 .. 1.400 A
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.003 .. 0.500 A
0.05 .. 4.00 sec; ∞
0.50 .. 15.00 ; ∞
0.00 .. 60.00 sec
Forward
Reverse
Non-Directional
0.001 .. 1.200 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
-45.0 .. 45.0 °
COS φ
SIN φ
0 .. 60 sec
0.003 .. 1.400 A
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
0.003 .. 0.650 A
1A
0.05 .. 17.00 A
5A
0.25 .. 85.00 A
0.20 .. 100.00 sec
Vgnd OR INs
Vgnd AND INs
1.00 .. 20.00 MofPU; ∞
0.01 .. 999.00 TD
0.05 .. 1.50
0.00 .. 30.00 sec
0.10 .. 30.00 sec
0.00 .. 30.00 sec
0.50 .. 200.00 sec
0.05 .. 15.00 sec; ∞
1.0 .. 4.0
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Default Setting
Comments
2.00 A
50Ns-1 Pickup
10.00 A
2.00 sec
50Ns-1 Time delay
0.100 A
51Ns Pickup
1.00 A
51Ns Pickup
5.00 A
0.004 A
51Ns Pickup
1.00 sec
51Ns Time Dial
5.00
51c Time dial
0.00 sec
50Ns Drop-Out Time Delay
Forward
67Ns-1 Direction
0.010 A
Release directional element
0.50 A
Release directional element
2.50 A
0.0 °
Correction Angle for Dir.
Determination
COS φ
Measurement method for
Direction
1 sec
Reset Delay
1.333 A
51Ns Current at const.
Time Delay T min
15.00 A
51Ns Current at const.
Time Delay T min
75.00 A
0.040 A
51Ns Current at Knee Point
5.00 A
51Ns Current at Knee Point
25.00 A
23.60 sec
51Ns Time Delay at Knee
Point
Vgnd OR INs
Sensitive Ground Fault
PICKUP criteria
Multiples of PU Time-Dial
0.20
51Ns Time Dial
1.20 sec
51Ns Minimum Time Delay
0.80 sec
51Ns Minimum Time Delay
5.80 sec
51Ns Maximum Time Delay
93.00 sec
51Ns Maximum Time Delay
(at 51Ns PU)
1.35 sec
51Ns Time Dial
1.1
51Ns Start Point of Inverse
Charac.
Normal Inverse
IEC Curve
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016