Settings - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.1 General
for line section 1, addresses 6006 (km) or 6007 (Miles)
for line section 2, addresses 6016 (km) or 6017 (Miles)
for line section 3, addresses 6026 (km) or 6027 (Miles)
The length set for the entire line must correspond to the sum of lengths configured for the line sections. A
deviation of 10% max. is admissible.
Recognition of Running Condition (only for Motors)
When the configured current value at Address 1107 I MOTOR START is exceeded, this will be interpreted as
motor starting. This parameter is used by the start-up time monitoring and overload protection functions.
For this setting the following should be considered:
A setting must be selected that is lower than the actual motor start-up current under all load and voltage
conditions.
During motor start-up the thermal replica of the overload protection is "frozen", i.e. kept at a constant
level. This threshold should not be set unnecessarily low since it limits the operating range of the over-
load protection for high currents during operation.
Inverting Power Measured Values/Metered Values
The directional values (power, power factor, work and related min., max., mean and setpoint values), calcu-
lated in the operational measured values, are usually defined a positive in the direction of the protected
object. This requires that the connection polarity for the entire device was configured accordingly in the
P.System Data 1 (compare also "Polarity of the Current Transformers", address 201). But it is also possible
to make different settings for the "forward" direction" for the protection functions and the positive direction
for the power etc., e.g. to have the active power supply (from the line to the busbar) displayed positively. To
do so, set address 1108 P,Q sign to reversed. If the setting is not reversed (default), the positive
direction for the power etc. corresponds to the "forward" direction for the protection functions. Section
4 Technical Data
2.1.6.3

Settings

The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
1101
FullScaleVolt.
1102
FullScaleCurr.
1103
RE/RL
1104
XE/XL
1105
x'
1106
x'
1107
I MOTOR START
1108
P,Q sign
1109
Line angle
1110
Line length
1111
Line length
54
provides a detailed list of the values in question.
C
Setting Options
0.10 .. 800.00 kV
10 .. 50000 A
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
1A
0.40 .. 10.00 A
5A
2.00 .. 50.00 A
not reversed
reversed
10 .. 89 °
0.1 .. 1000.0 km
0.1 .. 650.0 Miles
Default Setting
Comments
12.00 kV
Measurem:FullScale-
Voltage(Equipm.rating)
100 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1.00
Zero seq. compensating
factor RE/RL
1.00
Zero seq. compensating
factor XE/XL
0.2420 Ω/mi
feeder reactance per mile:
x'
0.0484 Ω/mi
0.1500 Ω/km
feeder reactance per km: x'
0.0300 Ω/km
2.50 A
Motor Start Current (Block
49, Start 48)
12.50 A
not reversed
P,Q operational measured
values sign
85 °
Line angle
100.0 km
Line length in kilometer
62.1 Miles
Line length in miles
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016