Siemens SIPROTEC 4 User Manual page 632

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A 46 T DROP-OUT
4101
FCT 48
4102
STARTUP CURRENT 48/66 Motor-
4103
STARTUP TIME
4104
LOCK ROTOR TIME
4105
STARTUP T WARM
4106
TEMP.COLD
MOTOR
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
4204
49 Θ ALARM
4205
I ALARM
4207A Kτ-FACTOR
4208A T EMERGENCY
4209
49 TEMP. RISE I
4210
49 TEMP. RISE I
4211
TEMPSENSOR RTD
4212
TEMPSENSOR RTD
4301
FCT 66
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL 48/66 Motor-
632
Function
C
Setting Options
46 Negative
0.50 .. 15.00 ; ∞
Seq
46 Negative
0.05 .. 3.20 sec; ∞
Seq
46 Negative
Instantaneous
Seq
Disk Emulation
46 Negative
0.00 .. 60.00 sec
Seq
48/66 Motor-
OFF
prot
ON
1A
0.50 .. 16.00 A
prot
5A
2.50 .. 80.00 A
48/66 Motor-
1.0 .. 180.0 sec
prot
48/66 Motor-
0.5 .. 180.0 sec; ∞
prot
48/66 Motor-
0.5 .. 180.0 sec; ∞
prot
48/66 Motor-
0 .. 80 %; ∞
prot
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
1.0 .. 10.0
49 Th.Overload
10 .. 15000 sec
49 Th.Overload
40 .. 200 °C
49 Th.Overload
104 .. 392 °F
49 Th.Overload
1 .. 6
49 Th.Overload
1 .. 12
48/66 Motor-
OFF
prot
ON
48/66 Motor-
1.10 .. 10.00
prot
48/66 Motor-
1 .. 320 sec
prot
48/66 Motor-
0.0 .. 320.0 min
prot
1A
0.20 .. 1.20 A
prot
5A
1.00 .. 6.00 A
Default Setting
Comments
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
OFF
48 Startup Time Supervi-
sion for Motors
5.00 A
Startup Current
25.00 A
10.0 sec
Startup Time
2.0 sec
Permissible Locked Rotor
Time
10.0 sec
Startup Time for warm
motor
25 %
Temperature limit for cold
motor
OFF
49 Thermal overload
protection
1.10
49 K-Factor
100.0 min
Time Constant
90 %
49 Thermal Alarm Stage
1.00 A
Current Overload Alarm
Setpoint
5.00 A
1.0
Kt-FACTOR when motor
stops
100 sec
Emergency time
100 °C
49 Temperature rise at
rated sec. curr.
212 °F
49 Temperature rise at
rated sec. curr.
1
Temperature sensor
connected to RTD
1
Temperature sensor
connected to RTD
OFF
66 Startup Counter for
Motors
4.90
I Start / I Motor nominal
10 sec
Maximum Permissible
Starting Time
1.0 min
Temperature Equalizaton
Time
1.00 A
Rated Motor Current
5.00 A
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016