Siemens SIPROTEC 4 User Manual page 384

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
Input/Output Board A–I/O-2 for 7SJ62.../EE
The layout of the printed circuit board for the input/output board A–I/O-2 is illustrated in the following Figure.
The set nominal currents of the current input transformers and the selected operating voltage of binary inputs
BI4 to BI11 are checked.
[ein-ausgabebgr-a-io-2-160502-wlk, 1, en_US]
Figure 3-13
The jumpers X60 to X63 must all be set to the same rated current, i.e. one jumper (X61 to X63) for each input
transformer and in addition the common jumper X60. The jumper X64 determines the rated current for the
input Ι
and may thus have a setting that deviates from that of the phase currents. In models with sensitive
N
ground fault current input there is no jumper X64.
Pickup Voltage of BI4 to BI11
Table 3-10
Binary inputs
BI4
384
Input/output module A–I/O-2 for devices (releases .../EE and higher) with representation of the
jumper settings required for the board configuration
Jumper settings for pickup voltages of binary inputs BI4 to BI11 on the input/output board A–
I/O-2 up to 7SJ62.../EE
Jumper
X21
DC 19 V threshold
1)
L
C53000-G1140-C207-8, Edition 08.2016
DC 88 V threshold
3)
H
SIPROTEC 4, 7SJ62/64, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents