Siemens SIPROTEC 4 User Manual page 77

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

The following must be observed:
The value pairs should be entered in increasing sequence. If desired, fewer than 20 pairs can be entered.
In most cases, about 10 pairs is sufficient to define the characteristic accurately. A value pair which is not
used has to be made invalid by entering "∞" for the threshold! The user must ensure that the value pairs
produce a clear and constant characteristic .
The current values entered should be those from the following table, along with the matching times.
Deviating values MofPU (multiples of PU-values) are rounded. This, however, will not be indicated.
Currents smaller than the current value of the smallest curve point will not lead to an extension of the
tripping time. The pickup curve (see
smallest current value point.
Currents larger than the largest current value entered will not lead to a reduction of the tripping time.
The pickup curve (see
greatest current value point.
Table 2-4
MofPU = 1 to 1.94
1.00
1.50
1.06
1.56
1.13
1.63
1.19
1.69
1.25
1.75
1.31
1.81
1.38
1.88
1.44
1.94
[anwenderkennl-260602-kn, 1, en_US]
Figure 2-18
The value pairs are entered at address 1231 MofPU Res T/Tp or 1331 MofPU Res T/TEp to recreate the
reset curve. The following must be observed:
The current values entered should be those from the following
Deviating values of MofPU are rounded. This, however, will not be indicated.
Currents larger than the largest current value entered will not lead to an extension of the dropout time.
The dropout curve (see
value point.
Currents which are smaller than the smallest current value entered will not lead to a reduction of the
dropout time. The dropout curve (see
with the smallest curve value point.
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Figure
Figure
2-18, right side) runs parallel to the current axis, beginning with the
Preferential values of standardized currents for user-defined tripping curves
MofPU = 2 to 4.75
2.00
3.50
2.25
3.75
2.50
4.00
2.75
4.25
3.00
4.50
3.25
4.75
Using a user-defined curve
Figure
2-18, left side) runs parallel to the current axis, up to the largest curve
2-18, right side) runs parallel to the current axis, up to the
MofPU = 5 to 7.75
5.00
5.25
5.50
5.75
6.00
6.25
Table
Figure
2-18, left side) runs parallel to the current axis, beginning
2.2 Overcurrent Protection 50, 51, 50N, 51N
MofPU = 8 to 20
6.50
8.00
6.75
9.00
7.00
10.00
7.25
11.00
7.50
12.00
7.75
13.00
14.00
2-5, along with the matching times.
Functions
15.00
16.00
17.00
18.00
19.00
20.00
77