Siemens SIPROTEC 4 User Manual page 641

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
6340
SYNC PERMIS.
6341
F SYNCHRON
6342
dV SYNC V2>V1
6343
dV SYNC V2<V1
6344
dα SYNC α2> α1
6345
dα SYNC α2< α1
6346
T SYNC-DELAY
6350
dV SYNCHK V2>V1 SYNC function
6351
dV SYNCHK V2<V1 SYNC function
6352
df SYNCHK f2>f1
6353
df SYNCHK f2<f1
6354
dα SYNCHK α2>α1 SYNC function
6355
dα SYNCHK α2<α1 SYNC function
6401
Synchronizing
6402
SyncCB
6403
Vmin
6404
Vmax
6405
V<
6406
V>
6407
SYNC V1<V2>
6408
SYNC V1>V2<
6409
SYNC V1<V2<
6410A Direct CO
6411A TSUP VOLTAGE
6412
T-SYN. DURATION
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Function
C
Setting Options
SYNC function
YES
3
NO
SYNC function
0.01 .. 0.04 Hz
3
SYNC function
0.5 .. 50.0 V
3
SYNC function
0.5 .. 50.0 V
3
SYNC function
2 .. 80 °
3
SYNC function
2 .. 80 °
3
SYNC function
0.00 .. 60.00 sec
3
0.5 .. 50.0 V
3
0.5 .. 50.0 V
3
SYNC function
0.01 .. 2.00 Hz
3
SYNC function
0.01 .. 2.00 Hz
3
2 .. 80 °
3
2 .. 80 °
3
SYNC function
ON
4
OFF
SYNC function
(Einstellmöglich-
4
keiten anwendung-
sabhängig)
SYNC function
20 .. 125 V
4
SYNC function
20 .. 140 V
4
SYNC function
1 .. 60 V
4
SYNC function
20 .. 140 V
4
SYNC function
YES
4
NO
SYNC function
YES
4
NO
SYNC function
YES
4
NO
SYNC function
YES
4
NO
SYNC function
0.00 .. 60.00 sec
4
SYNC function
0.01 .. 1200.00 sec;
4
Functions, Settings, Information
Default Setting
Comments
YES
Switching at synchronous
conditions
0.01 Hz
Frequency threshold
ASYN <--> SYN
5.0 V
Maximum voltage differ-
ence V2>V1
5.0 V
Maximum voltage differ-
ence V2<V1
10 °
Maximum angle differ-
ence alpha2>alpha1
10 °
Maximum angle differ-
ence alpha2<alpha1
0.00 sec
Release delay at synchro-
nous conditions
5.0 V
Maximum voltage differ-
ence V2>V1
5.0 V
Maximum voltage differ-
ence V2<V1
0.10 Hz
Maximum frequency
difference f2>f1
0.10 Hz
Maximum frequency
difference f2<f1
10 °
Maximum angle differ-
ence alpha2>alpha1
10 °
Maximum angle differ-
ence alpha2<alpha1
OFF
Synchronizing Function
none
Synchronizable circuit
breaker
90 V
Minimum voltage limit:
Vmin
110 V
Maximum voltage limit:
Vmax
5 V
Threshold V1, V2 without
voltage
80 V
Threshold V1, V2 with
voltage
NO
ON-Command at V1< and
V2>
NO
ON-Command at V1> and
V2<
NO
ON-Command at V1< and
V2<
NO
Direct ON-Command
0.10 sec
Supervision time of
V1>;V2> or V1<;V2<
30.00 sec
Maximum duration of
Synchronization
F.2 Settings
641

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents