Siemens SIPROTEC 4 User Manual page 108

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.3 Directional Overcurrent Protection 67, 67N
Addr.
Parameter
1611
67N-TOC IEC
1612
67N-TOC ANSI
1613A
MANUAL CLOSE
1614A
67N-2 active
1617
67N POLARIZAT.
1618A
67N T DROP-OUT
1619A
ROTATION ANGLE
1620A
67N-2 MEASUREM.
1621A
67N-1 MEASUREM.
1622A
67N-TOC MEASUR.
1623
67N-2 Direction
1624
67N-1 Direction
1625
67N-TOC Direct.
1626
67N-3 Direction
1627A
67N-3 MEASUREM.
1628
67N-3 PICKUP
1629
67N-3 DELAY
1630
M.of PU TD
108
C
Setting Options
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
67N-3 instant.
67N-2 instant.
67N-1 instant.
67N-TOC instant
Inactive
always
with 79 active
with VN and IN
with V2 and I2
0.00 .. 60.00 sec
-180 .. 180 °
Fundamental
True RMS
Fundamental
True RMS
Fundamental
True RMS
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Fundamental
True RMS
0.50 .. 35.00 A; ∞
0.00 .. 60.00 sec; ∞
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Default Setting
Comments
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
67N-2 instant.
Manual Close Mode
always
67N-2 active
with VN and IN
Ground Polarization
0.00 sec
67N Drop-Out Time Delay
-45 °
Rotation Angle of Refer-
ence Voltage
Fundamental
67N-2 measurement of
Fundamental
67N-1 measurement of
Fundamental
67N-TOC measurement of
Forward
67N-2 Direction
Forward
67N-1 Direction
Forward
67N-TOC Direction
Forward
67N-3 Direction
Fundamental
67N-3 measurement of
∞ A
67N-3 Pickup
0.00 sec
67N-3 Time Delay
Multiples of PU Time-Dial
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents