SIPROTEC
Multifunction protection with
control
7SJ61 / 7SJ62 / 7SJ64
Communication module
Redundant IEC 60870-5-103
Bus mapping
Edition: Januar 2010
C53000-L2540-A306-2
Preface
Table of Contents
Notes to SIPROTEC objects
IEC 60870-5-103 Interoperability
Point List
Glossary
Index
1
2
3

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7SJ61

  • Page 1 Preface Table of Contents Notes to SIPROTEC objects SIPROTEC IEC 60870-5-103 Interoperability Multifunction protection with Point List control 7SJ61 / 7SJ62 / 7SJ64 Glossary Index Communication module Redundant IEC 60870-5-103 Bus mapping Edition: Januar 2010 C53000-L2540-A306-2...
  • Page 2 We reserve the right to make technical improvements with- SIPROTEC, SINAUT, SICAM, and DIGSI are registered trade- out notice. marks of SIEMENS AG. Other names and terms can be trade- Document version: V01.10.00 marks the use of which may violate the rights of thirds.
  • Page 3: Preface

    Contents Order number Multi-Fuctional Function, operation, assembly and commissioning of C53000-G1140-C210 Protective Relay with the SIPROTEC device 7SJ61 BayController SIPROTEC 7SJ61 Multi-Fuctional Function, operation, assembly and commissioning of C53000-G1140-C207 Protective Relay with the SIPROTEC device 7SJ62 Local Control SIPROTEC 7SJ62/64...
  • Page 4 Note: The redundant IEC 60870-5-103 module is not for all SIPROTEC devices available. Check the manual of the device or contact your Siemens representative. For device parameterization DIGSI 4 version 4.8 or higher and IEC 60870-5-103 standard mappings 3-1 to 3-n (n = device type dependent number of standard map- pings) have to be used.
  • Page 5 Warning! Hazardous voltages are present in this electrical equipment during operation. Non– observance of the safety rules can result in severe personal injury or property dam- age. Only qualified personnel shall work on and around this equipment after becoming thor- oughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations.
  • Page 6 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 7: Table Of Contents

    Table of Contents Preface..............................3 Table of Contents ..........................7 Notes to SIPROTEC objects ......................11 Annunciations ........................12 1.1.1 Error with a summary alarm ....................12 1.1.2 Alarm Summary Event......................12 1.1.3 Stop Data Transmission ....................... 13 Commands ........................... 13 1.2.1 Single Commands ........................
  • Page 8 Application layer ........................19 2.3.1 Transmission mode for application data ................19 2.3.2 Common Address of ASDU ....................19 2.3.3 Selection of standard information numbers in monitor direction........... 19 2.3.3.1 System functions in monitor direction ................... 19 2.3.3.2 Status indications in monitor direction .................. 19 2.3.3.3 Supervision indications in monitor direction................
  • Page 9 Measurements........................42 3.3.1 ASDU3 (Measurements I) ....................42 3.3.2 ASDU9 (Measurements II) ....................42 3.3.3 User defined ASDU9 (Measurements II) ................43 3.3.4 Time Tagged Measurements....................43 3.3.5 Metering values ........................44 Settings ..........................45 Index ..............................69 Glossary ............................. 71 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 10 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 11: Notes To Siprotec Objects

    Notes to SIPROTEC objects This chapter contains notes for the use and evaluation of certain SIPROTEC objects which are available via IEC 60870-5-103 communication. Annunciations Commands Measured values Metered measurands 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 12: Annunciations

    Notes to SIPROTEC objects Note The description of the standard mappings contains the pre-allocation of the mapping files at delivery or first assignment of a mapping in DIGSI 4 to the SIPROTEC device. Changes of the allocation and the scaling of the measured values are possible in ad- aptation to the concrete installation enviroment (ref.
  • Page 13: Stop Data Transmission

    Notes to SIPROTEC objects 1.1.3 Stop Data Transmission The functionality "Stop data transmission" is not supported via IEC 60870-5-103 com- munication. If "Stop data transmission" is active nevertheless data via IEC 60870-5- 103 will be transmitted furthermore. The annunciation "DataStop" (Obj.- Adr. 16) signals the activation of "Stop data trans- mission"...
  • Page 14: Measured Values

    Notes to SIPROTEC objects Measured values Note Depending on the device composition not all of the indicated analog inputs (and cor- responding IEC 60870-5-103 mapping entrys) may be available in the SIPROTEC de- vice. For the transmission of measured values, the compatible range and the private range can be used.
  • Page 15: Metered Measurands

    Notes to SIPROTEC objects Metered measurands Metering values (e.g. kWh) are not defined in the IEC 60870-5-103 standard and there Scaling are no compatible data units available which are suitable for the transmission of me- tered values. Some SIPROTEC 4 relays offer the possibility to transmit metered val- ues via the IEC 60870-5-103 interface.
  • Page 16 Notes to SIPROTEC objects 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 17: Iec 60870-5-103 Interoperability

    IEC 60870-5-103 Interoperability Physical layer Link layer Application layer 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 18: Physical Layer

    IEC 60870-5-103 Interoperability Redundant IEC 60870-5-103 DEVICE PROFILE DOCUMENT Vendor Name: SIEMENS AG Device Name: 7SJ61 / 7SJ62 / 7SJ64 Physical layer 2.1.1 Electrical interface EIA RS-485 Number of loads _____________ for one protection equipment 2.1.2 Optical interface Glass fibre...
  • Page 19: Application Layer

    IEC 60870-5-103 Interoperability Application layer 2.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 2.3.2 Common Address of ASDU One Common Address of ASDU (identical with station address) More than one Common Address of ASDU 2.3.3 Selection of standard information numbers in monitor direction...
  • Page 20: Supervision Indications In Monitor Direction

    IEC 60870-5-103 Interoperability 2.3.3.3 Supervision indications in monitor direction Semantics <32> Measurand supervision I <33> Measurand supervision V <35> Phase sequence supervision <36> Trip circuit supervision <37> I>> back-up operation <38> VT fuse failure <39> Teleprotection disturbed <46> Group warning <47>...
  • Page 21: Fault Indications In Monitor Direction

    IEC 60870-5-103 Interoperability 2.3.3.5 Fault indications in monitor direction Semantics <64> Start /pick-up L <65> Start /pick-up L <66> Start /pick-up L <67> Start /pick-up N <68> General trip <69> Trip L <70> Trip L <71> Trip L <72> Trip I>> (back-up operation) <73>...
  • Page 22: Generic Functions In Monitor Direction

    IEC 60870-5-103 Interoperability 2.3.3.8 Generic functions in monitor direction Semantics <240> Read headings of all defined groups <241> Read values or attributes of all entries of one group <243> Read directory of a single entry <244> Read value or attribute of a single entry <245>...
  • Page 23: Selection Of Standard Information Numbers In Control Direction

    IEC 60870-5-103 Interoperability 2.3.4 Selection of standard information numbers in control direction 2.3.4.1 System functions in control direction Semantics <0> Initiation of general interrogation <0> Time synchronization 2.3.4.2 General commands in control direction Semantics <16> Auto-recloser on/off <17> Teleprotection on/off <18>...
  • Page 24: Miscellaneous

    IEC 60870-5-103 Interoperability 2.3.6 Miscellaneous Measurand Max. MVAL = rated value times Current L Current L Current L Voltage L Voltage L Voltage L Active power P Reactive power Q Frequency f Voltage L 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 25: Point List

    Point List General Command (control direction) Indications in monitor direction Measurements 3.3.5 Metering values Settings 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 26: General Command (Control Direction)

    Point List General Command (control direction) 3.1.1 Double Point Command ASDU Function Informa- Name Description Obj. - type tion Adr. number 52Breaker Trip / Close Breaker switch Disconnect Trip / Close Disconnect switch Gnd switch Trip / Close Ground switch Switch 1 Trip / Close switch 1 Switch 2...
  • Page 27: Indications In Monitor Direction

    Point List Indications in monitor direction 3.2.1 utomatic reclosure status ASDU Function Informa- Name Description Obj. - type tion Adr. number >79 ON >79 ON; Automatic reclosure ON; ON = 1, OFF = 0 2701 >79 OFF >79 OFF; ON = 1, OFF = 0 2702 >...
  • Page 28: Time Overcurrent Protection

    Point List 3.2.2 Time Overcurrent protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >BLOCK 50-2 >BLOCK 50-2; ON = 1, OFF = 0 1721 >BLOCK 50-1 >BLOCK 50-1; ON = 1, OFF = 0 1722 >BLOCK 51 >BLOCK 51;...
  • Page 29: Inrush Function

    Point List ASDU Function Informa- Name Description Obj. - type tion Adr. number 50N/51NPickedup 50N/51N picked up; ON = 1, OFF = 0 1765 50 (N)/51(N)TRIP 50(N)/51(N) TRIP; ON = 1 1791 50 (N) / 51 (N) PU 50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0 1761 50-1 TRIP 50-1 TRIP;...
  • Page 30: Directional Time Overcurrent Protection

    Point List 3.2.4 Directional time overcurrent protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >BLOCK 67-1 >BLOCK 67-1; ON = 1, OFF = 0 2621 >BLOCK 67-TOC >BLOCK 67-TOC; ON = 1, OFF = 0 2622 >BLOCK 67N-1 >BLOCK 67N-1;...
  • Page 31: Unbalanced Load Protection

    Point List ASDU Function Informa- Name Description Obj. - type tion Adr. number >BLOCK 67-2 >BLOCK 67-2; ON = 1, OFF = 0 2615 >BLOCK 67N-2 >BLOCK 67N-2; ON = 1, OFF = 0 2616 Phase A forward Phase A forward; ON = 1, OFF = 0 2628 Phase B forward Phase B forward;...
  • Page 32: Frequency Protection

    Point List 3.2.6 Frequency protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >BLOCK 81O/U >BLOCK 81O/U; ON = 1, OFF = 0 5203 >BLOCK 81-1 >BLOCK 81-1; ON = 1, OFF = 0 5206 >BLOCK 81-2 >BLOCK 81-2;...
  • Page 33: Voltage Protection

    Point List 3.2.7 Voltage protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >BLOCK 27 >BLOCK 27 undervoltage protection; ON = 1, OFF = 0 6503 >27 I SUPRVSN >27-Switch current supervision ON; ON = 1, OFF = 0 6505 >BLOCK 27-1 >BLOCK 27-1 undervoltage protection;...
  • Page 34: Internal Mode Status

    Point List 3.2.8 Internal Mode Status ASDU Function Informa- Name Description Obj. - type tion Adr. number >Door open >Door open; ON = 1, OFF = 0 >CB wait >Circuit breaker wait; ON = 1, OFF = 0 Control auth Control authority;...
  • Page 35 Point List ASDU Function Informa- Name Description Obj. - type tion Adr. number Initial Start Initial Start of the Relay; ON = 1 protection act. Protection activation 2782 DataStop Data stop; ON = 1, OFF = 0; (ref to chap. ) Test mode Test mode;...
  • Page 36: Highly Sensitive Earth Fault Protection

    Point List 3.2.9 Highly sensitive earth fault protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >Start Flt. Loc >Start Fault Locator; ON = 1, OFF = 0 1106 >BLOCK 64 >BLOCK 64; ON = 1, OFF = 0 1201 >BLOCK 50Ns-2 >BLOCK 50Ns-2;...
  • Page 37: Trip Coil Monitor

    Point List 3.2.10 Trip coil monitor ASDU Function Informa- Name Description Obj. - type tion Adr. number 74TC BLOCKED 74TC Trip circuit supervision is BLOCKED; ON = 1, OFF = 0 6862 74TC ACTIVE 74TC Trip circuit supervision is ACTIVE; ON = 1, OFF = 0 6863 >74TC trip rel.
  • Page 38: Thermal Overload Protection

    Point List 3.2.12 Thermal overload protection ASDU Function Informa- Name Description Obj. - type tion Adr. number >49 O/L BLOCK >BLOCK 49 Overload Protection; ON = 1, OFF = 0 1503 >EmergencyStart >Emergency start of motors; ON = 1, OFF = 0 1507 49 O / L OFF 49 Overload Protection is OFF;...
  • Page 39: Control Switches Return Position Indication(Double Point Commands)

    Point List 3.2.15 Control switches return position indication(double point commands) ASDU Function Informa- Name Description Obj. - type tion Adr. number 52 Breaker input state of switch breaker; 1=open, 2=close Disconnect switch input state of disconnect switch; 1=open, 2=close Gnd switch input state of ground switch;1=open, 2=close Switch 1 input state of switch 1;...
  • Page 40 Point List ASDU Function Informa- Name Description Obj. - type tion Adr. number >input channel 15 User input 15 >input channel 16 User input 16 >input channel 17 User input 17 >input channel 18 User input 18 >input channel 19 User input 19 >input channel 20 User input 20...
  • Page 41 Point List ASDU Function Informa- Name Description Obj. - type tion Adr. number >input channel 50 User input 50 >input channel 51 User input 51 >input channel 52 User input 52 >input channel 53 User input 53 >input channel 54 User input 54 >input channel 55 User input 55...
  • Page 42: Measurements

    Point List Measurements 3.3.1 ASDU3 (Measurements I) Function Informa- Position Name Description Obj. - type tion Adr. number Current phase b Va-b= Voltage phase a to phase b 3.3.2 ASDU9 (Measurements II) Function Informa- Position Name Description Obj. - type tion Adr.
  • Page 43: User Defined Asdu9 (Measurements Ii)

    Point List 3.3.3 User defined ASDU9 (Measurements II) Function Informa- Position Name Description Obj. - type tion Adr. number Res1 User define 1 Res2 User define 2 Res3 User define 3 Res4 User define 4 Res5 User define 5 Res6 User define 6 Res7 User define 7...
  • Page 44: Metering Values

    Point List Metering values 3.3.5 ASDU Function Informa- Name Description Obj. - type tion Adr. number Wp+= Wp Forward (metered measurand derived from measured value) Wq+= Wq Forward (metered measurand derived from measured value) Wp-= Wp Reverse (metered measurand derived from measured value) Wq-= Wq Reverse (metered measurand derived from measured...
  • Page 45: Settings

    Point List Settings Note The settings which can be read and written are given in the following table. The setting options are indicated in column "Generic identification data". If no values are indicated the setting is a number. For the vaild setting range please refer to the user manual of the device.
  • Page 46 Point List Obj.- Name Generic identification Note Adr. data Group Entry 1224 51V Voltage Influence 1301 50N, 51N Ground Time Overcurrent 22 ON 23 OFF 1317 50N-3 Pickup 1318 50N-3 Time Delay 1302 50N-2 Pickup 1303 50N-2 Time Delay 1304 50N-1 Pickup 1305 50N-1 Time Delay...
  • Page 47 Point List Obj.- Name Generic identification Note Adr. data Group Entry 1512 ANSI Curve 12808 Inverse 12809 Short Inverse 12810 Long Inverse 12811 Moderately Inv. 12812 Very Inverse 12813 Extremely Inv. 12814 Definite Inv. 1516 Phase Direction 12514 Forward 12515 Reverse 1523 67-2 Direction 12514 Forward...
  • Page 48 Point List Obj.- Name Generic identification Note Adr. data Group Entry 1624 67N-1 Direction 12514 Forward 12515 Reverse 1625 67N-TOC Direction 12514 Forward 12515 Reverse 2701 50 1Ph 22 ON 23 OFF 2702 50 1Ph-2 Pickup 2703 50 1Ph-2 Pickup 2704 50 1Ph-2 Time Delay 2705...
  • Page 49 Point List Obj.- Name Generic identification Note Adr. data Group Entry 4004 46-2 Pickup 4005 46-2 Time Delay 4006 46 IEC Curve 12559 Normal Inverse 12560 Very Inverse 12561 Extremely Inv. 12837 Long Inverse 4007 46 ANSI Curve 12808 Inverse 12809 Short Inverse 12810 Long Inverse 12811 Moderately Inv.
  • Page 50 Point List Obj.- Name Generic identification Note Adr. data Group Entry 1908 50Nc-3 Pickup 1909 50Nc-3 Time Delay 1901 50Nc-2 Pickup 1902 50Nc-2 Time Delay 1903 50Nc-1 Pickup 1904 50Nc-1 Time Delay 1905 51Nc Pickup 1906 51Nc Time Dial 1907 51Nc Time Dial 2001 67c-2 Pickup...
  • Page 51 Point List Obj.- Name Generic identification Note Adr. data Group Entry 5406 81-2 Pickup 5407 81-2 Pickup 5408 81-2 Time Delay 5409 81-3 Pickup 5410 81-3 Pickup 5411 81-3 Time delay 5412 81-4 Pickup 5413 81-4 Pickup 5414 81-4 Time delay 5421 81-1 Over/Under Frequency Protection 23 OFF...
  • Page 52 Point List Obj.- Name Generic identification Note Adr. data Group Entry 4309 Extension of Time Constant at Running 4310 Minimum Restart Inhibit Time 4311 Rotor Overload Protection 22 ON 23 OFF 12700 Alarm Only 8101 Measurement Supervision 22 ON 23 OFF 8102 Voltage Threshold for Balance Monitoring 8103...
  • Page 53 Point List Obj.- Name Generic identification Note Adr. data Group Entry 3104 with standard groud CT Current I2 for CT Angle Error 3105 CT Angle Error at I2 3106 L-Gnd Voltage of Faulted Phase Vph Min 3107 L-Gnd Voltage of Unfaulted Phase Vph Max 3108 64-1 Ground Displacement Voltage 3109...
  • Page 54 Point List Obj.- Name Generic identification Note Adr. data Group Entry 3120 Parameter 131 (sensitive) 51Ns Time Dial Ground fault is Time Overcurrent Curve IEC or User Defined Pickup Curve 3127 51Ns Current at const. Time Delay T min 3120 51Ns Time Dial Parameter 131 (sensitive) Ground fault is...
  • Page 55 Point List Obj.- Name Generic identification Note Adr. data Group Entry 3141 Parameter 131 (sensitive) 51Ns Maximum Time Delay (at 51Ns PU) Ground fault is Logarithmic inverse B Parameter 130 (sensitive) Ground fault dir. characteristic is cos phi / sin phi measurement (standard) Parameter 131 (sensitive) 3142...
  • Page 56 Point List Obj.- Name Generic identification Note Adr. data Group Entry 3150 7SJ64: 50Ns-2 minimum voltage with sensitive ground CT and VT and V will be measured Parameter 131 (sensitive) Ground fault is not Disabled 3150 7SJ62: 50Ns-2 minimum voltage with sensitive ground CT and VT and V will be measured...
  • Page 57 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7101 79 Auto-Reclose Function 23 OFF 22 ON 7103 AR blocking duration after manual close 7105 79 Auto Reclosing reset time 7108 Safety Time until 79 is ready 7113 Check circuit breaker before AR? 7114 AR start-signal monitoring time...
  • Page 58 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7167 50N-3 12891 No influence 12885 Starts 79 25011 Stops 79 7154 12892 No influence 12885 Starts 79 25011 Stops 79 7155 12893 No influence 12885 Starts 79 25011 Stops 79 7156 67-1 12894 No influence...
  • Page 59 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7201 before 1. Cycle: 50N-1 25346 Set value T=T 25344 instant. T=0 25343 blocked T= 7202 before 1. Cycle: 50-2 25347 Set value T=T 25344 instant. T=0 25343 blocked T= 7203 before 1.
  • Page 60 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7177 before 1. Cycle: 67Ns TOC 25358 Set value T=T 25344 instant. T=0 25343 blocked T= 7212 before 2. Cycle: 50-1 25359 Set value T=T 25344 instant. T=0 25343 blocked T= 7213 before 2.
  • Page 61 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7178 before 2. Cycle: 67Ns-1 25372 Set value T=T 25344 instant. T=0 25343 blocked T= 7179 before 2. Cycle: 67Ns-2 25372 Set value T=T 25344 instant. T=0 25343 blocked T= 7180 before 2.
  • Page 62 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7234 before 3. Cycle: 67 TOC 25385 Set value T=T 25344 instant. T=0 25343 blocked T= 7235 before 3. Cycle: 67N TOC 25386 Set value T=T 25344 instant. T=0 25343 blocked T= before 3.
  • Page 63 Point List Obj.- Name Generic identification Note Adr. data Group Entry 7244 before 4. Cycle: 67-2 25397 Set value T=T 25344 instant. T=0 25343 blocked T= 7245 before 4. Cycle: 67N-2 25398 Set value T=T 25344 instant. T=0 25343 blocked T= 7246 before 4.
  • Page 64 Point List Obj.- Name Generic identification Note Adr. data Group Entry 6108 ON-Command at V1> and V2< 24 NO 25 YES 6109 ON-Command at V1< and V2< 24 NO 25 YES 6112 Maximum duration of Synchronization 6120 Closing (operating) time of CB 6121 Balancing factor V1/V2 6123...
  • Page 65 Point List Obj.- Name Generic identification Note Adr. data Group Entry 6207 ON-Command at V1< and V2> 24 NO 25 YES 6208 ON-Command at V1> and V2< 24 NO 25 YES 6209 ON-Command at V1< and V2< 24 NO 25 YES 6212 Maximum duration of Synchronization 6220...
  • Page 66 Point List Obj.- Name Generic identification Note Adr. data Group Entry 6306 Threshold V1, V2 with voltage 6307 ON-Command at V1< and V2> 24 NO 25 YES 6308 ON-Command at V1> and V2< 24 NO 25 YES 6309 ON-Command at V1< and V2< 24 NO 25 YES 6312...
  • Page 67 Point List Obj.- Name Generic identification Note Adr. data Group Entry 6405 Threshold V1, V2 without voltage 6406 Threshold V1, V2 with voltage 6407 ON-Command at V1< and V2> 24 NO 25 YES 6408 ON-Command at V1> and V2< 24 NO 25 YES 6409 ON-Command at V1<...
  • Page 68 Point List Obj.- Name Generic identification Note Adr. data Group Entry 4406 Load Jam Blocking after motor start 4402 Load Jam Tripping Threshold 4403 Load Jam Trip Delay 4404 Load Jam Alarm Threshold 4405 Load Jam Alarm Delay 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 69: Index

    Index ..........4 Additional support ........12 Alarm summary event ........ 3 Applicability of manual ........... 4 Caution (definition) ........... 13 Command output ........... 13 continuous output ............2 Copyright ........... 4 Danger (definition) ............18 Idle Level ......4 IEC 60870-5-103 messages ......
  • Page 70 ....15 Scaling of the metered measurands ..........13 Setting group ........13 Stop data transmission ..........12 Summary alarm .........5 Symbol conventions ......3 Target audience of manual .........5 Typographic conventions ..............4 Validity ..........4 Warning (definition) 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...
  • Page 71: Glossary

    Glossary Automatic Recloser Continuous Function Chart Double Command Parameterization system for SIPROTEC devices DIGSI 4 Double-point Indication International Electrotechnical Commission Generic identification data Generic identification number Data from the IEC 60870-5-103 slave to the IEC 60870-5-103 master. Input data/ input direction Allocation of the SIPROTEC data objects to the IEC 60870-5-103 protocol.
  • Page 72 7SJ61 / 7SJ62 / 7SJ64 Bus mapping C53000-L2540-A306-2...