Siemens SIPROTEC 4 User Manual page 633

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
4306
MAX.WARM
STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
4311
ROTOR OVERLOAD 48/66 Motor-
4401
Load Jam Prot.
4402
Load Jam I>
4403
TRIP DELAY
4404
I Alarm
4405
ALARM DELAY
4406
T Start Blk.
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1-V2 PICKUP
5016
59-2-V2 PICKUP
5017A 59-1 DOUT RATIO
5018A 59-2 DOUT RATIO
5019
59-1 PICKUP V1
5020
59-2 PICKUP V1
5101
FCT 27
5102
27-1 PICKUP
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Function
C
Setting Options
48/66 Motor-
1 .. 4
prot
48/66 Motor-
1 .. 2
prot
48/66 Motor-
0.2 .. 100.0
prot
48/66 Motor-
0.2 .. 100.0
prot
48/66 Motor-
0.2 .. 120.0 min
prot
ON
prot
OFF
Alarm Only
48/66 Motor-
OFF
prot
ON
Alarm Only
48/66 Motor-
1A
0.50 .. 12.00 A
prot
5A
2.50 .. 60.00 A
48/66 Motor-
0.00 .. 600.00 sec
prot
48/66 Motor-
1A
0.50 .. 12.00 A
prot
5A
2.50 .. 60.00 A
48/66 Motor-
0.00 .. 600.00 sec
prot
48/66 Motor-
0.00 .. 600.00 sec
prot
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
40 .. 260 V
27/59 O/U Volt.
40 .. 150 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
40 .. 260 V
27/59 O/U Volt.
40 .. 150 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
2 .. 150 V
27/59 O/U Volt.
2 .. 150 V
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
40 .. 150 V
27/59 O/U Volt.
40 .. 150 V
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
10 .. 210 V
Functions, Settings, Information
Default Setting
Comments
2
Maximum Number of
Warm Starts
1
Number of Cold Starts -
Warm Starts
5.0
Extension of Time
Constant at Stop
2.0
Extension of Time
Constant at Running
6.0 min
Minimum Restart Inhibit
Time
ON
Rotor Overload Protection
OFF
Load Jam Protection
2.00 A
Load Jam Tripping
Threshold
10.00 A
1.00 sec
Load Jam Trip Delay
1.80 A
Load Jam Alarm
Threshold
9.00 A
1.00 sec
Load Jam Alarm Delay
10.00 sec
Load Jam Blocking after
motor start
OFF
59 Overvoltage Protec-
tion
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
30 V
59-1 Pickup Overvoltage
(neg. seq.)
50 V
59-2 Pickup Overvoltage
(neg. seq.)
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
110 V
59-1 Pickup V1
120 V
59-2 Pickup V1
OFF
27 Undervoltage Protec-
tion
75 V
27-1 Pickup
F.2 Settings
633