Overvoltage Protection 59 - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.6 Voltage Protection 27, 59
Function
Connection, three-phase
Parameter 213
Function
Connection, single-phase
Parameter 240
Overvoltage
Any phase-to-phase or phase-
to-ground voltage (see also
Undervoltage
Section
Single-phase Voltage Trans-
former
Connection)
Current Criterion
Depending on the system, the primary voltage transformers are arranged either on the supply side or the load
side of the associated circuit breaker. These different arrangements lead to different behaviour of the voltage
protection function when a fault occurs. When a tripping command is issued and a circuit breaker is opened,
full voltage remains on the supply side while the load side voltage becomes zero. When voltage supply is
suppressed, undervoltage protection, for instance, will remain picked up. If pickup is to drop out, the current
can be used as an additional criterion for pickup of undervoltage protection (current supervision CS). Under-
voltage pickup can only be maintained when the undervoltage criterion satisfied and a settable minimum
current level (BkrClosed I MIN) are exceeded. Here, the largest of the three phase currents is used. When
the current decreases below the minimum current setting after the circuit breaker has opened, undervoltage
protection drops out.
NOTE
i
i
If parameter CURRENT SUPERV. is set to disabled in address 5120, the device picks up immediately
without measurement voltage and the undervoltage protection function in pickup. Apply measuring
voltage or block the voltage protection to continue with configuration. Moreover you have the option of
setting a flag via device operation for blocking the voltage protection. This initiates the reset of the pickup
and device configuration can be resumed.

Overvoltage Protection 59

2.6.2
Function
The overvoltage protection has two elements. In case of a high overvoltage, tripping switch off is performed
with a short-time delay, whereas in case of less severe overvoltages, the tripping is performed with a longer
time delay. When one of the adjustable settings is exceeded, the 59 element picks up and trips after an adjust-
able time delay has elapsed. The time delay is not dependent on the magnitude of the overvoltage.
The dropout ratio for the two overvoltage elements (= V
The following figure shows the logic diagram of the overvoltage protection function.
128
None
(direct evaluation of the voltage
2.26 Protection for
connected in accordance with
address240
Selectable voltage
(Parameter 614 / 615
Selectable voltage
/V
dropout value
pickup value
C53000-G1140-C207-8, Edition 08.2016
Threshold to be set as
Threshold to be set as
Phase-to-phase or
Phase-to-ground-voltage
((in accordance with
address240)
) can be set.
SIPROTEC 4, 7SJ62/64, Manual