Siemens SIPROTEC 4 User Manual page 379

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Processor Board A–CPU for 7SJ62.../EE
[prozbgr-a-cpu-geraetebises-ee-160502-wlk, 1, en_US]
Figure 3-10
The preset nominal voltage of the integrated power supply is checked according to
voltages of the binary inputs BI1 to BI3 are checked according to
binary outputs (BO1 and BO2) is checked according to
Power Supply
Table 3-4
Jumper
X51
X52
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Processor printed circuit board A–CPU for devices releases ../EE and higher with jumpers
settings required for the module configuration (up to firmware V4.6)
Jumper settings for the nominal voltage of the integrated power supply on the processor
board A–CPU to 7SJ62.../EE
Nominal Voltage
DC 24 V/ 48 V
DC 60 V to 125 V
Not used
1-2
Not used
1-2 and 3-4
Table
3-5, and the contact mode of the
Table
3-6.
DC 110 V to 250 V,
AC 115 V to 230 V
2-3
2-3
Mounting and Commissioning
3.1 Mounting and Connections
Table
3-4, the pickup
379

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents