Functions, Settings, Information
F.2 Settings
Addr. Parameter
9031A RTD 3 TYPE
9032A RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
9035
RTD 3 STAGE 2
9036
RTD 3 STAGE 2
9041A RTD 4 TYPE
9042A RTD 4 LOCATION
9043
RTD 4 STAGE 1
9044
RTD 4 STAGE 1
9045
RTD 4 STAGE 2
9046
RTD 4 STAGE 2
9051A RTD 5 TYPE
9052A RTD 5 LOCATION
9053
RTD 5 STAGE 1
9054
RTD 5 STAGE 1
9055
RTD 5 STAGE 2
652
Function
C
Setting Options
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
Default Setting
Comments
Not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage
1 Pickup
212 °F
RTD 3: Temperature Stage
1 Pickup
120 °C
RTD 3: Temperature Stage
2 Pickup
248 °F
RTD 3: Temperature Stage
2 Pickup
Not connected
RTD 4: Type
Other
RTD 4: Location
100 °C
RTD 4: Temperature Stage
1 Pickup
212 °F
RTD 4: Temperature Stage
1 Pickup
120 °C
RTD 4: Temperature Stage
2 Pickup
248 °F
RTD 4: Temperature Stage
2 Pickup
Not connected
RTD 5: Type
Other
RTD 5: Location
100 °C
RTD 5: Temperature Stage
1 Pickup
212 °F
RTD 5: Temperature Stage
1 Pickup
120 °C
RTD 5: Temperature Stage
2 Pickup
SIPROTEC 4, 7SJ62/64, Manual