Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
7001
FCT 50BF
7004
Chk BRK CONTACT
7005
TRIP-Timer
7006
50BF PICKUP
7007
50BF PICKUP IE>
7008
50BF-2 Delay
7101
FCT 79
7103
BLOCK MC Dur.
7105
TIME RESTRAINT
7108
SAFETY 79 ready
7113
CHECK CB?
7114
T-Start MONITOR
7115
CB TIME OUT
7116
Max. DEAD EXT.
7117
T-ACTION
7118
T DEAD DELAY
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Function
C
Setting Options
50BF BkrFailure
OFF
ON
50BF BkrFailure
OFF
ON
50BF BkrFailure
0.06 .. 60.00 sec; ∞ 0.25 sec
50BF BkrFailure 1A
0.03 .. 20.00 A
5A
0.15 .. 100.00 A
50BF BkrFailure
0.03 .. 20.00 A
50BF BkrFailure
0.06 .. 60.00 sec; ∞ 0.50 sec
79M Auto Recl.
OFF
ON
79M Auto Recl.
0.50 .. 320.00 sec;
0
79M Auto Recl.
0.50 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
No check
Chk each cycle
79M Auto Recl.
0.01 .. 320.00 sec;
79M Auto Recl.
0.10 .. 320.00 sec
79M Auto Recl.
0.50 .. 1800.00 sec;
79M Auto Recl.
0.01 .. 320.00 sec;
79M Auto Recl.
0.0 .. 1800.0 sec; ∞ 1.0 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0 .. 9
79M Auto Recl.
0 .. 9
79M Auto Recl.
(Einstellmöglich-
keiten anwendung-
sabhängig)
Functions, Settings, Information
Default Setting
Comments
OFF
50BF Breaker Failure
Protection
OFF
Check Breaker contacts
TRIP-Timer
0.10 A
50BF Pickup current
threshold
0.50 A
0.10 A
50BF Pickup earth current
threshold
Delay of 2nd stage for
busbar trip
OFF
79 Auto-Reclose Function
1.00 sec
AR blocking duration after
manual close
3.00 sec
79 Auto Reclosing reset
time
0.50 sec
Safety Time until 79 is
ready
No check
Check circuit breaker
before AR?
0.50 sec
AR start-signal monitoring
time
3.00 sec
Circuit Breaker (CB)
Supervision Time
100.00 sec
Maximum dead time
extension
∞ sec
Action time
Maximum Time Delay of
Dead-Time Start
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground
Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground
Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground
Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground
Fault
1
Number of Reclosing
Cycles Ground
1
Number of Reclosing
Cycles Phase
none
Close command via
control device
F.2 Settings
643