Functions, Settings, Information
F.2 Settings
Addr. Parameter
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
5113A 27-1 DOUT RATIO
5114A 27-2 DOUT RATIO
5120A CURRENT SUPERV.
5201
VT BROKEN WIRE
5202
Σ V>
5203
Vph-ph max<
5204
Vph-ph min<
5205
Vph-ph max-min>
5206
I min>
5208
T DELAY ALARM
5301
FUSE FAIL MON.
5302
FUSE FAIL 3Vo
5303
FUSE FAIL RESID
5308A FFM Idiff (3ph)
5310
BLOCK PROT.
5401
FCT 81 O/U
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
634
Function
C
Setting Options
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
OFF
ON
Meas-
ON
urem.Superv
OFF
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
1.0 .. 100.0 V
urem.Superv
Meas-
10.0 .. 200.0 V
urem.Superv
Meas-
1A
0.04 .. 1.00 A
urem.Superv
5A
0.20 .. 5.00 A
Meas-
0.00 .. 32.00 sec
urem.Superv
Meas-
OFF
urem.Superv
Solid grounded
Coil.gnd./isol.
Meas-
10 .. 100 V
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.05 .. 1.00 A
urem.Superv
5A
0.25 .. 5.00 A
Meas-
NO
urem.Superv
YES
81 O/U Freq.
OFF
ON
81 O/U Freq.
10 .. 150 V
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
Default Setting
Comments
75 V
27-1 Pickup
1.50 sec
27-1 Time Delay
70 V
27-2 Pickup
70 V
27-2 Pickup
0.50 sec
27-2 Time Delay
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
ON
Current Supervision
OFF
VT broken wire supervi-
sion
8.0 V
Threshold voltage sum
16.0 V
Maximum phase to phase
voltage
16.0 V
Minimum phase to phase
voltage
16.0 V
Symmetry phase to phase
voltages
0.04 A
Minimum line current
0.20 A
1.25 sec
Alarm delay time
OFF
Fuse Fail Monitor
30 V
Zero Sequence Voltage
0.10 A
Residual Current
0.50 A
0.10 A
Differential Current
Threshold (3phase)
0.50 A
YES
Block protection by FFM
OFF
81 Over/Under Frequency
Protection
65 V
Minimum required
voltage for operation
49.50 Hz
81-1 Pickup
59.50 Hz
81-1 Pickup
60.00 sec
81-1 Time Delay
49.00 Hz
81-2 Pickup
59.00 Hz
81-2 Pickup
30.00 sec
81-2 Time Delay
47.50 Hz
81-3 Pickup