Addr. Parameter
1319A 50N-3 measurem.
1320A 50N-2 measurem.
1321A 50N-1 measurem.
1322A 51N measurem.
1330
50N/51N
1331
MofPU Res T/TEp
1501
FCT 67/67-TOC
1502
67-2 PICKUP
1503
67-2 DELAY
1504
67-1 PICKUP
1505
67-1 DELAY
1507
67-TOC PICKUP
1508
67 TIME DIAL
1509
67 TIME DIAL
1510
67-TOC Drop-out
1511
67- IEC CURVE
1512
67- ANSI CURVE
1513A MANUAL CLOSE
1514A 67-2 active
1518A 67 T DROP-OUT
1519A ROTATION ANGLE
624
Function
C
Setting Options
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
50/51 Overcur.
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
67 Direct. O/C
OFF
ON
67 Direct. O/C
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.10 sec
67 Direct. O/C
1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 5.00 A
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.50 sec
67 Direct. O/C
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
67 Direct. O/C
0.05 .. 3.20 sec; ∞
67 Direct. O/C
0.50 .. 15.00 ; ∞
67 Direct. O/C
Instantaneous
Disk Emulation
67 Direct. O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
67 Direct. O/C
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
67 Direct. O/C
67-3 instant.
67-2 instant.
67-1 instant.
67-TOC instant.
Inactive
67 Direct. O/C
with 79 active
always
67 Direct. O/C
0.00 .. 60.00 sec
67 Direct. O/C
-180 .. 180 °
Default Setting
Comments
Fundamental
50N-3 measurement of
Fundamental
50N-2 measurement of
Fundamental
50N-1 measurement of
Fundamental
51N measurement of
50N/51N
Multiple of Pickup <->
T/TEp
OFF
67, 67-TOC Phase Time
Overcurrent
2.00 A
67-2 Pickup
67-2 Time Delay
1.00 A
67-1 Pickup
67-1Time Delay
1.00 A
67-TOC Pickup
5.00 A
0.50 sec
67-TOC Time Dial
5.00
67-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
67-2 instant.
Manual Close Mode
always
67-2 active
0.00 sec
67 Drop-Out Time Delay
45 °
Rotation Angle of Refer-
ence Voltage
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016