Negative Sequence Protection (Definite-Time Characteristic) - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

4.9

Negative Sequence Protection (definite-time characteristic)

Setting Ranges / Increments
Unbalanced load tripping element
46-1.46-2
Delay Times 46-1, 46-2
Dropout Delay Times 46 T DROP-OUT
Functional Limit
Functional Limit
Times
Pickup Times
Dropout Times
Dropout Ratio
Characteristic 46-1, 46-2
Tolerances
Pickup values 46-1,
46-2
Time Delays
Influencing Variables for Pickup Values
Power supply direct voltage in range 0.8 ≤ V
Temperature in range 23.00 °F (-5 °C) ≤ Θ
Frequency in range 25 Hz to 70 Hz
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
Transient overreaction for τ > 100 ms (with full displacement)
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
for Ι
= 1 A
N
for Ι
= 5 A
N
all phase currents ≤ 10 A
for Ι
= 1 A
Nom
for Ι
= 5 A
all phase currents ≤ 50 A
Nom
for Ι
= 1 A
one phase current ≥ 0.1 A
Nom
one phase current ≥ 0.5 A
for Ι
= 5 A
Nom
approx. 35 ms
approx. 35 ms
approx. 0.95 for Ι
= 1 A
3 % of setting value or 10 mA
Ι
Nom
= 5 A
3 % of setting value or 50 mA
Ι
Nom
5 % of reference (calculated) value + 2 % current tolerance, or 30 ms
/V
PC
PSNom
≤ 131.00 °F (55 °C)
amb
4.9 Negative Sequence Protection (definite-time characteristic)
0.05 A to 3.00 A or ∞ (disabled)
0.25 A to 15.00 A or ∞ (disabled)
0.00 s to 60.00 s or ∞ (disabled)
0.00 s to 60.00 s
≥ 0,3
2
Nom
≤ 1.15
Technical Data
Increments 0.01 A
Increments 0.01 s
Increments 0.01 s
1 %
0.5 %/10 K
1 %
1 %
1 %
<5 %
469