Functions
2.1 General
2.1.4.4

Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted
30053
Fault rec. run.
2.1.5

Settings Groups

Up to four different setting groups can be created for establishing the device's function settings.
Applications
Setting groups enable the user to save the corresponding settings for each application so that they can
be quickly called up when required. All setting groups are stored in the device. Only one setting group
may be active at a time.
2.1.5.1

Description

Changing Setting Groups
During operation the user can switch back and forth setting groups locally, via the operator panel, binary
inputs (if so configured), the service interface using a personal computer, or via the system interface. For
reasons of safety it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected as Enabled during
configuration (see Section
are available. While setting values may vary, the selected functions of each setting group remain the same.
2.1.5.2

Setting Notes

General
If setting group change option is not required, Group A is the default selection. Then, the rest of this section is
not applicable.
If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled
(address 103) when the function extent is configured. For the setting of the function parameters, each of the
required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System
Description gives further information on how to copy setting groups or reset them to their status at delivery
and also how to change from one setting group to another.
Section
3.1 Mounting and Connections
externally via binary inputs.
2.1.5.3

Settings

Addr.
Parameter
302
CHANGE
50
Type of
Comments
Informa-
tion
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT_Ev
Waveform data deleted
OUT
Fault recording is running
2.1.1.2 Setting
Notes). In 7SJ62/64 relays, four independent setting groups (A to D)
of this manual tells you how to change between several setting groups
Setting Options
Group A
Group B
Group C
Group D
Binary Input
Protocol
Default Setting
Comments
Group A
Change to Another Setting Group
C53000-G1140-C207-8, Edition 08.2016
SIPROTEC 4, 7SJ62/64, Manual