Communication Interfaces - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

*)
UL–listed with the Following Nominal Values:
**)
UL–listed with the Following Nominal Values:
1)
FLA = "Full Load Ampere"
2)
High-duty relays are used for the direct activation of motor-driven switches. The high-duty relays operate in
an interlocked mode, i.e. only one binary output of each pair of switches is activated, thus avoiding a short-
circuit of the power supply. When used as a standard relay, only one binary output of a pair can be used.
Permanent operation is not specified.

Communication Interfaces

4.1.4
User Interface
Connection
Operation
Transmission speed
Bridgeable distance
Service/Modem Interface
Connection
Operation
Transmission Speed
RS232/RS485/FO according to the ordering variant
RS232/RS485
Connection for flush-mounted
casing
Connection for surface-mounted
casing
Test Voltage (PELV)
RS232 Maximum Distance of Trans-
mission
RS485 Maximum Distance of Trans-
mission
Fiber Optical Link (FO)
FO connector type
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
240 Vac
24 Vdc
48 Vdc
240 Vdc
120 Vac
240 Vac
240 Vdc
120 Vdc
60 Vdc
front side, non-isolated, RS232, 9 pole DSUB port for connecting a
personal computer
(PELV)
With DIGSI
min. 4,800 Bd; max. 115,200 Bd;
Factory Setting: 115,200 Baud; Parity: 8E1
15 m
isolated interface for data transfer
With DIGSI
min. 4,800 baud, max. 115,200 baud; Factory setting 38,400 Baud
rear panel, mounting location "C",
9-pole D-SUB miniature female connector
at the housing mounted case on the case bottom; shielded data cable
500 V; 50 Hz
15 m
1000 m
1)
ST connector
Technical Data
4.1 General Device Data
5 A General Purpose
5 A General Purpose
0.8 A General Purpose
0.1 A General Purpose
1/6 hp (4.4 FLA
1)
)
1/2 hp (4.9 FLA
1)
)
1.6 FLA
1)
3.2 FLA
1)
5.5 FLA
1)
441