Information List - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
6001
S1: RE/RL
6002
S1: XE/XL
6003
S1: x'
6004
S1: x'
6005
S1: Line angle
6006
S1: line length
6007
S1: Line length
6011
S2: RE/RL
6012
S2: XE/XL
6013
S2: x'
6014
S2: x'
6015
S2: Line angle
6016
S2: line length
6017
S2: Line length
6021
S3: RE/RL
6022
S3: XE/XL
6023
S3: x'
6024
S3: x'
6025
S3: Line angle
6026
S3: line length
6027
S3: Line length
2.1.6.4

Information List

No.
Information
126
ProtON/OFF
356
>Manual Close
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
C
Setting Options
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
Type of
Comments
Informa-
tion
IntSP
Protection ON/OFF (via system port)
SP
>Manual close signal
OUT
Relay PICKUP
OUT
Relay GENERAL TRIP command
VI
Primary fault current Ia
VI
Primary fault current Ib
VI
Primary fault current Ic
OUT
Manual close signal detected
SP
>Enable 50/67-(N)-2 (override 79 blk)
SP
>52-a contact (OPEN, if bkr is open)
Default Setting
Comments
1.00
S1: Zero seq. compen-
sating factor RE/RL
1.00
S1: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S1: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S1: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S1: Line angle
62.1 Miles
S1: Line length in miles
100.0 km
S1: Line length in kilometer
1.00
S2: Zero seq. compen-
sating factor RE/RL
1.00
S2: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S2: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S2: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S2: Line angle
62.1 Miles
S2: line length in miles
100.0 km
S2: Line length in kilometer
1.00
S3: Zero seq. compen-
sating factor RE/RL
1.00
S3: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S3: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: line length in miles
100.0 km
S3: Line length in kilometer
Functions
2.1 General
55