Technical Data

4.27 Additional Functions

4.27
Additional Functions
Operational Measured Values
Currents
; Ι
; Ι
Ι
A
B
C
Positive sequence component Ι
Negative sequence component Ι
or 3Ι0
Ι
E
Voltages (phase-to-ground)
V
, V
, V
A-N
B-N
C-N
Voltages (phase-to-phase)
V
, V
, V
, V
A-B
B-C
C-A
V
or V
GND
0
Positive sequence component V
Negative sequence component V
S, apparent power
P, Active power
Q, reactive power
cos φ, power factor
Frequencies f
Temperature overload protection
Θ /Θ
Trip
510
1
2
Range
Tolerance
1)
SYN
1
2
Range
Tolerance
1)
Range
Tolerance
1)
Range
Tolerance
1)
Range
Tolerance
1)
Range
Tolerance
1)
Range
Tolerance
1)
in A (kA) primary and in A secondary or in % Ι
10 % to 200 % Ι
Nom
1 % of measured value or 0.5 % Ι
in kV primary, in V secondary or in % V
10 % to 120 % of V
Nom
1 % of measured value or 0.5 % V
in kVAr (MVAR or GVAR) primary and in % S
0 % to 120 % S
Nom
1 % of S
Nom
for V/V
and Ι/Ι
= 50 to 120 %
Nom
Nom
with sign, total and phase-segregated in kW (MW or GW)
primary and in % S
Nom
0 % to 120 % S
Nom
1 % of S
Nom
for V/V
and Ι/Ι
= 50 to 120 % and | cos φ | = 0.707 to 1
Nom
Nom
with S
=√3 · V
· Ι
Nom
Nom
Nom
with sign, total and phase-segregated in kVAr (MVAr or GVAr)
primary and in % S
Nom
0 % to 120 % S
Nom
1 % of S
Nom
for V/V
and Ι/Ι
= 50 to 120 % und | sin φ | = 0.707 to 1
Nom
Nom
with S
= √3· V
· Ι
Nom
Nom
Nom
total and phase-segregated
–1 to +1
1 % for | cos φ | ≥ 0.707
in Hz
f
± 5 Hz
Nom
20 mHz
in %
C53000-G1140-C207-8, Edition 08.2016
Nom
Nom
Nom
Nom
Nom
SIPROTEC 4, 7SJ62/64, Manual