Siemens SIPROTEC 4 User Manual page 28

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Introduction
1.3 Characteristics
Overcurrent element with definite time or inverse time delay
For inverse time overcurrent protection, characteristics according to IEC or ANSI standards, one userde-
fined and two logarithmic inverse current/time characteristics are available
Direction determination with zero sequence quantities(Ι
nation
Any element can be set as directional or non-directional — forward sensing directional, or reverse
sensing directional
Directional characteristic curve adjustable
Optionally applicable as additional ground fault protection.
Intermittent Ground Fault Protection
Detects and accumulates intermittent ground faults
Tripping after configurable total time.
Directional intermittent ground fault protection
Detects intermittent ground faults
Direction determination
Tripping after settable number of intermittent re-ignitions
Automatic Reclosing 79
Single-shot or multi-shot
With separate dead times for the first and all succeeding shots
Protective elements that initiate automatic reclosing are selectable. The choices can be different for
phase faults and ground faults
Separate programs for phase and ground faults
Interaction to time overcurrent protection element and ground fault elements. They can be blocked in
dependence of the reclosing cycle or released instantaneously
Synchronous reconnection is possible (only for 7SJ623, 7SJ624, 7SJ625, 7SJ626 und 7SJ64) in combina-
tion with the integrated synchronization function..
Fault Location
Initiation by trip command, external command or dropout of pickup
Calculation of the fault distance and output of the fault location in ohms (primary and secondary) and in
kilometers or miles
Up to three line sections can be configured.
Breaker Failure Protection 50 BF
By checking the current and/or evaluating the circuit breaker auxiliary contacts
Started by any integrated protection function that trips
Initiation possible via a binary input from an external protective device.
Flexible Protective Functions
Up to 20 customizable protection functions with three-phase or single-phase operation
Any calculated or directly measured quantity can be evaluated on principle
Standard protection logic with definite time characteristic
28