Binary Input Points; Auto-Reclose Function; Overcurrent Protection; Inrush Function - Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection, motor protection, voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7SJ80:
Table of Contents

Advertisement

3.2

Binary Input Points

Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Name
Index
3.2.1
A
uto-Reclose Function
0
>79 ON
1
CB is NOT ready
2
79 DynBlock
3
79 in progress
4
79 Close
5
79 Successful
6
79 Lockout
7
79 L_N Sequence
8
79 L-L Sequence
3.2.2

Overcurrent Protection

9
50/51 PH ACT
10
50N/51N ACT
11
50 (N) / 51 (N) PU
12
50/51 Ph A PU
13
50/51 Ph B PU
14
50/51 Ph C PU
15
50N/51NPickedup
16
50 (N)/51(N)TRIP
3.2.3

InRush Function

17
PhA InrushBlk
18
PhB InrushBlk
19
PhC InrushBlk
20
INRUSH X-BLK
3.2.4

Directional Overcurrent Protection

21
67 ACTIVE
22
67N ACTIVE
23
67/67N pickedup
24
67 A picked up
25
67 B picked up
26
67 C picked up
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
C53000-L2040-A320-2
>79 ON; Automatic reclosure ON; ON = 1, OFF = 0
Circuit breaker is NOT ready; ON = 1, OFF = 0
79 – Auto-reclose is dynamically BLOCKED; ON = 1, OFF = 0
79 – in progress; ON = 1, OFF = 0
79 – Close command; ON = 1
79 – cycle successful; ON = 1, OFF = 0
79 – Lockout; ON = 1, OFF = 0
79-A/R single phase reclosing sequence; Program earthfault is running = 1, Pro-
gram is deactivated = 0
79-A/R multi-phase reclosing sequence; ON = 1, OFF = 0
50/51 O/C is ACTIVE; ON = 1, OFF = 0
50N/51N is ACTIVE; ON = 1, OFF = 0
50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0
50/51 Phase A picked up; ON = 1, OFF = 0
50/51 Phase B picked up; ON = 1, OFF = 0
50/51 Phase C picked up; ON = 1, OFF = 0
50N/51N picked up; ON = 1, OFF = 0
50(N)/51(N) TRIP; ON = 1
Phase A trip blocked by inrush detection; ON = 1, OFF = 0
Phase B trip blocked by inrush detection; ON = 1, OFF = 0
Phase C trip blocked by inrush detection; ON = 1, OFF = 0
Cross blk: PhX blocked Phy; ON = 1, OFF = 0
67/67-TOC is ACTIVE; activate = 1, deactivate = 0
67N/67N-TOC is ACTIVE; activate = 1, deactivate = 0
67/67N picked up; ON = 1, OFF = 0
67/67-TOC Phase A picked up; ON = 1, OFF = 0
67/67-TOC Phase B picked up; ON = 1, OFF = 0
67/67-TOC Phase C picked up; ON = 1, OFF = 0
Description
Binary Input Points
Class
3
2
3
2
3
3
1
3
3
3
3
2
2
2
2
2
2
3
3
3
3
3
3
2
2
2
2