Time Overcurrent Protection - Siemens SIPROTEC 7SJ61 Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

Point List
3.2.2

Time Overcurrent protection

ASDU
Function
Informa-
type
tion
number
1
60
1
1
60
2
1
60
3
1
60
4
1
60
5
1
60
6
1
60
21
1
60
22
1
60
23
1
60
26
1
60
27
1
60
28
2
60
49
2
60
53
2
60
57
2
60
58
2
60
59
2
60
60
2
60
62
2
60
63
2
60
64
2
60
65
2
60
66
2
60
75
2
60
76
2
60
77
1
60
243
1
60
244
1
60
245
1
60
246
1
60
247
2
160
64
2
160
65
2
160
66
28
Name
>BLOCK 50-2
>BLOCK 50-1
>BLOCK 51
>BLOCK 51N-2
>BLOCK 50N-1
>BLOCK 51N
50/51 PH OFF
50/51 PH BLK
50/51 PH ACT
50N/51N OFF
50N/51N BLK
50N/51N ACT
50-2 Time Out
50-1 Time Out
51 Time Out
51 TRIP
50N-2 picked up
50N-2 TimeOut
50N-1 picked up
50N-1 TimeOut
51N picked up
51N TimeOut
51N TRIP
50-2 picked up
50-1 picked up
51 picked up
>BLK CLP stpTim
CLP OFF
CLP BLOCKED
CLP running
Dyn set. ACTIVE
50/51 Ph A PU
50/51 Ph B PU
50/51 Ph C PU
Description
>BLOCK 50-2; ON = 1, OFF = 0
>BLOCK 50-1; ON = 1, OFF = 0
>BLOCK 51; ON = 1, OFF = 0
>BLOCK 50N-2; ON = 1, OFF = 0
>BLOCK 50N-1; ON = 1, OFF = 0
>BLOCK 51N; ON = 1, OFF = 0
O/C switched OFF; ON = 1, OFF = 0
O/C is BLOCKED; ON = 1, OFF = 0
50/51 O/C is ACTIVE; ON = 1, OFF = 0
50N/51N is OFF; ON = 1, OFF = 0
50N/51N BLK; ON = 1, OFF = 0
50N/51N is ACTIVE; ON = 1, OFF = 0
50-2 Time Out; ON = 1
50-1 Time Out; ON = 1
51 Time Out; ON = 1
51 TRIP; ON = 1, OFF = 0
50N-2 picked up; ON = 1, OFF = 0
50N-2 Time Out; ON = 1
50N-1 picked up; ON = 1, OFF = 0
50N-1 Time Out; ON = 1
51N picked up; ON = 1, OFF = 0
51N Time Out; ON = 1
51N TRIP; ON = 1, OFF = 0
50-2 picked up; ON = 1, OFF = 0
50-1 picked up; ON = 1, OFF = 0
51 picked up; ON = 1, OFF = 0
>BLOCK Cold-Load-Pickup stop timer; ON = 1, OFF = 0
Cold-Load-Pickup switched OFF; ON = 1, OFF = 0
Cold-Load-Pickup is BLOCKED; Blocked = 1, Unblocked = 0 1995
Cold-Load-Pickup is RUNNING; ON = 1, OFF = 0
Dynamic settings are ACTIVE; ON = 1, OFF = 0
50/51 Phase A picked up; ON = 1, OFF = 0
50/51 Phase B picked up; ON = 1, OFF = 0
50/51 Phase C picked up; ON = 1, OFF = 0
1721
1722
1723
1724
1725
1726
1751
1752
1753
1756
1757
1758
1804
1814
1824
1825
1831
1832
1834
1835
1837
1838
1839
1800
1810
1820
1731
1994
1996
1997
1762
1763
1764
7SJ61 / 7SJ62 / 7SJ64 Bus mapping