Siemens SIPROTEC 4 User Manual page 625

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
1520A 67-2 MEASUREM.
1521A 67-1 MEASUREM.
1522A 67-TOC MEASUR.
1523
67-2 Direction
1524
67-1 Direction
1525
67-TOC Direct.
1526
67-3 Direction
1527A 67-3 MEASUREM.
1528
67-3 PICKUP
1529
67-3 DELAY
1530
67
1531
MofPU Res T/Tp
1532A 67-3 active
1601
FCT 67N/67N-TOC
1602
67N-2 PICKUP
1603
67N-2 DELAY
1604
67N-1 PICKUP
1605
67N-1 DELAY
1607
67N-TOC PICKUP
1608
67N-TOC T-DIAL
1609
67N-TOC T-DIAL
1610
67N-TOC DropOut
1611
67N-TOC IEC
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Function
C
Setting Options
67 Direct. O/C
Fundamental
True RMS
67 Direct. O/C
Fundamental
True RMS
67 Direct. O/C
Fundamental
True RMS
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Fundamental
True RMS
67 Direct. O/C
1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞ ∞ A
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.00 sec
67 Direct. O/C
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
67 Direct. O/C
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
67 Direct. O/C
always
with 79 active
67 Direct. O/C
OFF
ON
67 Direct. O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.50 A
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.10 sec
67 Direct. O/C
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 1.00 A
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.50 sec
67 Direct. O/C
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
67 Direct. O/C
0.05 .. 3.20 sec; ∞
67 Direct. O/C
0.50 .. 15.00 ; ∞
67 Direct. O/C
Instantaneous
Disk Emulation
67 Direct. O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Functions, Settings, Information
Default Setting
Comments
Fundamental
67-2 measurement of
Fundamental
67-1 measurement of
Fundamental
67-TOC measurement of
Forward
67-2 Direction
Forward
67-1 Direction
Forward
67-TOC Direction
Forward
67-3 Direction
Fundamental
67-3 measurement of
∞ A
67-3 Pickup
67-3 Time Delay
67
Multiple of Pickup <->
T/Tp
always
67-3 active
OFF
67N, 67N-TOC Ground
Time Overcurrent
0.50 A
67N-2 Pickup
67N-2 Time Delay
0.20 A
67N-1 Pickup
67N-1 Time Delay
0.20 A
67N-TOC Pickup
1.00 A
0.20 sec
67N-TOC Time Dial
5.00
67N-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
F.2 Settings
625

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents