Inrush Restraint - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Technical Data

4.5 Inrush Restraint

4.5
Inrush Restraint
Controlled Elements
Time Overcurrent Elements
Setting Ranges / Increments
Stabilization factor Ι
Functional Limits
Lower Function Limit Phases
Lower Function Limit ground
Upper Function Limit,
configurable
Crossblock
Crossblock Ι
, Ι
A
464
2f
for Ι
Nom
for Ι
Nom
for Ι
Nom
for Ι
Nom
for Ι
Nom
for Ι
Nom
, Ι
B
C
50-1, 50N-1, 51, 51N, 67-1, 67N-1
10 % to 45 %
at least one phase current (50 Hz and 100 Hz) ≥ 25 mA
= 1 A
= 5 A
at least one phase current (50 Hz and 100 Hz) ≥ 125 mA
= 1 A
Ground current (50 Hz and 100 Hz) ≥ 25 mA
= 5 A
Ground current (50 Hz and 100 Hz) ≥ 125 mA
= 1 A
0.30 A bis 25.00 A
1.50 A bis 125.00 A
= 5 A
ON/OFF
Increments 1 %
increments 0.01 A
increments 0.01 A
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016