Siemens SIPROTEC 4 User Manual page 628

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
2101
67Nc-2 PICKUP
2102
67Nc-2 DELAY
2103
67Nc-1 PICKUP
2104
67Nc-1 DELAY
2105
67Nc-TOC PICKUP
2106
67Nc-TOC T-DIAL
2107
67Nc-TOC T-DIAL
2108
67Nc-3 PICKUP
2109
67Nc-3 DELAY
2201
INRUSH REST.
2202
2nd HARMONIC
2203
CROSS BLOCK
2204
CROSS BLK TIMER
2205
I Max
2701
50 1Ph
2702
50 1Ph-2 PICKUP
2703
50 1Ph-2 PICKUP
2704
50 1Ph-2 DELAY
2705
50 1Ph-1 PICKUP
2706
50 1Ph-1 PICKUP
2707
50 1Ph-1 DELAY
3101
Sens. Gnd Fault
3102
CT Err. I1
3102
CT Err. I1
3103
CT Err. F1
3104
CT Err. I2
3104
CT Err. I2
3105
CT Err. F2
3106
VPH MIN
628
Function
C
Setting Options
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup
0.25 .. 35.00 A; ∞
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
50/51 Overcur.
OFF
ON
50/51 Overcur.
10 .. 45 %
50/51 Overcur.
NO
YES
50/51 Overcur.
0.00 .. 180.00 sec
50/51 Overcur. 1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
50 1Ph
OFF
ON
50 1Ph
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 2.50 A
50 1Ph
0.003 .. 1.500 A; ∞ 0.300 A
50 1Ph
0.00 .. 60.00 sec; ∞ 0.10 sec
50 1Ph
1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 1.00 A
50 1Ph
0.003 .. 1.500 A; ∞ 0.100 A
50 1Ph
0.00 .. 60.00 sec; ∞ 0.50 sec
Sens. Gnd Fault
OFF
ON
ON with GF log
Alarm Only
Sens. Gnd Fault
0.001 .. 1.600 A
Sens. Gnd Fault 1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Sens. Gnd Fault
0.0 .. 5.0 °
Sens. Gnd Fault
0.001 .. 1.600 A
Sens. Gnd Fault 1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Sens. Gnd Fault
0.0 .. 5.0 °
Sens. Gnd Fault
10 .. 100 V
Default Setting
Comments
7.00 A
67Nc-2 Pickup
67Nc-2 Time Delay
1.50 A
67Nc-1 Pickup
67Nc-1 Time Delay
1.00 A
67Nc-TOC Pickup
5.00 A
0.50 sec
67Nc-TOC Time Dial
5.00
67Nc-TOC Time Dial
∞ A
67Nc-3 Pickup
67Nc-3 Time Delay
OFF
Inrush Restraint
15 %
2nd. harmonic in % of
fundamental
NO
Cross Block
0.00 sec
Cross Block Time
7.50 A
Maximum Current for
Inrush Restraint
37.50 A
OFF
50 1Ph
0.50 A
50 1Ph-2 Pickup
50 1Ph-2 Pickup
50 1Ph-2 Time Delay
0.20 A
50 1Ph-1 Pickup
50 1Ph-1 Pickup
50 1Ph-1 Time Delay
OFF
(Sensitive) Ground Fault
0.050 A
Current I1 for CT Angle
Error
1.00 A
Current I1 for CT Angle
Error
5.00 A
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle
Error
10.00 A
Current I2 for CT Angle
Error
50.00 A
0.0 °
CT Angle Error at I2
40 V
L-Gnd Voltage of Faulted
Phase Vph Min
SIPROTEC 4, 7SJ62/64, Manual