Information List - Siemens SIPROTEC 4 User Manual

Multi-functional protective relay with local control 7sj62/64
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.12 Monitoring Functions
Addr.
Parameter
5205
Vph-ph max-min>
5206
I min>
5208
T DELAY ALARM
5301
FUSE FAIL MON.
5302
FUSE FAIL 3Vo
5303
FUSE FAIL RESID
5308A
FFM Idiff (3ph)
5310
BLOCK PROT.
8101
MEASURE. SUPERV
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
8106
Σ I THRESHOLD
8107
Σ I FACTOR
8109
FAST Σ i MONIT
8110A
T BAL. V LIMIT
8111A
T BAL. I LIMIT
2.12.1.10

Information List

No.
Information
161
Fail I Superv.
162
Failure Σ I
163
Fail I balance
167
Fail V balance
169
VT FuseFail>10s
170
VT FuseFail
171
Fail Ph. Seq.
175
Fail Ph. Seq. I
176
Fail Ph. Seq. V
192
C
Setting Options
10.0 .. 200.0 V
1A
0.04 .. 1.00 A
5A
0.20 .. 5.00 A
0.00 .. 32.00 sec
OFF
Solid grounded
Coil.gnd./isol.
10 .. 100 V
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
NO
YES
OFF
ON
10 .. 100 V
0.58 .. 0.90
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
0.10 .. 0.90
1A
0.05 .. 2.00 A; ∞
5A
0.25 .. 10.00 A; ∞
0.00 .. 0.95
OFF
ON
0 .. 100 sec
0 .. 100 sec
Type of
Comments
Informa-
tion
OUT
Failure: General Current Supervision
OUT
Failure: Current Summation
OUT
Failure: Current Balance
OUT
Failure: Voltage Balance
OUT
VT Fuse Failure (alarm >10s)
OUT
VT Fuse Failure (alarm instantaneous)
OUT
Failure: Phase Sequence
OUT
Failure: Phase Sequence Current
OUT
Failure: Phase Sequence Voltage
Default Setting
Comments
16.0 V
Symmetry phase to phase
voltages
0.04 A
Minimum line current
0.20 A
1.25 sec
Alarm delay time
OFF
Fuse Fail Monitor
30 V
Zero Sequence Voltage
0.10 A
Residual Current
0.50 A
0.10 A
Differential Current
Threshold (3phase)
0.50 A
YES
Block protection by FFM
ON
Measurement Supervision
50 V
Voltage Threshold for
Balance Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Threshold for
Balance Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
ON
Fast Summated Current
Monitoring
5 sec
T Balance Factor for
Voltage Monitor
5 sec
T Current Balance Monitor
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents