5.7.3.2

Setting the forced dormant error detection (test stop)

Precondition
You have selected the extended functions via onboard terminals.
Procedure
To set the forced dormant error detection (test stop) of the safety output, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Press the "Configuration" button.
3. Interconnect this signal, for example with a digital input or a control bit in the fieldbus.
4. Set the monitoring time for the forced dormant error detection.
5. Close the two screen forms.
You have defined which signal the inverter uses to start the forced dormant error detection
(test stop) of its safety output.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
This signal starts the forced dormant error detection (test stop) of the safety output and
resets the remaining monitoring time to the value
We recommend that the safety output is tested together with the forced dormant error
detection of the safety functions. To do this, interconnect the signal source with the same
signal as the forced dormant error detection of the safety functions. See also Section:
Setting the forced dormant error detection (test stop) (Page 104).
The time must be longer than or equal to the time for monitoring the forced dormant error
detection of the extended functions. See also Section: Setting the forced dormant error
detection (test stop) (Page 104).
5.7 Setting extended functions
.
Commissioning
125