Commissioning
5.7 Setting extended functions
Debounce times for standard and safety functions
The debounce time p0724 for "standard" digital inputs does not influence the signals of the
safety inputs F-DI. Conversely, the same applies: The F-DI debounce time does not affect
the signals of the "standard" inputs.
If you use an input as a standard input, set the debounce time using parameter p0724 .
If you use an input as a safety input, set the debounce time as described above.
118
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA